BENDER ISOSCAN ® EDS460/490-EDS461/491 series
来源:
|
作者:FAN
|
发布时间 :2025-12-23
|
8 次浏览:
|
Share:
The insulation fault locators ISOSCAN® EDS460/490 in combination with the ISOMETER® IRDH575 or the locating current injector PGH are applied for localising insulation faults in unearthed systems (IT systems). The locating current signals generated by the insulation monitoring device IRDH575 or the locating current injector PGH are detected by measuring current transformers and evaluated by the insulation fault locators. Up to 12 measuring current transformers can be connected to one EDS460/490. A total of 90 EDS insulation fault locators can be connected via one RS-485 interface (BMS protocol). Hence, up to 1080 circuits can be monitored. The maximum scanning time is …10 s, see TGH1394.
DIN EN 61557-9(VDE 0413-9)、IEC 61557-9
IEC 61326-2-4、DIN EN 60664-1(VDE 0110-1)、DIN EN 60664-3
ASTM F1669M-96 (2007)、ASTM F1207M-96 (2007)