Environmental and Physical Parameters | Parameter Categories | Specific Specifications |
| Operating Temperature | -25...+55 ℃ | | Climate Class (IEC 60721) | Fixed Use 3K5, Transport 2K3, Long Term Storage 1K4 (No Condensation, No Ice) | | Mechanical Class (IEC 60721) | Fixed Use 3M4, Transport 2M2, Long Term Storage 1M3 | Protection Class (Terminal) | IP20 (DIN EN 60529) | | Shell Material | Polycarbonate (UL94 V-0 Flame Retardant Class) | | Weight | EDS46x Series ≤ 360g | | Installation Method | Screw Installation (2 × M4) or DIN Rail Installation (Compliant with IEC 60715) The sentence is:|
Interface and networking parameters | Interface type | Specific specifications |
| Communication interface | RS-485, supporting BMS protocol | | Baud rate | 9.6kbit/s | | Maximum cable length | 1200m (exceeding DI-1DL repeater required) | | Recommended cable | Twisted pair J-Y (St) Y, minimum 2 × 0.8mm ², shielding layer connected to PE | | Terminal resistance | 120 Ω (0.25W), enabled through DIP switch | Device address range | 1... 90 (BMS bus address)|
Core functions and operational features
Measurement and positioning function
Insulation fault location: By measuring the current transformer to collect the positioning current generated by the PGH injector or IRDH575, when the current exceeds the set response value, the ALARM 2 indicator light is triggered to light up, the D-type equipment displays the fault channel plaintext, and the corresponding channel LED of the L-type equipment lights up.
Residual current measurement: Monitor the AC residual current in the IT system, and when it exceeds 10A (EDS460/490) or 1A (EDS461/491), trigger the ALARM 1 indicator light to turn on.
Channel connection monitoring: Continuously monitor and measure the connection status between the current transformer and the equipment, and trigger the ALARM 1 indicator light to light up when there is a disconnection or short circuit (this function can be disabled).
Storage and alarm function
Historical storage: The D-type device has a built-in historical memory that can store 300 event records, including date, time, channel, event code, measurement value, and supports traceability queries.
Fault memory: "Fault memory activation" (alarm information retained until manual reset or bus reset) or "Fault memory deactivation" (alarm information retained until fault elimination) can be selected.
Alarm relay: supports normally open (N/O) or normally closed (N/C) operation mode selection, and the common alarm relay can be linked to external alarm devices or control systems.
Operation and configuration features
Operation buttons: D-type devices include buttons such as INFO (information query), TEST (self-test), RESET (reset), MENU (menu), etc; L-shaped devices only include basic settings and reset buttons.
Parameter configuration: D-type devices can locally set bus addresses, response delays, fault memory modes, etc; L-type equipment needs to be configured through D-type equipment, IRDH575, MK2430 alarm test combination, or COM460IP protocol converter.
External control: Supports connecting external test/reset buttons (cable length 0... 10m), external buttons of multiple devices cannot be connected to each other.

Core components and accessories
Supporting measurement current transformer: BENDER dedicated measurement current transformer is required, and different models are compatible with different equipment series. The core models are as follows: | Equipment series | Recommended transformer types | Transformer structure | Inner diameter specification (mm) | Model example | Accessory code | | --------------; Rectangle: 70x175, etc; Opening and closing type: 20x30/50x80, etc. | W20 (circular 20mm) | B98080003 | | EDS461/491 | W/WS-8000 series | Circular/opening and closing type | Circular: 20/35/60; Opening and closing: 20x30/50x80 | W20-8000 (round 20mm) | B98080009|
Auxiliary Accessories | Accessory Type | Function Description | Model | Accessory Code |
| RS-485 Repeaters | Extended Bus Distance (over 1200m) or Number of Extended Devices (over 32 units) | DI-1DL | B95012047 | | USB Powered, No Additional Power Supply | DI-2USB | B95012045 | Protocol Converter | BMS Bus to TCP/IP (Ethernet) | COM460IP | B95061010 | | | BMS Bus to Modbus/RTU | FTC470XMB | B95061002 | | BMS Bus to PROFIBUS DP | FTC470XDP | B95061000 | | Power Adapter | Power Supply for Repeaters DI-1/DI-2 | AN471 B924189|
Power supply specifications and ordering information
Power supply voltage options: The device provides two power supply specifications, suitable for different industrial scenarios: | Power supply type | Specification parameters | Corresponding model suffix |
Typical ordering code example:
EDS460-D-1: EDS460 series, D-type display, low voltage power supply, 2... 10mA sensitivity
EDS491-L-2: EDS491 series, L-shaped display, high voltage power supply, 0.2... 1mA sensitivity, independent alarm contacts per channel
Compliance standards
The equipment complies with multiple international and German industrial standards to ensure measurement accuracy and safety performance:
DIN EN 61557-8(VDE 0413-8)、EN 61557-8、IEC 61557-8