System scanning: Open the software, click on "Scan Network", select the COM port with a baud rate of 9600bps, and the software will automatically scan the RM module in the network, displaying the module model, address, and serial number.
(2) Core configuration: Modbus TCP settings (RMA module required)
Select the RMA module, enter the "Communications" tab, set "IP Address Mode=Fixed", IP=192.168.1.10, Subnet Mask=255.255.255.0, Gateway=192.168.1.1.
Enable "Modbus TCP Enable", set "Modbus Port=502" (default port), and "EtherNet/IP Enable" (if EtherNet/IP communication is required).
Enter the "Gateway" tab, enable "Gateway Instance 1-4", corresponding to RME module addresses 1-4, and set "Modbus Offset=0" (address offset free).
Click "Save" to save the configuration, restart the RMA module, verify network connectivity through "Ping 192.168.1.10" on the PC, and use Modbus testing tools (such as Modbus Poll) to read the I/O register of RME (such as address 40001=digital input 1 status).
3. Communication testing tools
Modbus RTU Test: Use Watlow Modbus RTU Diagnostic Tool, set baud rate=9600, address=1, read register 2500 (process value), and if the correct data is returned, communication is normal.
EtherNet/IP testing: Use Rockwell RSLogix software, add EtherNet/IP driver for RMA module, import GSD file (Part Number: 0601-0002-0000), read implicit assembly (Input Assembly=1, Output Assembly=2), and verify data interaction.

Maintenance and troubleshooting
1. Daily maintenance (preventive maintenance)
(1) Regular inspection (monthly)
Appearance and status inspection: Check the module indicator lights (Power light green constant light=normal, red constant light=power failure; The green flashing Comm light indicates active communication, and the constant red light indicates communication failure, with no error messages.
Wiring inspection: The terminals are not loose or oxidized, the shielding layer is well grounded, there is no parallel wiring between the communication line and the power line (spacing ≥ 10cm), and the wires have no insulation damage.
SD card check (if any): Check if the SD card is in place, with a remaining space of ≥ 10%, and regularly export data logs (to avoid full storage causing the logs to stop recording). It is recommended to back up once a month.
(2) Annual maintenance
Power test: Use a multimeter to measure the voltage at Slot C 98/99 terminals, ensuring that the ripple is ≤ 5% within the range of 20.4-30.8V; Check if the fuse (if any) is blown and there are no signs of heating in the power wiring.
Communication test: Use diagnostic tools to verify that all protocol communication is normal, Modbus RTU response time ≤ 100ms, Ethernet packet loss rate=0, EtherNet/IP cycle time ≤ 50ms.
Load test: Measure the current/voltage of the output terminal and compare it with the configured value, with a deviation of ≤± 1% (for example, the deviation between the SSR output current and the set value should be within ± 0.1A); Check that the relay/SSR contacts are not corroded and replace them if necessary.
2. Troubleshooting (problem location and resolution)
(1) Common faults and solutions
Possible causes of malfunction, troubleshooting steps, and solutions
The module has no display and the Power light is not on. 1. The power supply is not connected or the voltage is abnormal
2. The fuse is blown
3. Internal module fault 1. Measure the voltage at Slot C 98/99 terminals and confirm 20.4-30.8V
2. Check if the power input fuse (if any) is blown
3. Replace the spare module for testing. 1. Reconnect the wiring to ensure correct polarity
2. Replace the 1A slow melting fuse (Littelfuse 0215001. MXP)
3. Apply for RMA repair (provide module serial number and fault description)
Modbus communication failed, Comm light is red. 1. Address/baud rate mismatch
2. Wiring error (reversed polarity)
3. The terminal resistor is not connected or damaged
4. Excessive bus load 1. Verify the Modbus address, baud rate, and checksum between RME and PLC
2. Check the terminal wiring of Slot C CA/CB/CC to ensure that CA=T -/R -, CB=T+/R+
3. Measure the bus voltage (normal 2.5-5V), connect the first and last modules to a 120 Ω resistor
4. Check the number of bus nodes (≤ 32), if exceeded, add a repeater. 1. Unify communication parameters and restart the module to take effect
2. Correct the polarity of the wiring
3. Replace the terminal resistor
4. Add EIA-485 repeaters (such as B&B Electronics 485RPT)
Digital output unresponsive, load not operating. 1. I/O direction configuration error (set as input)
2. Output function not associated (fn=Off)
3. Load overload or short circuit
4. Relay/SSR damage 1. Enter Setup → Digital I/O Menu, confirm "dir=Output"
2. Check if 'fn' is associated with the correct function (such as Alarm, Logic)
3. Measure the load resistance and confirm that there is no short circuit and the current is ≤ the rated output value
4. Measure the output terminal voltage. If there is no voltage, replace the relay/SSR. 1. Reconfigure the I/O direction and restart to take effect
Email:wang@kongjiangauto.com