FOXBORO 21h2y6b4 Intrinsically Safe I/O Subsystem
The Intrinsically Safe I/O Subsystem provides integration between the Pepperl+Fuchs™ (P+F) modular intrinsically safe remote I/O systems and the I/A Series® system. The Intrinsically Safe Communications Module (ISCM) enables I/A Series control processors to view the P+F I/O modules as equivalent 200 Series Fieldbus Modules (FBMs), which can be monitored with standard I/A Series blocks and standard InFusion™ or I/A Series system/control configurator applications such as the InFusion Engineering Environment and the Integrated Control Configurator.
FEATURES
Intrinsically safe - supports Zone 2, Div. 2 or Zone 22 (LB-style) environments or Zone 1, or Zone 21 (FB-style) environments
ISCMs interface the 2 Mbps HDLC Module Fieldbus to the FCP270 or ZCP270
Up to 46 (for LB-style Zone 2 Applications) or 48 (for FB-style Zone 1 Applications) P+F intrinsically safe I/O modules supported per
Redundant ISCMs allow either module to control the process. Role reversal is automatic on detected failures
Letterbug set through a letterbug module with rotary switch plugged into the ISCM.
Monitored by standard System Manager or I/A Series SMDH and FoxView™ displays
“CE” logo marked on product.
OVERVIEW
The Intrinsically Safe I/O Subsystem provides integration between the Pepperl+Fuchs (P+F) modular intrinsically safe remote I/O systems and the I/A Series system. The Intrinsically Safe Communications Module (ISCM) communicates between the two systems, as it enables I/A Series control processors to view supported P+F intrinsically safe I/O modules as equivalent 200 Series Fieldbus Modules (FBMs) over the I/A Series 2 Mbps HDLC Fieldbus. This allows the I/O modules to be monitored with standard I/A Series blocks and standard I/A Series or InFusion system/control configurator applications such as InFusion Engineering Environment and ICC.
HIGH RELIABILITY
In redundant ISCM configurations, the redundancy of the module pair provides very high subsystem availability time.
Either ISCM may be hot-swapped without upsetting input or output communications to the other module, or removing power from either module.
PEPPERL+FUCHS MODULAR REMOTE I/O SYSTEMS
The Pepperl+Fuchs modular remote I/O systems - for Zone 2 or Zone 1 applications - are the costeffective connection of field signals in the hazardous and the intrinsically safe areas to your process control system via the HDLC Fieldbus. Combinable I/O modules and high modularity offers cost-saving installations. The P+F remote I/O systems are characterized by high functionality and simple handling.
Only intrinsically safe I/O modules from P+F that are listed in this PSS are supported by the ISCM. If it is desired to also include non-IS signals in the same I/A Series system, then standard 200 Series FBMs must be used for these signals.
MODULAR UNIT MOUNTING
The ISCM mounts on supported P+F-supplied LBstyle or FB-style base or extension units, which accommodate different quantities of P+F I/O modules, depending on the application. The ISCM base unit includes signal connectors for the ISCM and P+F I/O modules, redundant independent power connections, and 2 Mbps HDLC module Fieldbus connections for communications to the I/A Series FCP270 or ZCP270.