The Eaton JM60400-3MW22 is a high‑quality molded case circuit breaker (MCCB) designed for reliable protection in commercial and industrial power distribution systems. With a continuous current rating of 400 A and a voltage rating of 600 VAC, it is suitable for use as a main disconnect or feeder breaker in panelboards, switchboards, and motor control centers. The JM series breakers combine thermal‑magnetic trip technology with compact dimensions and optional accessories for versatile application.
Frame: JM, 3‑pole
Current rating: 400 A (fixed thermal)
Voltage: 600 VAC maximum, 50/60 Hz
Interrupting capacity: 35 kA RMS symmetrical at 480 VAC (standard), 18 kA at 600 VAC
Trip type: thermal‑magnetic (fixed thermal, adjustable magnetic)
Magnetic trip adjustment: 5x to 10x of rated current (field adjustable via dial)
Connection: I‑Line plug‑in (for Eaton panelboards) or bolt‑on lugs (optional)
Terminals: suitable for copper or aluminum conductors up to 500 kcmil
Accessories: auxiliary switches, alarm contacts, shunt trip, undervoltage release, motor operator
Standards: UL489, CSA C22.2 No. 5, IEC 60947‑2
Number of poles: 3
Rated insulation voltage (Ui): 750 V
Rated impulse withstand (Uimp): 8 kV
Thermal element: non‑interchangeable, calibrated for 40 °C ambient
Magnetic trip range: 2000‑4000 A
Interrupting rating (UL489): 35 kA at 480 VAC; 18 kA at 600 VAC
Frequency: 50/60 Hz
Dimensions: 270 x 160 x 100 mm (H x W x D)
Weight: approximately 8 kg
Operating temperature: -25 °C to +55 °C

The thermal‑magnetic trip unit provides two levels of protection: the thermal bimetal element responds to overload currents with an inverse‑time characteristic, allowing harmless inrush currents while tripping on sustained overloads. The magnetic solenoid reacts instantaneously to short‑circuit currents above the adjustable threshold, minimizing damage to downstream equipment. The trip mechanism is common to all poles, ensuring all phases are disconnected on a fault.
Main breaker in lighting and distribution panelboards
Feeder protection for commercial buildings and industrial plants
Motor circuit protection (when used with separate overload relay)
Transformer secondary protection
Generator output breakers
The JM60400-3MW22 with I‑Line connectors can be easily plugged into Eaton panelboards equipped with I‑Line bus stacks. For other applications, bolt‑on terminal kits are available. A wide range of field‑installable accessories includes internal auxiliary contacts for status indication, shunt trips for remote opening, and undervoltage releases for safety interlocks. The breaker can also be padlocked in the OFF position for lockout/tagout procedures.
With its robust construction and dependable protection, the Eaton JM60400-3MW22 is a trusted choice for electrical professionals requiring a high‑quality MCCB for critical power distribution.