TRICONEX I/O Module
DESCRIPTION
The Triconex product family includes a comprehensive range of modules. This section includes: a summary of the system components and their uses, a table that lists standard products and their model numbers, and a summary of specifications for each standard product in the Tricon family.
Summary of Tricon Components
Chassis
• Main Chassis—houses Main Processors, memory back-up batteries, communication modules and I/O modules.
• Expansion Chassis—for additional I/O modules up to 100 feet (30 meters) away from the Main Chassis. In restricted applications, operation up to 1,000 feet (300 meters) is supported.
• RXM Chassis—for I/O modules up to 7.5 miles (12 kilometers) away from the Main Chassis.
• Mechanical Keying—Each slot in the Tricon is mechanically keyed to correspond with a specific type of module. This prevents the installation of modules into improper slots.
Power Supply Modules
• Provide logic power to modules in the Main, Expansion or RXM Chassis. Available in 24 VDC, 115 VAC and 230 VAC versions. The power rating of each power supply is 175 watts at 140 ° F (60° C).
Main Processors
The Main Processors execute the system diagnostics and the user-written control program.
Communication Modules
• Tricon Communication Modules (TCM) support a number of Triconex protocols and applications and user-written applications on Ethernet (802.3) networks, including TriStation, Modbus TCP and OPC. It also supports RS-232 and RS-485 serial communication with Modbus devices, TriStation 1131, and GPS for time synchronization.
• Enhanced Intelligent Communication Modules (EICM) support RS-232, RS-422 and RS- 485 serial communication with Modbus devices and TriStation 1131.
• Network Communication Modules (NCM) support a number of Triconex protocols and applications and user-written applications on Ethernet (802.3) networks, including TriStation 1131.
• Safety Manager Modules (SMM) act as an interface between a Tricon controller and a Honeywell Universal Control Network (UCN), one of three principal networks of the TDC-3000 DCS.
• Hiway Interface Modules (HIM) act as an interface between a Tricon controller and a Honeywell TDC-3000 Hiway Gateway and Local Control Network (LCN).
Interface Modules
• HART Analog Input Interface Modules act as an interface between 4-20 mA analog input points from HART smart devices in the field and HART Host software running on a PC.
• HART Analog Output Interface Modules act as an interface between 4-20 mA analog output points from HART smart devices in the field and HART Host software running on a PC.
I/O Modules
• Digital Input Modules receive discrete signals of these nominal voltages: 115 VAC/VDC, 48 VAC/VDC, and 24 VAC/VDC. All voltages are available in TMR modules. Non-TMR modules are available in 24 VDC and 48 VDC only. Speed input and totalization modules are also available.
• Supervised Digital Output Modules produce discrete output signals of these nominal voltages, with diagnostic coverage of the field circuit and load device: 115 VAC, 120 VDC, 48 VDC, and 24 VDC.
email:1583694102@qq.com