2. Installation method and compatible accessories
(1) Classification of installation methods
Installation method, applicable scenarios, key requirements, and compatible accessories
The heat sink inside the cabinet is built into a clean room, with sufficient space and no need for additional brackets. The cabinet needs ventilation-
External cooling fins inside the cabinet are installed in a clean room. Due to limited cabinet space, external cooling fin adapters ZPSA series (UL Type 1) and ZPSD series (IP55/UL Type 12) are required
Directly install inorganic cabinets in clean rooms, without dedicated cabinets requiring Type 1 adapters to convert protection level 900-192-121 series Type 1 adapters
Type 12 flange with external dusty heat sink installed on the back, compatible with Type 12 cabinet AWA suffix flange models
(2) Installation accessory selection
Type 1 adapter: 240V 2211ABA model compatible with 900-192-121-009480V 4361ABA model compatible with UUX001700.
External heat sink adapter: 240V 2011AFA model compatible with ZPSA-600-EH1-FR1 (UL Type 1), ZPSD-600-EH12-FR1 (IP55/UL Type 12).
DIN rail installation: Only supports low-power compact models and requires a dedicated DIN rail kit.
Key components and power optimization options
1. Operation and communication accessories
(1) Operation panel and cables
Type, Model, and Function Description of Accessories
Standard LCD panel JVOP-KPPLCA04MEB local/remote control, parameter setting, operation monitoring
Bluetooth LCD panel JVOP-KPLCC04MBB supports wireless operation with DriveWizard Mobile mobile app
Remote installation cables UWR0051 (1 meter), UWR0052 (3 meters) panel remote installation extension cable
PC communication cable UWR01258 (3 meters) PC and driver USB communication, parameter upload/download
Android device cables UWR01516-B (Micro-B), UWR01516-C (Type-C) Android device connection driver USB port debugging
(2) Communication tab
Model Communication Protocol Function Description
JOHB-SMP3-MA Multi Protocol Ethernet supports EtherNet/IP, Modbus TCP/IP, PROFINET, EtherCAT
SI-P3 PROFIBUS-DP compatible with PROFIBUS-DP network
SI-N3 DeviceNet compatible with DeviceNet network
SI-W3 LonWorks Building Automation Communication
SI-B3 BACnet MSTP Building Automation Network Communication
SI-S3 CANopen CAN bus communication
2. Power optimization options (reactors, filters)
(1) AC input reactor (1.5%/3% impedance)
Used to improve input power factor, reduce harmonics, and protect drivers (recommended for power capacity>600kVA), example selection:
Voltage level driver model 1.5% impedance (open) 1.5% impedance (closed) 3% impedance (open) 3% impedance (closed)
240V 2011AFA URX000315 URX000418 URX000307 URX000413
240V 2017AFA URX000319 URX000420 URX000311 URX000415
480V 4005AFA URX000299 URX000410 URX000300 URX000503
480V 4011AFA URX000307 URX000413 URX000308 URX000414
(2) AC output reactor (3% impedance)
Used to reduce transient interference on the load side and adapt to long cable routing scenarios. Example selection:
Voltage level driver model Open model Closed model
240V 2011AFA 05P00620-0134 05P00620-0032
240V 2017AFA 05P00620-0136 05P00620-0036
480V 4005AFA 05P00620-0025 05P00620-0029
480V 4011AFA 05P00620-0135 05P00620-0033
(3) Single phase converter (SPC)
System kit model Maximum motor load (HP) Input current (A) Output DC current (A) Core components
SPBC-240-20HP 20 79 57 SPBC-2015AAA converter+URX000530 reactor
SPBC-240-30HP 30 116 84 SPBC-2022AAA converter+URX000531 reactor
SPBC-480-30HP 30 58 42 SPBC-4022AAA converter+URX000534 reactor
SPBC-480-125HP 125 234 170 SPBC-4093AAA converter+URX000529 reactor

Size and weight
1. IP20/UL Type 1 models (AFA suffix)
Chassis frame height (in), width (in), depth (in), compatible model example
1 14.1 4.9 8.6 2011AFA、4005AFA
2 17.6 4.9 9.2 2024AFA、4021AFA
3 20.1 7.9 9.3 2046AFA、4040AFA
4 21.3 10 10.4 2075AFA、4077AFA
6 30.5 12.3 15.7 2143AFA、4156AFA
2. IP55/UL Type 12 models (AVA suffix)
Chassis frame height (in), width (in), depth (in), compatible model example
1 14.1 4.9 9.0 2011AVA、4005AVA
2 17.6 4.9 9.6 2024AVA、4021AVA
3 20.1 7.9 9.7 2046AVA、4040AVA
4 21.3 10 10.7 2075AVA、4077AVA
6 30.14 14.26 16.14 2143AVA、4156AVA
3. Protective casing models (ABA suffix)
Chassis frame height (in), width (in), depth (in), compatible model example
9 27.6 12.3 16.5 2211ABA、4180ABA
10 31.5 17.3 18.6 2343ABA、4361ABA
11 44.9 20.1 18.9 4477ABA、4720ABA
Environmental and safety regulations
1. Environmental requirements
Temperature: IP20/flange model -10~+50 ℃, Type 1 kit installation -10~+40 ℃, up to+60 ℃ (capacity reduction required);
Humidity: ≤ 95% RH (no condensation);
Altitude: ≤ 1000 meters without capacity reduction, with a capacity reduction of 8% for every 1000 meters increase between 1000-4000 meters;
Vibration: 10-20Hz (9.8m/s ²), 20-55Hz (5.9m/s ²);
Protection level: IP20/UL Type 1, IP20/protective type IP55/UL Type 12、 Back of flange type 12.
2. Safety certification and standards
Certification: UL, cUL, CE, RoHS 2, WEEE, TUV SUD;
Functional safety: Safe Torque Off (STO), compliant with IEC 62061 SIL3, ISO 13849-1 PLe;
EMC standard: Built in reactor, compliant with EN 61800-3 C2 level requirements;
PCB coating: Complies with IEC 60721-3-3 Class 3C2 (chemical gases) and 3S2 (solid particles).
Email:wang@kongjiangauto.com