ABB Symphony Plus system IOR810 S800 I/O gateway
Overview of IOR810 Gateway
Function positioning: IOR810 is a gateway module that connects Symphony Plus SD/HR series controllers with S800 I/O. It supports integrating S800 I/O into Symphony Plus/Harmony control systems and has the ability to collect sequence of events (SOE) data. The SOE timestamp accuracy is determined by the S800 SOE digital input module.
Communication interface: It is connected to the Module bus (fiber only) of S800 I/O through HN800 I/O bus (electrical or fiber optic), and its core function is to scan S800 I/O modules and transmit data to the controller through HN800.
Connectivity: Up to 7 S800 cluster modems can be connected and scanned via fiber optic Modulabus, with each modem supporting up to 12 S800 I/O modules.
Technical specifications and parameters
1. Hardware and power supply
Power supply: Supports redundant power input, voltage range 21.6-28.0 VDC (nominal 24 VDC), typical current 220 mA (maximum 250 mA).
Installation: Standard 35mm DIN rail horizontal installation, requiring the use of IOR810N200 mounting base.
Redundancy design: Supports module redundancy, with dimensions of 54mm wide x 119mm high (single module), and a base size of 124mm wide x 186.5mm high (can accommodate two modules).
2. Characteristics of HN800 bus
Communication speed: 4 Mbaud, supports bus redundancy.
Connection distance:
Electrical HN800 bus: The maximum distance between the controller and IOR810 is 30 meters.
Fiber optic HN800 bus (using RFO810 repeater): up to 3000 meters.
Topology: Star architecture, up to 4 RFO810 fiber optic links, up to 64 devices per electrical bus, divided into 8 network segments, with a maximum of 24 devices per network segment.
3. Fiber optic Modulus distance
Plastic fiber optic: The maximum distance between IOR810 and the cluster modem or modem is 15 meters.
HCS fiber optic: up to 200 meters.
Glass fiber optic (with TB825 optical medium converter): up to 1000 meters.
Environmental and Certification Standards
1. Environmental requirements
Working conditions:
Temperature: 0-55 ° C (inside the cabinet), humidity: 20% -95% (no condensation at 40 ° C).
Altitude: 0-3048 meters, vibration 10-60Hz (0.0375mm amplitude), 60-150Hz (0.5G sine).
Storage and transportation: temperature -40-85 ° C, humidity 5% -95%, altitude 0-12192 meters, impact 15G (11ms).
2. Certification standards
Explosion proof and safety:
Compliant with CSA C22.2 No.213 and ISA S12.12 standards, suitable for non flammable environments (FM Class 3611, Division 2).
The flame retardant rating of plastic materials is UL 94 V-0/V-1/V-2/V5, and the cable complies with IEEE 383 and UL VW-1 standards.
Electrical certification: cCSAus certification, applicable to Class I Zone 2, Groups A/B/C/D hazardous areas, and requires SELV power supply.
Supported S800 I/O modules
1. Analog Input (AI)
AI801、AI810、AI815、AI820、AI825、AI830、AI830A、AI835A、AI843、AI845、AI890。
2. Analog Output (AO)
AO801、AO810、AO815、AO820、AO845、AO890。
email:1583694102@qq.com