Product Overview
(1) Core positioning and applicable scenarios
Product Name: IRDH575 Insulation Monitoring Equipment (including fault location control function)
Applicable systems: Non grounded (IT) systems, including 3 (N) AC, AC-DC hybrid, and pure DC systems, with voltage coverage of two levels:
Low voltage type (B1 series): AC/DC 20... 575V
High voltage type (B2 series): AC/DC 340... 760V
Typical applications: Industrial scenarios with sensitive loads such as frequency converters, thyristor controlled DC drives, PLCs, etc., such as factory power distribution and automation control systems
Core value: By monitoring the insulation resistance of the system to ground in real-time, early warning of grounding faults can be given, and the expandable positioning function can accurately lock the fault circuit, ensuring the continuous operation of the IT system
(2) Compliance and Certification
Following standards: DIN EN 61557-8/9(VDE 0413-8/9)、IEC 61557-8/9、IEC 61326-2-4、ASTM F1669M-96 wait
Certification qualifications: CE, UL/US LISTED, flame retardant rating UL94 V-0, halogen-free design of the shell
Core functions and operational features
(1) Insulation monitoring function
Key specifications of specific parameters for functional items
Measurement range of 1k Ω... 10M Ω covers faults from low resistance to high resistance, identifying risks in advance
The alarm mechanism has two levels of independent alarms (K1 warning, K2 main alarm) and supports N/O (normally open)/N/C (normally closed) mode switching. The factory default is N/O
Measurement accuracy 10k Ω... 10M Ω: 0%...+20%; 1k Ω... 10k Ω:+2k Ω Measurement voltage ≤ 40V, measurement current ≤ 220 µ A, does not affect system operation
Self monitoring equipment fault alarm relay (K3) monitors its own grounding, line connections, and internal circuits, and triggers an alarm when abnormal
Test and Reset: Press and hold the TEST button for self-test, and press the RESET button to clear the alarm memory (supports self-locking/non self-locking modes)
(2) Ground fault location function
Extended Configuration
Core components: IRDH575 host+EDS460 (main circuit positioning)/EDS461 (control circuit positioning)+dedicated current transformer (W series/8000 series)
Scalability: Supports up to 90 EDS4 devices for interconnection, with each device monitoring 12 circuits, covering a total of 1080 circuits
Portable extension: optional EDS3090/EDS3091 portable locator to track the source of faults
Positioning principle and process
Trigger method: Automatic activation after fault or manual start
Signal characteristics: Generate adjustable positioning current (maximum 50mA), pulse period of 2s/interval of 4s, automatic current limiting in case of low resistance fault
Fault identification: The positioning current returns through the fault circuit, and the LCD synchronously displays the fault EDS address, circuit number, and signal strength (mA/µ A). The EDS device also provides local synchronous indication
(3) Data storage and communication functions
data recording
Storage capacity: 99 alarm records with date and time, including fault type, insulation resistance value, occurrence time, and will not be lost in case of power failure
Information inquiry: The INFO key quickly retrieves system leakage capacitance, device parameters, alarm history, etc
Communication interface | Interface type | Specification parameters | Applicable scenarios | | --- | --- | | RS-485 (BMS protocol) | Maximum cable length of 1200m, 120 Ω terminal resistance (S1 switch control) | Interconnected with Bender equipment, or adapted to MODBUS/PROFIBUS through protocol converter | Analog output | 0/4... 20mA optional, load ≤ 500 Ω | Connected to PLC, DCS and other upper level systems for centralized monitoring|
(4) Operation and display functions
Display system: Backlit 4 × 16 character LCD, supports pure text fault prompts, real-time display of insulation resistance (k Ω), EDS status, alarm information, etc
Operation buttons:
Function keys: INFO (information query), MENU (menu), ESC (return/confirm), TEST (self-test), RESET (reset)
Navigation keys: up/down arrows (parameter adjustment), Enter (confirm settings)
Status indication: EDS LED (positioning start), EDS alarm LED (fault location), Alarm LED1/2 (two-level alarm), equipment fault LED

Detailed technical parameters
(1) Electrical parameters
Category specific specifications
Monitoring system voltage B1 series: AC 20... 575V (50... 460Hz), DC 20... 575V; B2 series: AC 340... 760V, DC 340... 575V
The power supply voltage is AC 88... 264V (50... 460Hz), DC 77... 286V. 5A fuses are required for UL/CSA applications, and 6A is recommended for other scenarios
Allow system leakage capacitance ≤ 150 (500) µ F
Relay parameters: 3 conversion contacts (K1/K2/K3), rated voltage AC 250V/DC 300V, making capacity 5A, breaking capacity 2A (AC 230V, cos φ=0.4)
Power consumption ≤ 14 VA
(2) Environmental and mechanical parameters
Category specific specifications
Working environment temperature -10 ℃...+55 ℃ (cannot operate continuously in 50mA positioning mode)
Storage environment temperature -40 ℃...+70 ℃