Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Schneider Modicon M340 Strict Environment Deployment and Troubleshooting Guide

F: | Au:FANS | DA:2026-06-02 | 447 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Schneider Modicon M340 Strict Environment Deployment and Troubleshooting Guide

Introduction: Why is there a need for M340 deployment guidelines for harsh environments

In harsh industrial environments such as petrochemicals, offshore platforms, sewage treatment, mines, and high-altitude substations, standard PLCs often find it difficult to operate stably for a long time. The Modicon M340, as a mid-range PAC (Programmable Automation Controller) from Schneider Electric, has become a common choice in the fields of process control and infrastructure due to its compact size, flexible X80 I/O system, and powerful communication capabilities. However, on-site engineers often encounter issues such as power module failure under high temperature and humidity, communication interruption, unstable X-bus expansion, and compatibility problems when replacing old systems. This article is based on official technical information from Schneider and combined with frontline operation and maintenance experience. It systematically reviews the hardware selection, installation protection, common fault diagnosis, and troubleshooting methods of M340 in harsh environments, and provides a standardized process for migrating from old platforms such as Modicon Premium/Quantum to M340.


Chapter 1: Overview of M340 Hardware Platform and Selection of Strict Environment

1.1 Processor Family and Key Parameters

The M340 offers two processor levels: the standard BMXP341000 (2 racks, 512 DI/128 AI, 2MB memory) and the performance BMXP3420xx (4 racks, 1024 DI/256 AI, 4MB memory). Performance based subdivision of three types of integrated communication:

BMXP342000: Only integrates Modbus serial link

BMXP3420102: Integrated Modbus serial link+CANopen master station

BMXP342020: Integrated Modbus Serial Link+Ethernet Modbus/TCP

BMXP3420302: Integrated CANopen+Ethernet Modbus/TCP

All processors are equipped with USB Mini-B programming ports and SD card slots, and come standard with BMXRMS008MP memory card (8MB). For applications that require file storage, such as recipes and historical data, it can be upgraded to BMXRMS128MPF (128MB).

1.2 Strict Environment Version (suffix H)

The working temperature of standard M340 is 0-60 ℃, with a pollution level of 2, and is not suitable for scenarios with conductive dust, corrosive gases, or severe temperature changes. Schneider offers reinforced versions with the suffix H (such as BMXP341000H, BMXNOE0100H), which feature:

Circuit board conformal coating (AVR 80): resistant to condensation, conductive dust, and chemical corrosion

Extended working temperature: -25 ℃~+70 ℃ (single rack configuration can even start briefly at -40 ℃)

Corrosion resistant gas: Complies with IEC/EN 60721-3-3 grades 3C1~3C4, and can withstand H ₂ S (9900 ppb), SO ₂ (4800 ppb), Cl ₂ (200 ppb), etc

Salt spray resistance: tested according to IEC 60068-2-52 Kb, severity level 2 (3 24-hour cycles, 5% NaCl)

Selection suggestion: For M340 used in outdoor cabinets, chemical plants, coastal areas, or ships, choose H-suffix CPUs, power supplies, I/O, and communication modules. At the same time, all electrical connection points must be coated with BMXGEL0025 protective gel to prevent corrosive gas from entering the terminal.

1.3 Rack and power module

M340 uses Modicon X80 rack (BMXBP • 00), with optional slots of 4, 6, 8, 12, and 16. When expanding multiple racks, BMXXBE1000 expansion modules need to be installed in the XBE slot for each additional rack. The racks are connected through X-bus cables (BMXXBC ••• K), with a total bus length of ≤ 30m, and TSXTLEYEX terminal resistors must be installed at both ends.

The power module needs to be selected based on the total load current:

BMXCPS2000 (24V DC, 20W) is suitable for small configurations

BMXCPS3020 (24V DC, 36W) commonly used

BMXCPS3540T (100-240V AC, 40W) is suitable for AC power supply and wide voltage input applications

In harsh environments, the corresponding H model (such as BMXCPS3020H) should be selected

Fault prevention: The electrolytic capacitor inside the M340 power module has a shortened lifespan at high temperatures. When the ambient temperature exceeds 50 ℃, it is recommended to control the load rate of the power module below 80% and replace the power supply every 5 years.

Chapter 2: Diagnosis and Troubleshooting of Common Hardware Malfunctions

2.1 Interpretation of LED Status Code

The M340 processor and module front panel provide status LEDs, which are the first-hand diagnostic basis on site.

Troubleshooting of LED color meanings

RUN green normal operation (cycle execution) flashing indicates stop or start in progress

ERR red processor or system failure 1Hz flashing: missing or damaged application program; Always on: Hardware malfunction, CPU needs to be replaced

I/O red I/O module detected a fault. Check if the configuration matches the actual module and verify the X-bus connection

SER COM yellow Modbus serial port is constantly on and inactive: communication configuration error or wiring fault

CAN RUN green CANopen bus running off: bus not configured or master station not started

CAN ERR red CANopen fault flashing: At least one slave station communication is interrupted; Always on: Bus short circuit or missing terminal resistance

ETH STS green Ethernet status is off: no IP address; Always on: Connected but inactive; Flashing: Normal communication

ETH ACT green network activity flashing indicates sending and receiving data

Practical case: The ERR light of BMXP3420302H in a sewage treatment plant flashes at 2Hz and cannot be connected through Control Expert. The reason is that the loose SD card caused the startup file to fail to read. Solution: Re plug and unplug the SD card. If it doesn't work, use an empty SD card to download the firmware via USB.

2.2 X-bus expansion failure

A common fault phenomenon in multi rack configurations is that some I/O modules cannot be recognized or randomly disconnect. Reasons include:

Missing or incorrect terminal resistor: TSXTLEYEX terminal resistors must be installed on both ends of the X-bus chain (XBE module of the first rack and XBE module of the last rack). The middle rack does not require installation.

Cable length exceeding limit: The total length of all X-bus cables exceeds 30m, or a single cable is too long (up to 12m). Suggest a total length of ≤ 25m to ensure signal integrity.

Insufficient power supply to the rack: Each power module on the rack must supply power to all modules in the rack, and cannot supply power across racks. Calculate the total current consumption (refer to the power consumption table in Control Expert) to ensure that it does not exceed the rated value of the power supply.

Exclusion steps:

Disconnect all X-bus cables, keep only the main station rack, and confirm that the CPU can recognize the local module normally.

Gradually add expansion racks and check if the I/O scan is normal after each addition.

Use an oscilloscope to measure the X-bus signal (differential, standard amplitude of approximately 2.5V). If the amplitude is below 1.5V or there is ringing, replace the cable or shorten the distance.

2.3 Common failures of power modules

Typical symptoms of power module failure: CPU failure to start, all LEDs not lit, or intermittent restarts. The power module of M340 has input fuses (non replaceable) and primary capacitors inside. Quick on-site inspection:

Measure whether the input voltage is within the nominal range (DC 24V allows 18-31.2V, AC 230V allows 85-264V).

Disconnect all loads, leaving only the power supply and CPU, and measure the output of 24V (for CPS3020, there are 24V+and COM output terminals). If the output is normal but the CPU is not working, the CPU is damaged.

If there is voltage but significant fluctuations in the output, it is mostly due to capacitor aging. In high-temperature environments, it is recommended to proactively replace the power module every 3-5 years.


Chapter 3: Troubleshooting of Communication Network Malfunctions

3.1 Modbus Serial Link

The integrated serial port (RJ45) of M340 supports non isolated RS-232 (4-wire) or RS-485 (2-wire), but this port is non isolated. In industrial sites, ground loop interference often leads to unstable communication and even port burnout.

Fault phenomenon: SER COM light flashes but the main station cannot receive a response, or sometimes communication is possible and sometimes timeout occurs.

resolvent:

For long-distance (>15m) or multi device RS-485, an external isolator TWDXCAISO must be used to connect between RJ45 and the device, otherwise it is highly likely to damage the CPU serial port.

Confirm wiring: When using RS-485 2-wire system, connect pin 3 (D1) and pin 8 (D0) of RJ45 to A (+)/B (-) respectively. The terminal resistor (120 Ω) is only connected at both ends of the bus.

Use the serial debugging assistant to capture packets and check for garbled or CRC errors. Usually, reducing the baud rate (from 19.2k to 9.6k) can alleviate noise issues.

3.2 Ethernet Communication

The Ethernet ports of M340 (BMXP342020/0302, BMXNOE0100/0110, BMXNOC0401) support 10/100M adaptation. Common problems and solutions:

Possible causes of the problem resolved

ETH STS light off, IP address not assigned. Check the rotation switch position on the back panel (0/0 is set through software, other positions are fixed IP), or enable BOOTP/DHCP service

Can ping but unable to program. Programming port disabled by firewall. Control Expert needs to use TCP 502 port to ensure it is not blocked

I/O scan timeout, network congestion or switch cache overflow, use QoS to increase the priority of Modbus/TCP packets; Reduce scanning cycle or use RSTP ring network

FactoryCast webpage cannot access HTTP service disabled. Enable HTTP service through Control Expert device properties (requires configuration download)

Key configuration: For the BMXNOE0110 FactoryCast module, the default password for the web server is empty, which poses a security risk. The first use requires setting a strong password through Web Designer and disabling unused services (FTP, TFTP).

3.3 CANopen bus fault

BMXP3420102/0302 integrates CANopen master station, with a maximum of 63 slave stations. Typical faults:

CAN ERR light flashing: indicates that at least one slave is lost. Open the CANopen configuration interface of Control Expert and view the slave status. Common reasons: broken bus cable, missing terminal resistance, and power failure at the substation.

Abnormal data reception but no errors: It may be due to inconsistent baud rate settings. All nodes of CANopen must have the same baud rate (such as 500kbps), and the bus length cannot exceed the maximum distance of the corresponding baud rate (up to 100m at 500kbps).

Frequent triggering of emergency objects: Check if the power supply from the substation is sufficient or if there is EMC interference. Use twisted pair shielded cables and ensure reliable grounding.

Wiring requirements: The CANopen bus must use a dedicated twisted pair shielded cable (such as TSXCANCA50). The length of the branch line should not exceed 0.6m at 1Mbps. Terminal resistors must be installed at both ends of the bus (enabled through TSXCANTDM0 or connectors with switches).

Chapter 4: Migration from Old Systems to M340

4.1 Feasibility of Migration

Schneider provides EcoFit PLC Replacement service, supporting migration from the following platforms to M340 or M580:

Modicon Premium

Modicon Quantum (retains I/O rack, only replaces CPU and backplane)

Modicon 984 and 800 series

SquareD Symax

April Series 1000/2000/3000

Even third-party: Rockwell SLC500/PLC5, Siemens S5/S7 (via PROFIBUS-DP gateway)

Migration strategy:

Partial replacement: Keep the original I/O wiring and only replace the CPU and rack (using Modicon X80 adapter).

Gradual upgrade: Replace the control cabinet first, and expand it after passing the test.

Complete replacement: Replace all with M340+X80 and rewrite the program.

4.2 Software Conversion Tools

Schneider provides Control Expert (formerly Unity Pro) with an application conversion tool that can automatically convert DFB, DFC, DDT, and configuration data of Premium or Quantum projects into M340 format. However, it should be noted that:

Some specialized modules, such as counters and motion control, may require configuration rewriting.

The I/O address mapping rules are different: in Premium, discrete I/O addresses are% I and% Q, while in M340,% I and% Q are used, but the module slot numbering method is different. The conversion tool will generate a mapping table.

Key points for manual transplantation:

Check if all hardware modules have corresponding models in the X80 product line of M340 (for example, the Premium TSX • series needs to be replaced with the BMX • series).

Special attention should be paid to the high-speed counter and serial link module: M340 does not support some old modules and needs to use BMXEH • or BMXNOR0200H instead.

Retest task cycle: The default cycle for M340's MAST task is 20ms. If the original system uses a shorter cycle (such as 10ms), it needs to be modified in the configuration.

4.3 On site replacement steps (taking Premium → M340 as an example)

Backup original program: Upload the program and symbol table from Premium.

Hardware inventory: Record all I/O module models and wiring methods (especially relay output and analog range).

Create a new project: Create a new M340 project in Control Expert and select the corresponding CPU (recommended performance type).

Configure rack: Insert X80 modules in the original rack slot order. Note that the width of BMX series modules varies, but the number of rack slots can be adjusted.

Import program: Use conversion tools to import XEF files and fix all errors and warnings.

Offline simulation: Use Control Expert emulator to test logic.

On site replacement: power off, mark all cables, remove the original rack, install new racks and modules, rewire (original terminals can be used as M340 terminals are compatible with some Premium terminals but need to be verified).

Download and debug: First download the empty program to test communication, then download the complete program and gradually put it into operation.

Common trap: The Premium power module outputs 24V to the backplane, while the M340 X80 power module does not provide 24V to the backplane (only 5V/3.3V), and external sensor power supply needs to be introduced separately. Be sure to check the sensors that rely on the 24V backplane in the original system and switch to independent power supply.


Chapter 5: Network Security Enhancement and Maintenance Suggestions

5.1 Built in security features

M340 supports multiple network security features from both hardware and firmware perspectives:

Access Control List (ACL): It can define the IP address range that allows remote connections, and online editing does not require downtime.

Password Protection: Programmable passwords can be set to prevent unauthorized downloads/uploads.

Disable unused services: HTTP, FTP, SNMP, etc. are disabled by default and need to be manually enabled.

Memory protection bit: After setting, it is prohibited to modify the program through the programming terminal.

Signature protection: The program signature can be stored on the SD card, and execution will be prohibited if the signature does not match (to prevent tampering).

Configuration suggestion: After debugging is completed, immediately set a strong password (at least 12 characters, including uppercase and lowercase letters, numbers, and special characters), and enable ACL to only allow access to the IP address of the maintenance site. Disable programming permissions for all debugging interfaces (such as USB).

5.2 Regular Maintenance Checklist

To ensure the long-term reliability of the M340 system, it is recommended to implement the following plan:

Periodic tasks

Check the status of all LEDs monthly, check the system diagnostic buffer in Control Expert, and clean the cabinet filter

Backup applications to SD cards and external storage every quarter, and test backup CPUs (if redundant)

Tighten all terminal screws (especially power and grounding) every six months, and measure the temperature inside the cabinet (should be below 55 ℃)

Check the X-bus cable and terminal resistance contact every year, replace the battery (some models require motherboard battery replacement), and reapply the connection points with BMXGEL0025 (in harsh environments)

Replace the power module and SD card every 5 years (flash memory has write life)

5.3 Using RTU module to achieve remote monitoring

For distributed stations such as oil and gas pipelines and water treatment, BMXNOR0200H RTU module (supporting IEC 60870-5-101/104 and DNP3 serial/IP protocol) can be used. This module also has an H version (-25~70 ℃) and is equipped with a built-in web server and data recording function (CSV files stored on SD card).

Common RTU communication faults:

Dial up connection failure: Check PPP configuration and AT command set of external modem (such as GPRS). M340 supports serial modem and Ethernet PPPoE.

Event loss: The BMXNOR0200H event buffer has a maximum of 100000 entries, which will be overwritten if SCADA does not read for a long time. Appropriate event generation masks and reporting cycles should be set.

Time asynchronous: The RTU module acts as an NTP client to synchronize CPU time. If the NTP server is unreachable, a GPS receiver can be used to send a time string through the serial port (a custom function block is required).

  • ETEL ILM03-060-3RA-A00 Linear Motor
  • ETEL EA-S0M-300-40/80A-0090-00 Power Supply Module
  • Etel DSCDP131-111-000 Position Controller
  • ETEL DSC2P121-111E-001A Digital Servo Amplifier
  • ETEL DSB2P101-121E-009H Position Controller
  • ETEL IWM040-0128-00 Ironcore Linear Motor Magnetic Way
  • ETEL AccurET EA-S0M-400-40/80A-0000-00 Modular Power Supply
  • ETEL LMC11-050-3TA-S10C Motion Controller
  • ETEL LMC11-050-3TA-250A Controller Module
  • ETEL DSB2P101-121E-009H Digital Servo Amplifier Position Controller
  • ETEL AccurET Modular 400 Position Controller
  • ETEL DSA2 Digital Servo Amplifier
  • ETEL DSC2P154-421-000 Servo Drive
  • ETEL DSO-PWS121-003 Power Supply Module
  • ETEL 0348M-070-02D-004 Linear Encoder
  • ETEL DSC2P131-111-000 Linear Servo Amplifier – 10Arms/30Arms
  • ETEL DSC2P131-121-000 Digital Servo Amplifier
  • ETEL DSB2P131-111E-000H Digital Servo Amplifier
  • ETEL DSO-PWS111-000 Power Supply Module
  • ETEL LMC11-050-3TA-S41C Linear Motor Module – High Thrust Density
  • ETEL EA-P2M-300-07/15A Drive Specs
  • ETEL DSO-RAC200A-011D Dual Position Controller Rack
  • ETEL Short-Stroke Actuator ID809786-03
  • ETEL DSCDM332-111-000 Servo Controller Specs
  • ETEL DSCDL332-131-000A Position Controller
  • ETEL LMP07-100-3TAS-229 Linear Motor
  • ETEL LMA11-120-3ZA-359C Linear Motor
  • ETEL DSA2S211ZA-018A Digital Servo Amplifier
  • ETEL EA-P2M-300-07/15A AccurET Controller
  • ETEL LMB06-050-2QA-239B Linear Motor Guide
  • ETEL DSCDP334‑421‑000 Servo Drive – High‑Power Digital Controller Positioner
  • ETEL DSCDP121‑111E‑000A Dual Driver Board – High‑Density Motion Control Module
  • ETEL DSA2 S1B22A Digital Servo Amplifier – High‑Efficiency Drive for Industrial Motors
  • ETEL DSCDM342‑111‑000 Servo Amplifier – Multi‑Axis Digital Drive
  • ETEL MWA120‑0512‑00B 512mm Linear Motor Magnet
  • ETEL EA‑P2M‑300‑07/15A‑0100‑01 AccurET Modular Position Controller – Medium‑Power Drive
  • Etel DSC2P141‑111‑000 568425‑01 Digital Servo Amplifier – Compact High‑Performance Drive
  • Etel EA‑P2M‑400‑10/20A‑0000‑01 AccurET Modular Position Controller – High‑Voltage Drive
  • ETEL DSC2P142‑111‑000 Digital Servo Amplifier – Compact Position Controller
  • ETEL DSDH153‑121C‑001D Digital Servo Drive – High‑Power Motion Control
  • ETEL DSB2P131 & DSO-CAN111A Servo Amplifier Set
  • ETEL DSA2S211ZA-018A Digital Servo Amplifier
  • ETEL DSMAX212-111-001 568540-01 DSMAX2 Servo Controller
  • ETEL TMB+0291-150 Torque Motor Stator Assembly
  • ETEL EA-S0M-300-40/80A AccurET PSU
  • ETEL DSO-PWR112C-000B Power Supply Module
  • ETEL DSC2P141-111-000 Linear Servo Amplifier
  • ETEL DSB2S154-211-000H Servo Amplifier
  • ETEL DSCDP121-122-000 Digital Controller
  • ETEL DSCDP121-111E-000A Dual Position Controller
  • ETEL DSCDM332-111-000 Linear Servo Controller
  • ETEL DSB2P134-111E-000H Servo Amplifier
  • ETEL DSCDP132-111-000 Control Board Guide
  • ETEL DSB2S154-211E-000H Servo Amplifier
  • ETEL EA-SOM-300-40/80A Power Supply Module
  • ETEL ILM12-060-3PD-R20C Linear Motor with IWM Ways
  • ETEL P2M-300-07 AccurET Position Controller
  • ETEL DSB2P124-111E-000H Servo Amplifier
  • ETEL EA-P2M-048-05/10A Position Controller
  • ETEL EA-S0M-300-40/80A Power Supply Module
  • ETEL MWA070-0256-20B Linear Motor Magnet Guide
  • ETEL MWD070‑0128‑21A Linear Motor – Compact Ironless Linear Motor for High‑Speed Precision
  • ETEL DSB2P124‑211E‑000H Digital Servo Amplifier – 300 VDC Slave Drive for High‑Voltage Systems
  • ETEL MWD100‑0128‑00B Linear Motor – High‑Force Ironless Linear Motor for Precision Motion
  • ETEL AccurET EA‑S0M‑400 & P2M‑400‑05/10A Drive Module
  • ETEL EA‑S0M‑400‑40/80A‑0000‑00 AccurET Power Supply – High‑Power DC Supply for Motion Systems
  • ETEL MWA050‑0128‑20B Linear Motor Magnet – High‑Force Magnet Assembly for Linear Motors
  • ETEL DSB2S121‑111E‑000H Digital Servo Amplifier – High‑Current Drive for Demanding Motion
  • ETEL DSCDM332‑111C‑000B Digital Position Controller DSCDM – High‑Density Motion Module
  • ETEL EA‑P2M‑048‑2.5/5A‑0100‑01 AccurET Modular Position Controller
  • ETEL DSC2P121-111E-001A Digital Servo Controller – High‑Precision Motion Control
  • ETEL MWA050-0128-20B Linear Motor Magnet
  • ETEL DSB2P142-111E-000H Drive Specs
  • ETEL DSB2S234-111E-000H Servo Amplifier
  • ETEL EA-P2A-400-10-20A Position Controller
  • ETEL DSB2 Digital Servo Amplifier Controller DSB2P142-111E-000H SN 014661437
  • ETEL EA-S0M-400-40/80A-0000-00 AccurET Power Supply Module 650140-01
  • ETEL DSB2P131-111E-000H Servo Amplifier
  • ETEL EA-P2M-400-10/20A AccurET Controller
  • ETEL DSDP324-322F-000C Dual Motor Driver
  • ETEL DSB2S154-211E-000H Digital Servo Amplifier Drive
  • ETEL DSO-PWS111B-000C Power Supply Board 1130E-070-018
  • ETEL DSCDP324-322G-000A Servo Amplifier
  • ETEL DSB2P142-111E-000H Servo Amplifier Drive
  • ETEL EA-P2M-400-15/40A & EA-S0M-400 Drive Set
  • ETEL DSB2P142-111E-000H Digital Servo Amplifier
  • ETEL LMG15-070-3QC-H11 Linear Motor
  • ETEL TMA0140-070-3RB-S62B Torque Motor
  • ETEL DSA2S211ZA Digital Servo Amplifier
  • ETEL AccurET EA-P2M-300-4/7.5A-0100-01 Modular Position Controller
  • ETEL DSCDL332-131C-000A Servo Control Board
  • ETEL DSCDP324-322F-000C Dual Motor Driver
  • ETEL EA-P2M-400-10/20A Position Controller
  • ETEL DSC2P121 and DSO-HIO33 Servo Amplifier Set
  • ETEL EA-P2M-400-15/40A AccurET Drive
  • ETEL EA-P2M-300-07/15A Position Controller
  • ETEL EA-P2M-048-05/10A-0100-01 Servo Drive
  • ETEL EA-S0M-300-40/80A Servo Drive Guide
  • ETEL DSB2P131-111E-000H Digital Servo Amplifier
  • ETEL DSCDP334-421-000 Servo Drive Guide
  • ETEL EA-S0M-300-40 80A-0000-00 Motion Control Module
  • ETEL UltimET Light Motion Controller EU-LGP-0-0-1000-01 Multi-Axis
  • ETEL DSO-RAC601-029 Controller Rack
  • ETEL DSMAX212-121C-000C Board
  • ETEL DSCDL132-212B-000C Position Controller
  • ETEL TMB0291-050-3TDS-E82 Torque Motor
  • ETEL DSMAX212-121-000 Board
  • ETEL DSB2P131-111E-000H Digital Servo Controller Amplifier Unit
  • ETEL DSB 2S 124-211E-000H Digital Servo Amplifier
  • ETEL AccurET EA-P2M-300-4/7.5A-0100-01 Modular Position Controller
  • Beckwith Electric M-6280A Digital Capacitor Bank Control
  • Beckwith M-2355B Adapter Panel with M-2001C-6SL Tapchanger Control
  • Beckwith M-0359 Syncrocloser MOD512
  • Beckwith Electric M-2001C-6ELFA Tap Changer Controller
  • Beckwith M-3311A 4-Coil Transformer Protection Relay
  • Beckwith M-0124 Terminal Board Adapter Plate Guide
  • Beckwith Pride M-0296C 3-Phase Programmable Relay
  • Beckwith M-0388 Syncrocloser Check Relay Guide
  • Beckwith M-0170A AC Current Relay Guide
  • Beckwith M-3311 Transformer Protection Relay Guide
  • Beckwith Electric M3310 Integrated Transformer Protection Panel
  • Beckwith M-0145 First Customer Protector
  • Beckwith M-0170A AC Current Relay
  • Beckwith PRIDE M-0296C 3 Phase Programmable Relay
  • Beckwith Pride M-0296b 3-Phase Programmable Relay
  • Beckwith M-0245C High Speed Sync-Check Relay Guide
  • Beckwith M-0115A AC Parallel Balancing Module
  • Beckwith M-0389 Voltage Verifier Relay