For pull-out type, ensure that the operating hole cover on the compartment door has been opened.
Spare parts and lifecycle management
8.1 Recommended spare parts list
Wide voltage power module (divided into 24~60V and 110~250V)
Auxiliary switch (5NO+5NC)
Operation counter
Plum blossom touch finger (suitable for pull-out style)
Hand car locking electromagnet
Fuse adapter kit
8.2 Long term storage
Keep the original packaging, with built-in desiccant, and replace every 6 months.
Environment: -15 ℃~40 ℃, dry and dust-free, without corrosive gases.
It is recommended to randomly inspect the vacuum arc extinguishing chamber for storage exceeding 20 years.
8.3 Scrap and Recycling
The main materials for VSC contactors are metal (iron, copper, aluminum, silver) and plastic/epoxy resin. Recycling should be classified according to local environmental regulations. Metal parts can be melted and reused, while plastics and epoxy resins can be crushed and used as industrial fillers or incinerated to recover heat energy.