Ordering of Ramp-Soak Profile Parameters:
Ramp-soak profile parameters are ordered first by profile, then by segment where applicable. So, for example, the first 8 registers of the Ready Events parameter are the ready segment event states for the first profile (profile A), the next 8 registers are for profile B, and so on. In the case of the segment triggers, the first register contains the first trigger setting for the first segment of profile A, the second register contains the settings for the second trigger for the first segment of profile A, the third register contains the settings for the first trigger for the second segment of profile A, and so on.
Relative and Absolute Modbus® Addresses:
In the tables on the following pages, absolute addresses are in decimal and relative addresses are in hexadecimal. Absolute addresses include the type of register. Refer to the absolute address to determine which function to use to read or write values.
Relative addresses indicate the register offset from the first register of the particular type. For example, the first register for the Derivative parameter is at 40067, which is offset 66 (x42) registers from the beginning of the holding registers at 40001.
Modbus® RTU Protocol Data Table: