Watlow CLS200 series controller

F: | Au:FAN | DA:2025-11-10 | 831 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Watlow CLS200 series controller

Product Overview and Core Features

1. Product positioning and circuit configuration

The CLS200 series controller is an industrial grade multi loop control device that provides 4 (CLS204), 8 (CLS208), or 16 (CLS216) completely independent control loops. It can be used as an independent controller (operated through a 2-line 16 character display screen and touch keyboard) or as a core component of a computer monitoring data acquisition and control system, supporting local or remote control through EIA/TIA-232 or EIA/TIA-485 serial communication interfaces.

2. Core functional features

Multi type sensor compatibility: directly connect multiple thermocouples (J, K, T, S, R, B, E types) without hardware modification, with reference compensation, linearization, measurement offset calibration, disconnection/short circuit/reverse connection detection functions, supporting Fahrenheit/Celsius display; Support 3-wire 100 Ω platinum resistance RTD (0.00385 curve), calibration resistors need to be configured for CLS204/CLS208; Automatic calibration of linear analog input (requires installation of calibration resistors), input two points to automatically calibrate according to user units.

Flexible output control: Each circuit includes dual outputs for heating and cooling, with independent configuration of output parameters; Supports multiple control and output modes, with control outputs set to ON/OFF, TP, DZC, and SDAC modes. Each circuit can have up to 2 outputs set to ON/OFF, P, PI, or PID control, and supports reverse/forward actions.

Alarm and Monitoring: Supports high/low process alarm and high/low deviation alarm. Each loop alarm can independently activate digital output or group activate output; The global alarm output is activated upon any alarm trigger and needs to be manually confirmed before being turned off; The CPU watchdog timer output can monitor system faults, keep the relay closed during controller operation, and trigger notifications when the microprocessor shuts down.

Communication and Storage: Supports Modbus RTU protocol, connects PLC, operation interface terminal, and third-party software through EIA/TIA-232/485 interface; The memory can store up to 8 tasks, which can be called locally or remotely through numerical input. Each task includes operating conditions such as set values and alarms.

Other practical functions: support non-linear output curve selection; The self-tuning function can quickly optimize PID parameters; Pulse counter input (up to 2000Hz) can accurately control motor or belt speed; Low power shutdown function, automatically shuts down and all outputs when the input voltage is below the safe value detected 🔶 1-163, 1-164, 1-165, 1-166 🔷。

image.png

Installation Guide

1. Preparation and safety requirements before installation

Environmental requirements: The controller should be installed in a location without excessive temperature (not exceeding 50 ℃/122 ℉), low dust, and unauthorized operation, to avoid electromagnetic and radio frequency interference. Sensor wiring should be kept away from high-voltage lines, power switch equipment, and motors.

Safety warning: Cut off the power supply throughout the entire process before installation to prevent electric shock; The controller may malfunction to 0% or 100% power output state, requiring the installation of independent external safety shutdown devices (such as FM certified high/low process limit controllers and mechanical contactors), and the safety devices must be independent of the process control equipment. If the malfunction may result in death or injury, FM certified safety devices must be used.

Tool preparation: It is recommended to use a 1/8-DIN rectangular punch (such as Greenlee 600-68), curved saw and metal file (stainless steel/thick panel), nibbler and metal file (aluminum/light panel), as well as a cross screwdriver, 1/8 inch (3mm) straight screwdriver (for wiring), and multimeter.

2. Installation steps of core components

(1) Controller installation

Panel opening: A hole of 1.80 inches (46mm) x 3.63 inches (92mm) (tolerance ± 0.02 inches/1mm) needs to be opened on the panel, and the panel thickness should not exceed 0.2 inches (5mm).

Installation process: First, remove the bracket and collar of the processor module, and slide the module into the panel cut; Insert the installation collar onto the back of the module (with the screw groove facing back), loosen the screws of the installation bracket, insert the bracket into the installation groove (with the screw head facing back), tighten and fix it laterally; Ensure that the casing is installed in place and tighten the screws to secure the bracket against the collar.

Space requirements: The controller can extend up to 7.0 inches (178mm) behind the panel, and the screw bracket can extend up and down by 0.5 inches (13mm) each; If using a straight SCSI cable, an additional 1.6 inches (41mm) should be reserved behind the terminal board; If using a right angle SCSI cable, an additional 0.6 inches (15mm) need to be reserved.

(2) Installation of TB50 terminal board

TB50 is a screw terminal interface used to connect relays, encoders, and discrete I/O devices. It supports 18 AWG (0.75mm ²) wires and is connected to the controller through a 50 pin SCSI cable. There are two installation methods:

DIN rail installation: First, clamp the hook side of TB50 onto the rail, and then push the buckle side into place for fixation; Use a Phillips screwdriver to pry open the buckle during disassembly.

Bracket installation: First remove the DIN rail bracket of TB50, mark 4 installation holes, drill the # 6 (3.5mm) screw hole, and fix TB50 with 4 screws; The four small holes on the terminal board can be used to secure wiring with zip ties.

(3) Installation of power supply and DAC module

Power installation: If using a built-in power supply, choose a Class 2, isolated and regulated 12-24V DC (1A) power supply, and install it according to the instructions of the power supply manufacturer; The installation bracket with built-in power supply needs to reserve a gap of 0.3 inches (8mm) and be fixed with 2 # 10 (5.0mm) screws. Pay attention to using 6-32 and 1/4 inch screws to avoid damaging the power supply with excessively long screws.

Installation of Dual DAC/Serial DAC Module: The module is used to convert the open collector output of the controller into an analog signal. During installation, it is necessary to select a wall position close to the controller, mark and drill 4 # 8 (4.0mm) screw holes for fixation; The output signal range of the module is configured through jumper wires. The dual DAC requires independent power supply to isolate the digital and analog circuits. The serial DAC supports cascading multiple modules (up to 16), and the 5V DC output of the CLS200 power supply is required to power multiple modules 🔶 1-381 to 1-397, 1-773 to 1-794 🔷。

3. System cabling and testing

(1) Wiring specifications

Cable selection: It is recommended to use multi strand wires (solid lines are only used for fixed scenarios and are prone to poor contact during maintenance); Thermocouple extension wire uses 20 AWG (0.5mm ²); Shielded wires are used for analog input/output and RTD input, with one end of the shielding layer connected to the ground; Except for thermocouples, copper wires are used for other connections.

Anti interference measures: Separate the wiring of high and low voltage lines to avoid parallelism or bundling; If an electromechanical relay must be used, a 0.01 μ F (1000V AC) capacitor and a 47 Ω (0.5W) resistor absorption network should be connected in series at both ends of the normally open contact of the relay load, or a metal oxide varistor (MOV) and a bidirectional voltage regulator diode (Transorb) should be connected in parallel.

Grounding requirements: Avoid grounding loops, and the DC common terminal, analog common terminal, reference voltage common terminal, communication common terminal, etc. of the controller must not be connected or grounded to each other; CLS216 is a single ended input, and all sensor negative terminals are connected to the analog common terminal. Grounded or ungrounded thermocouples must be used uniformly, and special wiring is required for mixed current and low voltage inputs.

(2) Power supply and terminal connection

Power connection: Connect the DC common terminal of the power supply to the DC common terminal of CLS200 TB2 (-), and connect the positive terminal of the power supply to the DC positive terminal of TB2 (+); If an external power source is used to supply power to the load, the DC common terminal of the load power source must be connected to the DC common terminal of the controller power source; The grounding terminal of TB2 must be connected to the controller casing and grounded; Finally, connect the 120/240V AC power supply to the power source.

TB50 connection: Connect TB50 to the controller through a 50 pin SCSI cable, ensuring that the cable is securely inserted into the interface.

(3) System testing

TB50/TB18 test: After power on, the controller displays "SCALE CHECK SUM", followed by a bar chart; Measure the+5V DC voltage of TB50/TB18 with a multimeter (terminal 1 is positive, terminal 3/TB18 terminal 2 is common), and the voltage should be between 4.75-5.25V.

Digital output test: Connect a 500 Ω -100k Ω resistor between terminal 1 (+5V) of TB50/TB18 and the digital output terminal to be tested. Use the "MANUAL I/O TEST" menu to control the output switch. When the output is ON, the voltage is less than 1V, and when it is OFF, the voltage is 4.75-5.25V. The heating output is enabled by default and needs to be set to manual mode for 100% output before testing.

Digital input test: Disconnect the input wiring and enter the "DIGITAL INPUTS" test menu. When the input is not connected, it displays "H" (high level/open circuit). When the input terminal is connected to the controller common terminal (TB50 terminal 3/TB18 terminal 2), it displays "L" (low level/closed).


Operation Guide

1. Front panel and button functions

Panel layout: Includes a 2-line 16 character display screen and an 8-key keyboard. The display screen can display process variables, set values, output levels, and other information. The keyboard includes "Ramp/OAK" (slope/constant temperature control), "ALARM ACK" (alarm confirmation), "MAN/AUTO" (manual/automatic switching), "CHNG SP" (set value modification), "ENTER" (confirm/store), "BACK" (return/cancel), "YES" (up/add), and "NO" (down/reduce) keys.

Key function: The "YES" key is used to select menus/parameters, confirm YES/NO prompts, increase values, and stop scanning; The "NO" key is used to skip menus/parameters, reject YES/NO prompts, reduce values, stop scanning, and perform NO key reset (press and hold to restore default parameters when powered on); The 'BACK' key is used to cancel editing, return to the previous menu, and switch display modes; The 'ENTER' key is used to store modifications, enter the next parameter, and start scanning (press twice); The "CHNG SP" key is used to modify the set value; The "MAN/AUTO" key is used to switch between manual/automatic modes, adjust manual output, and start self-tuning; The 'RAMP/SOAK' key is used to allocate slope/constant temperature curves, select modes, and view curve status (controllers with this option only); The 'ALARM ACK' button is used to confirm alarms and reset global alarm outputs.

2. Core display mode

(1) Bar chart display (default upon startup)

Display content: The top displays up to 8 circuit numbers/names and alarm symbols (such as "<" for low process/deviation alarm, ">" for high process/deviation alarm, "F" for sensor failure), and the bottom displays control status symbols (such as "M" for manual, "A" for automatic, "T" for self-tuning).

Operation: Press the "YES"/"NO" keys to switch circuit groups, press "ENTER" twice to start scanning (each group displays for 3 seconds), press any key to stop scanning, press the "BACK" key to switch to task display (if enabled) or single circuit display.

(2) Single loop display

Display content: Display the process variables, engineering units, set values, control status (MAN/AUTO/TUNE/HEAT/COOL), and output percentages of a single circuit. If dual outputs are enabled, heating and cooling output percentages will also be displayed separately.

Operation: Press the "YES"/"NO" keys to switch circuits, press "ENTER" twice to start single circuit scanning (each circuit displays for 1 second), press any key to stop, press the "BACK" key to switch to task display or bar chart display.

(3) Alarm display

Trigger logic: When the process/deviation/sensor failure/system alarm is triggered, the controller automatically switches to the single loop display of the fault circuit, and the global alarm output is activated, displaying a 2-character alarm code (such as "FS" indicating thermocouple disconnection, "HP" indicating high process alarm). When the sensor fails, the output is set to the "sensor fault heating/cooling output" parameter value (default 0%), and the alarm code flashes. Other functions can only be operated after confirmation.

Alarm types: including sensor faults (thermocouple open/short/reverse, RTD open/short), process alarms (high/low process, high/low deviation), system alarms (battery failure, low power consumption, excessive ambient temperature, hardware failure), each alarm corresponds to a specific code and processing method.

Alarm confirmation: Press the "ALARM ACK" button to confirm the alarm. If multiple circuits alarm, they will switch to each faulty circuit in sequence. All alarms need to be confirmed before resetting the global alarm output.

3. Key operational procedures

(1) Modify the set value

Switch to the single circuit display of the target circuit;

Press the "CHNG SP" button, and the display screen will show "SETPOINT? XX" (XX is the current set value);

Press the "YES" key to enter modification mode, and press the "YES"/"NO" keys to increase or decrease the set value;

Press the "ENTER" key to save and return to the single circuit display, or press the "NO"/"BACK" keys to cancel the modification.

(2) Manual/automatic mode switching

Switch to the single circuit display of the target circuit;

Press the "MAN/AUTO" button, press the "YES" button to confirm the mode switch, or press the "NO" button to cancel (in automatic mode);

If switching to manual mode, press the "YES"/"NO" keys to set the heating/cooling output percentage, and press the "ENTER" key to save;

If switched to automatic mode, the controller controls according to the preset PID parameters;

If switched to TUNE mode, the controller automatically optimizes the PID parameters.

(3) Self tuning operation

Prerequisite: The controller has installed control and sensor circuits, the thermal load is in place, the system can operate safely, and the approximate target temperature is known.

Operation steps:

Switch to the single loop display of the target loop, ensuring that the process variable is stable and in manual mode;

Set the set value close to the normal operating temperature (note: during the self-tuning period, the output is 100% or the output limit value must be within a safe range);

Press the "ENTER+ALARM ACK+CHNG SP" key combination to enter the settings menu, and set "INPUT Filter" to 0 SCANS in the "SETUP LOOP INPUT" menu;

Return to single circuit display, press the "MAN/AUTO" key, press the "NO" key to switch to TUNE mode, press the "ENTER" key to start self-tuning (TUNE "flashes);

After self-tuning is completed, automatically switch to automatic mode and restore the original setting value of "INPUT Filter".

image.png

Setting guide

1. Enter the settings menu

Enter through the "three key combination": Under the single circuit display of the target circuit, press the "ENTER", "ALARM ACK", and "CHNG SP" keys in sequence (not simultaneously). If there is no operation for 3 minutes, the controller will automatically return to the single circuit display to prevent unauthorized access.

2. Core Settings Menu

(1) SETUP Global Parameters

Includes parameters such as task loading/saving, task selection digital input, output forced digital input, startup alarm delay, ramp/constant temperature time reference, keyboard lock, power on output status, process power digital input, controller address, communication parameters (baud rate, protocol, verification), AC line frequency, digital output polarity during alarm, etc. For example:

Load SETUP FROM JOB "/" SAVE SETUP TO JOB ": Load/save tasks 1-8, which include PID parameters, control status, alarm settings, etc;

Controller Address ": Set the communication address (1-247) to be unique in the EIA/TIA-485 network. Anasoft software supports up to 16 controllers (addresses 1-16);

Communications BAUD RATE ": Set the baud rate (2400/9600/19200) to be consistent with the upper computer.

(2) Loop input setting (SETUP LOOP INPUT)

Configure input type (thermocouple/RTD/linear/pulse/SKIP), circuit name, input unit, input offset, thermocouple reverse detection, pulse sampling time, display format, linear calibration parameters, input filtering, etc., for example:

INPUT TYPE ": Select the sensor type, SKIP is used for unused circuits (does not detect alarms, does not participate in scanning);

INPUT SCALING ": Linear input requires setting high/low process variables and corresponding high/low readings to achieve signal calibration;

INPUT Filter ": Set the filtering for the 0-255 scan period, disable filtering at 0, to suppress input signal fluctuations.

(3) Loop Control Parameter Setting (SETUP LOOP Control PARAMS)

Set PID core parameters such as heating/cooling ratio band (PB), integration time (TI), differentiation time (TD), control filtering, temperature difference (SPREAD), PID recovery digital input, etc., for example:

HEAT Control PB ": The larger the proportional band, the weaker the proportional effect, and the default value varies with the sensor type (e.g. J-type thermocouple defaults to 50);

SPREAD ": It is a hysteresis loop during switch control, and a switching threshold (0-255, consistent with the display format) for process variable deviation from the set value during PID control.

(4) Loop output setting (SETUP LOOP OUTPUTS)

Enable/disable heating/cooling output, set output type (TP/DZC/SDA/ON/OFF/3P DZC), cycle time (TP mode), SDAC parameters, output action (reverse/forward), output limit, sensor fault output, thermocouple break output average, output linearity, etc., for example:

HEAT CON OUTPUT ": Enable/disable heating output, which can be used as an alarm output when disabled;

SENSOR FAIL HT OUTPUT ": Heating output percentage (0-100%) in case of sensor failure, default 0%.

(5) SETUP LOOP ALARMS

Configure high/low process alarm settings, alarm types (OFF/ALARM/MOTOR), alarm outputs, deviation alarm values, alarm dead zones, alarm delays, for example:

HI PROC ALARM SETPT "/" LO PROC ALARM SETPT ": High/low process alarm threshold, within the sensor range;

ALARM DEADBAND ": Alarm hysteresis, preventing process variables from fluctuating near the alarm threshold and causing frequent alarms (0-255, units consistent with display format).

(6) Manual I/O Test

Test digital input (displaying H/L status), digital output (manually switching ON/OFF), keyboard (displaying key names by pressing any key), and display screen (displaying pixel patterns) to troubleshoot I/O faults.


Troubleshooting and Maintenance

1. Common faults and their solutions

(1) Power and display malfunction

LOW POWER: Confirm that the power supply voltage is ≥ 12.0V DC (1A), and check the power supply wiring; If the error persists after restarting, record the parameters and perform a NO key reset. If it is ineffective, contact the manufacturer.

BATTERY DEAD (battery failure): When the battery cannot maintain parameter storage during power failure, the parameters will be reset to default and the battery needs to be replaced. If it fails, contact the manufacturer.

The display screen does not light up: check the power wiring and confirm that the power supply is normal; If it is an EPROM issue, replace the EPROM (anti-static operation is required); If the controller is damaged, send it back for repair.

(2) Sensor malfunction

Thermocouple failure (FS/RT/ST): Check the thermocouple wiring (positive and negative poles, broken wires, short circuits), and confirm whether the "REVERSED T/C DETECT" parameter is enabled; If it is a broken wire, replace the thermocouple; If it is reversed, adjust the wiring.

RTD fault (RO/RS): Check the RTD wiring (open/short circuit), measure the RTD resistance (20-250 Ω normal), replace if damaged.

(3) Communication malfunction

Check whether the communication parameters (address, baud rate, protocol, verification) are consistent with the upper computer;

Check the wiring of EIA/TIA-232/485, terminal resistance (150-200 Ω) is required for EIA/TIA-485, shielded wire is needed for long-distance communication, and one end of the shielding layer is grounded;

Use a communication tester or oscilloscope to detect the signal and eliminate the grounding loop (an optical isolation converter can be used).

2. Maintenance operations

(1) NO key reset

Restore all parameters to default values. Operation: Press and hold the "NO" key after power off, release it after power on, and press the "YES" key to confirm when the prompt "RESET WITH DEFAULTS?" appears; Before resetting, the parameters need to be recorded, and the computer monitoring system can save the parameters through software.

(2) EPROM replacement

Prerequisite: A cross screwdriver, a straight screwdriver, and an anti-static wristband are required. Record the parameters before replacement.

Step: Power off, remove the 4 screws on the front panel of the controller, and take out the electronic components; Remove the 4 screws from the top circuit board and unplug the circuit board; Use an IC extractor to remove the old EPROM and insert the new EPROM (pay attention to the direction of the notch); Reverse the steps to reassemble, power on and re-enter the parameters.

(3) Calibration resistor installation

The current, voltage, and RTD inputs of CLS204/CLS208/CLS216 require the installation of specific calibration resistors. The resistance value and position vary with the input type (such as CLS204 current input using 6 Ω or 3 Ω resistors), and must be soldered by professional technicians to avoid damaging the circuit board.


Technical specifications

1. Core specifications of the controller

Environmental parameters: working temperature 0-50 ℃, storage temperature -20-60 ℃, humidity 10-95% (non condensing), indoor use.

Physical dimensions: CLS200 processor module weighs 1.98 pounds (0.9kg), measures 8.0 inches (203mm) in length (without SCSI interface), has a width of 3.78 inches (96mm), and a height of 1.96 inches (50mm); TB50 weighs 0.32 pounds (0.15kg), measures 4.1 inches (104mm) in length, 4.0 inches (102mm) in width, and 1.5 inches (37mm) in height 🔶 1-3423, 1-3425, 1-3451 🔷。

Input/output: Analog input supports -10 to+60mV (or 0-25V with calibrated resistor), resolution>14 bits, accuracy 0.03% of full range (25 ℃); 8 digital inputs (TTL level), 35 digital outputs (open collector, maximum 60mA/24V DC); One CPU watchdog output (maximum 10mA/5V DC).

Communication: Supports EIA/TIA-232 (3-wire, maximum 50 feet), EIA/TIA-485 (4-wire, maximum 4000 feet), baud rate 2400/9600/19200, protocol Modbus RTU/Anafaze/Allen Bradley, verification BCC/CRC.

2. Auxiliary component specifications

Power supply: Input 120/240V AC (0.75A, 50/60Hz), output 5V DC (4A), 15V DC (1.2A).

Dual DAC: Operating temperature 0-50 ℃, output supports 4-20mA, 0-5V, 0-10V, accuracy ± 0.75% of full scale, load resistance varies with output type and power supply.

Serial DAC: Operating temperature 0-70 ℃, output supports 0-10V or 4-20mA (jumper selection), can cascade up to 16, CE certified.

image.png

  • Basler D90 96801 100 PCB Card
  • Basler XR2002F Voltage Regulator (110 VAC, 48-480 Hz)
  • Basler SR8A-2B14B3A Regulator
  • Basler 9561500100 Module
  • Basler DECS-400 BE1-11 System
  • Basler DECS-100-B15 Excitation Control
  • Basler SCP 210 Frequency Controller
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE1-32R Power Relay
  • Basler PIA2400-17GM Power Interface Adapter
  • Basler MVC 232 Manual Voltage Control Module
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler 5MW AVR Generator Voltage Regulator
  • Basler VR63-4B Voltage Regulator
  • Basler DECS-100-A05 AVR for Engine Generator
  • Basler DECS-100-B15 Automatic Voltage Regulator
  • Basler BE1-32R Directional Power Relay
  • Basler BE1-87B Differential Relay
  • Basler UFOV 260A Protective Module
  • Basler 9-2614-02-100 PCB Rev M
  • Basler DECS-100-B15 Digital AVR
  • Basler 9284900103 PS DECS-400N
  • Basler D4N3H1U Intertie Protection
  • Basler DECS-100-B15 A15 AVR
  • Basler KR4F Voltage Regulator
  • Basler BE26434 T14 Transformer
  • Basler SR8A-2B15B3A Regulator
  • Westinghouse 774B472A12 AR Relay
  • Basler DECS-100-B15 AVR
  • Basler XR2002F Regulator 110V
  • Basler SR125-E Static Regulator
  • Basler SSR 125-12 Regulator
  • Basler MOC2599 Motor Pot
  • Basler BE1-DFPR Feeder Relay
  • Basler CBS 305 Current Boost
  • Basler BE1-25 AutoSync
  • Basler MVC 300 Voltage Control
  • Basler BE3-25A AutoSync
  • Basler KR7FF Static Regulator
  • Basler 90-49000-100 Regulator
  • Basler 880 kVA Dry Type Transformer Specs
  • Basler Electric BE1-25 Sync-Check Relay Specs
  • Basler SSR 125-12 Voltage Regulator Specs
  • Basler Electric BE1-851 Overcurrent Relay Review
  • Basler Electric 149D930G02 Control Sub-Assembly
  • Basler Electric BE1-81O/UT Frequency Relay Specs
  • Basler Electric BE1-51/27C Overcurrent Relay
  • Basler Electric 149D956G02 Industrial Component
  • Basler Electric BE1-51A Overcurrent Relay Specs
  • Basler Electric BE1-40Q Loss of Excitation Relay
  • Basler DECS-200 Excitation Control System
  • Basler DECS-200 Voltage Regulator 56-277V AC / 125V DC
  • Basler BE1-87T Transformer Differential Relay
  • Basler RDP-110-S1 Protection Relay
  • Basler BE1-700V Digital Protective Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler DECS-300 Digital Excitation Control
  • Basler DECS-200 Digital Excitation Control
  • Basler DECS-200-1C Excitation Control System
  • Basler DECS-200-1L Digital Excitation Control
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-200-1C Digital Excitation Controller
  • Basler Electric DECS125-15 Excitation Control with Power Module
  • Basler Electric BE1-87G Differential Relay
  • Basler Electric BE1-11 Protection System I5A3M2P2N0EA00
  • Basler Electric DECS-200-1C Excitation Control System
  • Basler Electric BE1-11g Generator Protection Relay
  • Basler Electric DECS 125-15-B2C1 V2.0.9 Excitation Control
  • Basler Electric BE1-81O/UT3ED1JA7N2F Frequency Relay
  • Basler Electric BE1-81O/UT3EE1YB7N1F Frequency Relay
  • Basler Electric DECS-200-1L Digital Excitation Control System
  • Basler DECS125-15-B2C1 Excitation Control
  • Basler 9507900205 SSR Retrofit Voltage Regulator
  • Basler BE2000E Digital Voltage Regulator
  • Basler BE1-GPS Generator Protection System
  • Basler DECS-250-CN1CN1N Digital Excitation Control
  • Basler DGC-2020 Genset Controller
  • Basler BE1-81O UT3ED1LA7N0F Frequency Relay (Variant)
  • Basler BE1-81O UT3EE1YA9S0F Frequency Relay (Variant)
  • Basler BE1-81O Over/Under Frequency Relay
  • Basler DECS125-15 Digital Excitation Control
  • Basler Electric BE1-951 Overcurrent Protection System
  • Basler Electric BE1-700V Digital Protective Relay
  • Basler Electric APR63-5 Automatic Voltage Regulator
  • Basler Electric BE1-851 Overcurrent Protection System
  • Basler Electric DECS-250-LN1SN1N Excitation Control
  • Basler Electric BE1-87T Transformer Differential Relay
  • Basler Electric DECS-200-1L Excitation Control System
  • Basler Electric 9310300100 DECS-300 Excitation Control
  • Basler Electric SSE-N 125-4.5KW Shunt Exciter Regulator
  • Basler Electric DGC-2020HD-5NS1DNSBA Genset Controller
  • Basler Electric BE1-81-O/UT3EE1JB7N1F Frequency Relay
  • Basler Electric BE1-81T1EE1WA0N1F Frequency Relay
  • Basler Electric BE1-25M1EA6PN5R1F Sync-Check Relay
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-250-LN1SN1N Excitation Control Rev V
  • Basler Electric DECS-250-CN2CN1N Excitation Control
  • Basler Electric BE1-50/51B-207 Overcurrent Relay
  • Basler Electric DECS-300-C0N0 Excitation Control System
  • Basler Electric DECS-200 Digital Excitation Control System
  • Basler Electric DECS-250-LN1CN1N Excitation Unit
  • Basler Electric DECS-250 LN2SA1D Excitation Unit Specs
  • Basler Electric BE1-87T Transformer Relay Review
  • Basler Electric BE1-11 Protection System
  • Basler Electric BE1-GPS100-E4N1H1N Protection System
  • Allen-Bradley 442G-MABH-R Safety Module
  • Beckhoff CX1030-0111 PLC Assembly Profile
  • FANUC IC693CPU364 PLC Module
  • Orange Denmark Type 200816 220 PLC Specs
  • OMRON C200H-SNT31 Sysmac PLC Module
  • Allen Bradley 20AB022A3AYNANC0 PowerFlex 70
  • OMRON C200HW-PCU01 Position Control Unit
  • ABB AO845A-eA Analog Output Module
  • OMRON CJ1M-CPU22 CPU Unit
  • Allen Bradley 100-E265ED11 Contactor
  • Honeywell 51304511-100 Interface Module
  • SOLEXY BXF3S0101N0018 Gateway Module
  • OMRON CJ2H-CPU65 CPU Unit
  • Automation Direct GS2-45P0 AC Drive
  • M68-2000 2-Axis Motion CNC Controller
  • OMRON CJ1M-CPU11 V3.0 PLC CPU Unit
  • OMRON CJ1W-NC413 4-Axis Positioning Controller
  • OMRON 3G2A3-PRO16 Programming Console HMI
  • Siemens 3VT8440-2AA04-2GA2 Molded Case Circuit Breaker
  • Siemens 3RT5045 Contactor Series
  • OMRON C200HS-CPU01-E SYSMAC PLC Controller
  • OMRON C500-NC103-E Positioning Control Unit
  • OMRON CJ1W-TC001 Temperature Control Unit