Short circuit current rating (SCCR): 1492-CAM1 has an SCCR of 100000A at 600V, and 1492-CE2 also has an SCCR of 100000A at 600V to ensure equipment safety in the event of a short circuit fault.
(4) Power Blocks
Application positioning: Used in high-power distribution scenarios, such as industrial equipment power distribution, large motor control, etc., supporting large cross-section wires (such as 250kcmil, 600kcmil) and high current (such as 760A).
key performance
Short circuit current tolerance: Most models have a high fault SCCR of 100000A (such as 1492-BE, 1492-BF), and some models have an SCCR of 35000A when used in conjunction with circuit breakers. The selection of overcurrent protection devices should be based on the type to ensure that the system is not damaged in the event of a fault.
Wire connection: 1492-PD3163 supports 400kcmil... 3/0Cu wires (input end) and 2-8AWG wires (output end), allowing multiple small wires to be connected to meet power distribution requirements; Some models distinguish between copper (marked with "C") and aluminum terminals, and are compatible with wires of different materials.
Safety and maintenance: Provide protective covers (such as the 1492-PBC series) and marking strips to facilitate circuit identification and prevent accidental contact; Clear size parameters facilitate installation layout planning.
Terminal block accessory system
(1) IEC terminal block accessories
Installation and fixing category
Installation guide rail: such as 199-DR1 (35mm × 7.5mm × 1m), 1492-N1 (breakable 3ft guide rail), used to fix the terminal block, reduce the use of panel screws, and facilitate the disassembly and adjustment of the terminal block.
End anchor and end baffle: 1492-EAJ35 end anchor enhances the rigidity of the terminal block group to prevent sliding along the guide rail; The 1492-EBL series end shields (such as 1492-EBL3) provide insulation protection and are compatible with terminal blocks of different heights.
Circuit connection and isolation class
Jumper: divided into screw type (such as 1492-CJJ series) and non screw type (such as 1492-CJL series), supports 2-50 pole configuration, can be cut, and carries 100% rated current of the terminal block. Attention should be paid to the derating (such as 400V) and partition requirements when crossing different potentials.
Partitions and separators: The 1492-PPJD3 partition is used for visual and electrical isolation of terminal groups, while the 1492-SP3 partition isolates adjacent jumpers to ensure circuit safety.
Testing and Identification Category
Test plugins: 1492-TP23 test plug, 1492-TPS23 test socket, convenient for circuit testing; 1492-TA285 test adapter, suitable for different testing scenarios.
Marking system: ClearMark printer (600/1200dpi, supports color printing) and X-Y plotter meet different batch marking requirements; Blank markings (such as 1492-M3X12), pre printed markings (by serial number), and custom markings can be designed and ordered through software to ensure clear circuit identification.
(2) NEMA terminal block accessories
Stacking Bridge: Composed of 1492-N26 (external mounting pins), 1492-N27 (side panel extensions), etc., it can stack up to 4 layers of terminal blocks, saving panel space. Only fuse blocks, circuit breakers, etc. are allowed to be installed on the top layer.
Marking and tools: 1492-N43 label paper (132 pieces/sheet), 1492-N8 engravable marking strip, used for terminal identification; 1492-N90 screwdriver (3mm hardened blade), 1492-KWC wire breaking tool, convenient for installation and operation.
Selection and application precautions
Standard adaptation: Select certified terminal blocks based on the application region (such as NEMA for North America and IEC for Europe) and industry standards (such as ATEX for explosion-proof environments) to avoid compliance risks.
Electrical parameter matching: Based on the circuit voltage, current, and wire specifications, select the terminal block according to its rated value. For example, choose the 1492-J120 and 1492-PD series for high voltage and high current scenarios, and choose 1492-W3 and 1492-L3 for low current control circuits.
Environmental adaptation: 1492-15T and 1492-25T are preferred for high-temperature environments; Choose spring clip type terminal block (1492-L series) for vibration environment to ensure stability.
Safety and maintenance: Reasonably select accessories (such as end shields, testing plugins, marking systems) for easy maintenance and troubleshooting in the later stage; Follow the requirements of tightening torque, wire stripping length, etc. to avoid faults caused by poor connections.
Short circuit current consideration: Based on the type and rated value of overcurrent protection devices (fuses, circuit breakers), confirm the SCCR of the terminal block to ensure safety in case of system failure, and refer to the SCCR table in the document for selection.