Docket Nos.: 50-424 NL-21-0444
50-425
U. S. Nuclear Regulatory Commission
ATTN: Document Control Desk
Washington, D. C. 20555-0001
Southern Nuclear Operating Company
Vogtle Electric Generating Plant – Units 1 and 2
Supplement to License Amendment Request to Revise
Technical Specification 3.3.5.2 Allowable Values
Ladies and Gentlemen:
On March 30, 2021 (ML21089A388), pursuant to the provisions Section 50.90 of Title 10 Code
of Federal Regulations (CFR), Southern Nuclear Operating Company (SNC) requested a
license amendment to Vogtle Electric Generating Plant (VEGP) Unit 1 renewed operating
license NFP-68 and Unit 2 renewed operating license NFP-81. The proposed amendment
revises Technical Specification (TS) 3.3.5, “Loss of Power (LOP) Instrumentation”, Surveillance
Requirement (SR) 3.3.5.2 Allowable Values.
On April 19, 2021 (ML21095A087), the U.S. Nuclear Regulatory Commission (NRC) staff
provided the results of their acceptance review and concluded that technical information was not
provided in sufficient detail to enable the NRC staff to complete its detailed review. In order to
make the application complete, the NRC staff requested that SNC supplement the application
by May 6, 2021.
SNC’s response is provided in the Enclosure.
SNC requests the same approval and implementation schedule as requested in its original
application.
The conclusions of the No Significant Hazards Consideration Determination Analysis and
Environmental Consideration contained in the original application have been reviewed and are
unaffected by this supplement.
This letter contains no NRC commitments. If you have any questions, please contact Jamie
Coleman at 205.992.6611
SNC Response to NRC Request for Supplemental Information
E-1
NRC Request to Supplement
The NRC staff identified that the following information is needed, within 13
working days from the date of this letter, to begin its detailed technical review:
The as-found tolerance (AFT) and as-left tolerance (ALT) values of the
nominal trip setpoint (NTS) calibrations.
The potential transformer ratio (for voltage conversion from the
transformer’s primary winding to secondary winding).
Verification of (a) the current Analytical Limits (ALs) of the 4.16 kV
Engineered Safety Features (ESF) Bus LOP Instrumentation are 2912 V
(Loss of Voltage) and 3683 V (Degraded Voltage), and (b) these ALs are
not changed in the calculation.
The NRC staff identified the following information as a request of additional
information (RAI) which should be provided with the supplemental information
requested for acceptance. If this information cannot be provided, please provide
a date when it will be available:
The full model numbers and the vendor (ABB) datasheets of the affected
relays, including the relays’ applicable pickup and dropout voltages and
performance tolerances. Also, discuss whether a harmonic filter will be
used, which could affect the repeatability versus temperature range
uncertainty.
The full model numbers and the vendor datasheets of the voltage-tocurrent
module and the analog-to-digital module, including the uncertainty
values of these devices.
The NRC staff needs the above information to begin its detailed technical review
and perform an independent verification of the allowable values for the LOV and
DV relays’ trip setpoints.
SNC Response to NRC Request for Supplemental Information
E-2
of the sensing transformer. Using the sensing transformer ratio of 35:1, the
AFT and ALT Values on the 4160 Volt side of the sensing transformer is
equal to +/- 0.30 Volts x 35. The Loss of Voltage AFT and ALT Values are
+/- 10.5 Volts about the NTS of 2975 Volts.
The winding ratio of the sensing potential transformer is 35:1.
The Analytical Limit (AL) for Degraded Voltage is 3683V and for LOP is
2912V. The ALs have not changed in the calculation.
There are not any physical bistable relays. They are modeled in software.
The pickup and dropout voltages are the ‘Setpoint’ and ‘Reset’ values. The
values and tolerances on the 120 Volt side of the sensing transformer for
degraded voltage and loss of voltage are listed below. A harmonic filter is not
needed because there aren’t any physical relay contacts opening and closing
and generating harmonics when doing so. There is an analog low pass
prefilter and a digital low pass filter built into the analog-to-digital module
(ABB AI620).
Degraded Voltage:
Setpoint (pickup) = 107.03V Hi Limit = 107.33V Low Limit = 106.73V
Reset (dropout) = 108.53V Hi Limit = 108.83V Low Limit = 108.23V
Loss of Voltage:
Setpoint (pickup) = 85.00V Hi Limit = 85.30V Low Limit = 84.70V
Reset (dropout) = 86.50V Hi Limit = 86.80V Low Limit = 86.20V
The Dataforth voltage-to-current module part number supplied by
Westinghouse is DSCA33-1566. The accuracy data for this Westinghouse
part number is the same as the non-proprietary accuracy data for Dataforth
part number DSCA33-04C. The non-proprietary data sheet for Dataforth part
number DCCA33-04C is provided as Attachment 1 to this Enclosure. The
ABB analog-to-digital module part number is Al620. The non-proprietary data
sheet for the ABB part number AI620 is provided as Attachment 2 to this
Enclosure.
Features
• Interfaces RMS Voltage (0 – 300V) or
email:1583694102@qq.com
wang@kongjiangauto.com