(1) Environmental adaptability
Temperature range:
-Operating temperature: Vertical installation 0-50 ° C, maximum tilt angle 0-40 ° C; vertical screen installation 0-40 ° C, maximum tilt angle 0-35 ° C
-Storage/transportation temperature: -20-60 ° C
Humidity: Maximum relative humidity of 90% (without condensation)
Installation angle: Vertical installation is the main method, with a maximum tilt angle of 35 ° (without external ventilation)
(2) Certification and Compliance
Basic certifications: CE, KC, cULus, RCM (formerly C-TICK)
Maritime certification: GL, ABS, BV, DNV, LRS, NK, not supported by PRS
Hazardous Area Use: Supports ATEX Zone 2/22, IECEx Zone 2/22 (soon to be available) cULus Class I Zone 2(Division 2)、FM Class I Division 2, Not supporting cULus Class I Zone 1
EMC compliance: Complies with EN 55 011 radio interference emission standard (limit level A, non level B)
Equipment compatibility
Support coupling communication with various industrial equipment, including Siemens S7-1200/1500/200/300/400, LOGO! 、 Win AC、SINUMERIK, And third-party devices such as Allen Bradley(EtherNet/IP、DF1)、Mitsubishi(MC TCP/IP、FX)、OMRON(LINK/Multilink, Not supporting FINS TCP, Modicon (Modbus TCP/IP, Modbus); Support OPC UA client (non server).

Email:wang@kongjiangauto.com