International certification: meets ROHS environmental requirements; CE certification requires the use of appropriate filters to cover the 2004/108/EC Electromagnetic Compatibility Directive (EN 61326 Industrial Immunity Class A emission, not applicable to Class B environment) and the 2006/95/EC Low Voltage Directive (EN 50178 safety requirements), but phase angle and phase angle input control signal types with current limitation (P and L) do not have CE certification 🔶 1-45 🔶 1-46 🔶 1-47 🔶 1-48 🔶 1-49 🔶 1-50 🔶 1-51.
North American certification: UL ® 50 Type 4X shell certification, UL ANSI/ISA 12.12.01 temperature code T4A; The through wall heat sink component is suitable for Class I, Zone 2, Groups A, B, C, and D hazardous and non hazardous areas, but safety warnings such as "replacing any component may affect the applicability of hazardous areas" and "cannot be disconnected when the circuit is live unless the area confirms that there is no flammable concentration" are clearly stated 🔶 1-54 🔶 1-55 🔶 1-56; Simultaneously for UL ® 508 listed products, C-UL ® Document number E73741.

Installation specifications and size requirements
1. Installation method and steps
(1) DIN rail installation (DIN EN 50022, 35 × 7.5mm rail)
Installation steps: ① Push the device in and press down to clamp the top rail hook into the rail; ② Rotate the bottom of the device towards the guide rail; ③ The guide rail buckle will "click" to fasten. If it is not fastened, check whether the guide rail is bent; ④ The heat sink must be installed vertically (core requirement to ensure heat dissipation efficiency) 🔶 1-223 🔶 1-224 🔶 1-225.
Disassembly steps: Press and release the buckle, while rotating the device upwards and away from the guide rail to remove it.
Spacing requirement: A 102mm (4.0 inches) gap should be reserved on the side for airflow and wire bending radius; The front is designed with anti touch features, requiring no additional clearance; Minimum snap distance 34.8mm (1.37 inches), maximum 35.3mm (1.39 inches) 🔶 1-236 🔶 1-245.
(2) Panel installation
Four M4 (# 8) fasteners are required for fixation. Please refer to the panel installation dimension diagram on page 7 of the manual for specific dimensions, with a focus on the grounding wire entry position (13mm/0.50 inches) and the parallel arrangement wire gap (83mm/3.25 inches).
(3) Wall through installation (UL) ® 50 Type 4X Shell Model
Additional materials: 1 silicone gasket, 8 M5 screws and locking washers, 1 DIN-A-MITE C wall penetrating device 🔶 1-253 🔶 1-254 🔶 1-255.
Installation steps: ① Drill holes and cut the panel according to the size diagram on the right; ② Remove the mounting screws from the heat sink; ③ Tear off the protective film of the silicone gasket, attach the gasket to the heat sink, and ensure that the gasket hole is aligned with the heat sink screw hole; ④ Vertically install heat sink, torque controlled at 2.26-2.82 Nm (20-25 inch pounds) 🔶 1-257 🔶 1-258 🔶 1-259.
Size and Gap: The panel opening should meet the contour requirements of 178mm (7.00 inches) × 122mm (4.81 inches), and a minimum gap of 102mm (4.0 inches) should be reserved above and below the heat sink for airflow. A minimum gap of 10mm (0.4 inches) should be reserved on both sides.
2. Requirements for wiring terminals
(1) Input terminal (control signal type)
Adopting a crimping design, compatible with 0.2-1.5mm ² (24-16 AWG) wires; Use a 3.5mm (1/8 inch) flathead screwdriver and tighten to a torque of 0.5 Nm (4.4 inch pounds); The stripping length of the wire is 5.5mm (0.22 inches); The insulation level of the wire must be ≥ 75 ° C and is only applicable to copper conductors 🔶 1-61 🔶 1-62 🔶 1-63 🔶 1-64.
(2) Main circuit terminals (phase line, load, grounding)
Also of crimping type, compatible with 2.5-25mm ² (14-3 AWG) wires; Can be tightened with a 6.4mm (1/4 inch) flathead screwdriver or a 1A type # 2 Pozidriv screwdriver to a torque of 2.7 Nm (24 inch pounds); Wire stripping length 11mm (7/16 inches); Core maintenance requirement: Re tighten after 48 hours (to reduce wire cold flow), and then re tighten every 3-6 months thereafter 🔶 1-66 🔶 1-67 🔶 1-68 🔶 1-69 🔶 1-70.
(3) Cooling fan terminal
Adopting a quick connect design (1/8 inch push in), compatible with 16-14 AWG wires; Recommend using Amp part number 640929-1 or equivalent product 🔶 1-85.
Control mode and signal configuration
1. Zero crossing control mode (including contactor and proportional control)
(1) Type of contactor (input control signal)
DC input (Type C): 4.5-32V (DC) input, with a maximum current of 6mA per channel at 4.5V. An additional 2mA total current is required for each additional LED; To extend the service life, the cycle time should be less than 3 seconds 🔶 1-94.