AC input (Type K): Suitable for 24V (ac) ± 10%, 120V (ac)+10%/-25%, 240V (ac)+10%/-25%, with a maximum current of 25mA per circuit; it is strictly prohibited to share with temperature controllers with RC buffer circuits. If used, the RC buffer circuit must be removed first; Cycle time should be less than 3 seconds to extend lifespan 🔶 1-95 🔶 1-98.
(2) Proportional control (Type F, 4-20mA DC)
Variable time base control for loop power supply, only applicable to F0 input option; A current source of 8.0V (dc) or higher is required, with no more than 2 series inputs; Linearity requirements: Full open point 19.5-19.9mA (dc), maximum peak voltage 6.2V; Input output power accuracy ± 5% (0% -100% range, 4.3-19.7mA or 12.3-19.7mA); Temperature stability<0.15%/° C 🔶 1-96 🔶 1-102 🔶 1-105 🔶 1-106.
2. Phase angle and single cycle variable time base control
(1) Phase angle control (single-phase specific)
Applicable models: Type P (pure phase angle), Type L (phase angle with current limitation), only supports single-phase configuration, and has no alarm option 🔶 1-111.
Input signal: Supports 0-20mA, 4-20mA, 12-20mA (DC) and 0-5V, 1-5V, 0-10V (DC); Input impedance: 4-20mA signal is 250 Ω, linear voltage signal is 5k Ω 🔶 1-112.
Output and accuracy: Output voltage covers 100-120V, 200-208V, 230-240V, 277V, 400V, 480V, 600V (ac), deviation -15%/+10%, frequency 50/60Hz (deviation ± 5%); At 25 ° C, the output conduction time is directly proportional to the command signal, with an accuracy of ± 5%; Temperature stability<0.25%/° C 🔶 1-115 🔶 1-117.
Soft start function: 5-second soft start when powered on, soft start when thermostat overtemperature occurs, soft start when half cycle dropout detection occurs, 1-second soft switching when set value changes, protecting load and devices 🔶 1-124 🔶 1-125 🔶 1-126.
(2) Single cycle variable time base (Type S)
Working logic: At 50% power, "1 cycle on, 1 cycle off"; At 25% power, "conduct for 1 cycle and close for 3 cycles"; Continuous conduction for no more than 1 cycle when power is less than 50%, and continuous shutdown for no more than 1 cycle when power is greater than 50% 🔶 1-110.
Accuracy and adaptability: The output power is proportional to the command signal at 25 ° C, with an accuracy of ± 5%; Temperature stability<0.25%/° C; supports linear voltage, 4-20mA or potentiometer input 🔶 1-120.
3. Resolution and Additional Options
Resolution: The accuracy of the output variation relative to the input range is greater than 0.1%.
Manual control kit: Optional 1k Ω single turn potentiometer (with 0-100% dial), part number 08-5362.

Ordering coding rules and current levels
1. Model code disassembly (complete code: DC+phase+cooling/current+voltage+control signal+alarm+language+customization)
Meaning and Options of Encoding Segments
DC prefix: Fixed identifier (DIN-A-MITE Style C)
Phase configuration 1=single-phase 1 controlled leg; 2=Three phase 2 controlled legs; 3=Three phase, three controlled legs (four wire star); 8=2 independent area; 9=3 independent areas
Cooling/current 0=natural convection (standard DIN rail/panel heat sink); 1=120V AC fan cooling; 2=240V AC fan cooling; 3=24V DC fan cooling; T=Natural convection (wall/cabinet type heat sink, UL 50)
Voltage level 02=24-48V AC (C/F/K control); 12=100-120V AC (L/P/S control); 20=200-208V AC (L/P/S control); 24=120-240V AC(C/F/K)/230-240V AC(L/P/S); 27=277V AC(L/P/S); 40=400V AC(L/P/S); 48=480V AC(L/P/S); 60=277-600V AC(C/F/K)/600V AC(L/P/S)
Control signal C0=4.5-32V DC contactor; K1=22-26V AC contactor; K2=100-120V AC contactor; K3=200-240V AC contactor; F0=4-20mA ratio (loop power supply); L (0-5)=phase angle with current limitation (single-phase); P (0-5)=phase angle (single-phase); S (0-5)=single cycle variable time base; Input types corresponding to 0-5 in parentheses: 0=4-20mA, 1=12-20mA (S only), 2=0-20mA, 3=0-5V DC, 4=1-5V DC, 5=0-10V DC
Alarm option 0=No alarm; S=SCR short circuit alarm (not applicable to 8/9 area or L/P control); H=heater open circuit+SCR short circuit alarm (only S control)
Manual language 0=English; 1=German; 2=Spanish; 3=French
Customized option 00=standard parts; 1X=1-second soft start (P/L control); XX=Custom Options/Identification
2. Current level table (by model prefix)
Model prefix Current level Remarks
DC10 55A natural convection (standard heat sink)
DC1T 62A natural convection (through wall/cabinet type heat sink)
DC11/DC12/DC13 75A fan cooling (120V AC/240V AC/24V DC)
DC20/DC80 40A three-phase 2-leg/2-zone, natural convection
DC2T/DC8T 46A three-phase 2-leg/2-zone, through wall heat sink
DC81/DC82/DC83/DC30/DC90 30A 2-zone fan cooling/three-phase 3-leg/3-zone natural convection
DC3T/DC9T 35A three-phase 3 leg/3 area, wall penetrating heat sink
DC31/DC32/DC33/DC91/DC92/DC93 55A three-phase 3 leg/3 zone, fan cooling
Selection of fuses and EMI filtering
1. Semiconductor fuse (suitable for applications with 600V AC and below)
Rated current of fuse Watlow fuse model Bussman fuse model Watlow bracket model Ferraz bracket model