Event recording and alarm: Supports out of limit alarm detection (upper/lower limit monitoring), can monitor parameters such as voltage, current, active/reactive/apparent power, power factor, frequency, etc. Each monitoring object can generate out of limit SOE and return SOE, with a maximum of 32 out of limit alarm events recorded.
Input/output control: equipped with 4 passive switch inputs, capable of recording up to 32 switch SOE events; Supports 2-channel relay control output, enabling remote control and linkage protection.
3.2 Detailed explanation of time-sharing billing function
IQ500 has powerful time of use billing capabilities to meet the refined management needs under complex electricity pricing policies
Flexible configuration of rates and time periods: up to 4 rates, 12 time periods, 8 time period tables, 12 annual time zones, 90 public holidays can be set, and a weekly holiday time period table can be set.
Priority execution mechanism: Prioritize the execution of the time period table used for public holidays, followed by the time period table used for weekly holidays, and finally execute the time period table used for each time zone.
Dual switching mechanism: It has two sets of time zone tables, two sets of daily time period tables, and two sets of public holiday tables, and can automatically switch at set time points to adapt to seasonal or policy based electricity price adjustments.
3.3 Data Freeze Function
IQ500 supports multiple data freezing modes, providing a foundation for data analysis and auditing:
Periodic timed freezing: Based on the set freezing time, achieve timed freezing of electricity data on a monthly, daily, or hourly basis.
Instant Freeze: Immediately generate a freeze record after receiving the instant freeze command through communication.
Agreement freeze: When two sets of time zone tables switch, two sets of daily time period tables switch, or two sets of public holiday transitions occur, an agreement freeze is triggered once.
Freeze content: including total active power, total reactive power, and total active and reactive power data for each phase.
Storage capacity: The device can record 12 frozen records.

Technical indicators and performance parameters
4.1 Working Parameters
Power characteristics:
Working power supply: 85-265VAC or 85-265VDC (wide voltage input range, suitable for different on-site power supply conditions)
Power consumption: ≤ 2W (low-power design, reduces power supply burden)
Environmental adaptability:
Working temperature: -25 ℃~+70 ℃ (suitable for harsh industrial environments)
Storage temperature: -40 ℃~+85 ℃ (meets transportation and long-term storage needs)
Humidity condition: 95% non condensing (suitable for high humidity environments)
Mechanical characteristics:
Dimensions: 96 × 96 × 78mm (width × height × depth), in compliance with DIN96 × 96 standard
Weight: Segmented LCD display module
Installation method: Panel hole installation, hole size 91 × 91mm
Protection level: Panel IP52, shell IP20 (front panel dustproof and waterproof, internal anti solid foreign object)
4.2 Input/output characteristics
Voltage input:
Rated value: 220VAC
Measurement range: 20VAC~264VAC
Extended measurement range (via PT): 0-42000V
Current input:
Rated value: 5A or 1A (two specifications are optional)
Measurement range: 5A specification 0.05-6A; 1A specification 0.01-1.2A
Continuous overload capacity: 1.2 times the rated current
Instantaneous overload capacity: 20 times rated current, duration<1s
Extended measurement range (via CT): 0-6000A
Frequency characteristics:
Rated value: 50Hz or 60Hz (configurable)
Measurement range: 45-65Hz
Switch input:
Type: Passive Node Optical Isolation Input
Isolation voltage: 1500VDC
Relay output:
Capacity: 250V/5A AC or 30V/5A DC
Purpose: Remote control, alarm output
Transmission output (optional):
Signal: 4-20mA
Load resistance: ≤ 600 Ω
Isolation voltage: 500VDC
4.3 Measurement accuracy
IQ500 achieves industry-leading accuracy levels in all measurement dimensions:
Parameter accuracy level measurement range
Voltage level 0.2 0~42000V
Current 0.2 level 0-6000A
Power factor 0.5 level 0 ≤ | COS φ | ≤ 1
Active power level 0.5 0~756000kW
Reactive power level 0.5 0~756000kvar
Visual power level 0.5 0~756000kVA
Electricity measurement level 0.5 0~9999999.9kWh
Frequency 0.02Hz 45-65Hz
Harmonic S level 2-31st order
4.4 Electromagnetic compatibility performance
IQ500 has adopted various anti-interference measures in the design process, which can operate stably in complex power system environments. Its electromagnetic compatibility performance has reached the international advanced level:
Test project standard code level
Electrostatic discharge immunity GB/T 17626.2-2018 Level 4
Radio frequency electromagnetic field radiation immunity GB/T 17626.3-2016 Level 3
Electrical Fast Transient Pulse Group Immunity GB/T 17626.4-2018 Level 4
Surge immunity GB/T 17626.5-2019 Level 4
Radio frequency conducted immunity GB/T 17626.6-2017 Level 3
Power frequency magnetic field interference test GB/T 17626.8-2006 Level 4
Damping oscillation magnetic field interference test GB/T 17626.10-2017 Level 4
The electrostatic discharge, electrical fast transient pulse group, and surge immunity all reach level 4 (the highest level), ensuring reliable operation in harsh electromagnetic environments.