ANB10 - E/ANB11 - E/ANR10 - E Hazardous Area ≤ 88
ANB10 F/ANB11 F/ANR10 F Hazardous area ≤ 80
AFV10D/AFV30D (dual redundancy) non hazardous area factor A ≤ 20; Factor A+Factor B ≤ 65
(2) Spacing and isolation requirements
The intrinsic safety zone and non intrinsic safety zone must maintain a distance of ≥ 50mm. The node unit (ANB10 ) needs to be equipped with an insulation partition (T9083NA), and the FCU (AFV10 /AFV30 ) needs to be equipped with an insulation partition kit (T9083ND);
The built-in isolation barrier module needs to be installed separately from other modules to avoid electromagnetic interference.
(3) Special environment and module limitations
Wide temperature environment (60-70 ℃): A maximum of 4 IOMs can be installed on a single node, and slots need to be left between modules. Installation of AAI543- 6 /- F (quick response type) is prohibited;
TC input module (AAT141/AAT143): It should be kept away from heat sources (such as CP461, bus interface module), avoid direct airflow, and can only be installed adjacent to designated modules (AAT141, AAR181, etc.);
Dual redundancy configuration: I/O modules need to be installed in paired slots (IO1-IO2, IO3-IO4, etc.), and empty slots need to be protected with a false cover plate (ADCV01).
Compliance standards
Safety standards: CSA, CE Marking, EAC Marking;
EMC standards: CE Marking, EAC Marking, RCM, KC Marking (excluding built-in isolation barrier modules);
Explosion proof standards: CSA/FM Non Intrinsic, Type n, Type i, FM certified.