Software and hardware specifications
1. Hardware specifications
Specification category specific parameters
Backplane compatibility single slot 1756 ControlLogix backplane, supporting local rack and remote rack deployment
Backboard current load 5VDC: 800mA; 24VDC:3mA
Ethernet port (E1) 10/100 Base-T, RJ45 interface (compatible with CAT5 cable); Support automatic cross cable detection; Equipped with Link/Activity LED indicator light
Environmental parameters (operation) - MVI56E-MNET: 0 ° C~60 ° C (32 ° F~140 ° F);
-MVI56E-MNETXT: -25 ° C~70 ° C (-13 ° F~158 ° F) (protective coating+wide temperature design)
Environmental parameters (storage) -40 ° C~85 ° C (-40 ° F~185 ° F)
Impact resistance performance during operation: 30g; non operation: 50g
2. Functional specifications
Data transmission optimization: Transfer data at the maximum I/O image block size to improve throughput and update speed.
Module identification: Recognized as an "I/O module" (non communication module) in the ControlLogix processor, adapted to the system's native I/O management logic.
Special function support: Through the "block transfer code" in ladder logic, special operations such as module state reading, instruction control, and event instructions can be achieved.
Derivative models: Provide MVI56E-MNETR model (remote rack optimized version), support reducing data block size, and adapt to remote rack bandwidth limited scenarios.
Email:wang@kongjiangauto.com