7.3 Speed/Analog IO Combination Intelligent Enhancement Module
This module provides four speed inputs (configurable as MPU, Prox, or Eddy inputs in GAP applications) as well as 12 analog inputs and 4 4-20 mA outputs. The analog input can be configured as 0-5VDC voltage mode or 4-20mA current mode in GAP applications.
8、 Safety regulations and compliance
The MicroNet digital control system follows strict safety standards and regulatory requirements:
8.1 European Compliance
CE mark: The product complies with the relevant EU directive requirements
RoHS: Compliant with Directive 2011/65/EU requirements
EMC Directive: Compliant with the 2014/30/EU Electromagnetic Compatibility Directive
Low Voltage Directive: Compliant with the 2014/35/EU Low Voltage Equipment Directive
ATEX Directive: Compliant with the 2014/34/EU Directive on Equipment for Potential Explosive Environments
8.2 North American Compliance
CSA certification: applicable to Class I, Division 2, Groups A, B, C, and D areas, with a maximum ambient temperature of 55 ° C
8.3 Classification Society Certification
American Bureau of Shipping (ABS): Complies with steel vessel code requirements
Lloyd's Register (LR): Complies with LR type approval test specifications
DNV/GL: Complies with standard certification requirements
9、 Installation and Maintenance Guide
9.1 Installation precautions
The MicroNet digital control system must be installed in a metal enclosure or cabinet to meet EMC directive requirements. Please refer to section 15 of manual 26166V2 for installation location and specific cabinet construction requirements.
The system grounding requirements are strict, and the grounding leakage current exceeds 3.5 mA. Before supplying power to the MicroNet control device, it is necessary to verify that the PE terminal is connected. Fixed wiring installation is required, and the main power circuit should be blown correctly according to national standards. It is recommended to use European T-type fuses.
9.2 Electrostatic discharge protection
The electronic control device contains electrostatic sensitive components, and the following precautions should be taken to prevent damage:
Release body static electricity before handling control devices
Avoid using plastic, vinyl and foam around printed circuit boards
Do not touch the components or conductors on the printed circuit board with your hands or conductive devices
9.3 Fault diagnosis and troubleshooting
The system provides comprehensive diagnostic functions, which can monitor system status, view fault codes, and configure network settings through AppManager software. Each module is equipped with LED indicator lights to display module status and fault information, making it easy to quickly locate and solve problems.
10、 Technological development trends and application prospects
With the advancement of Industry 4.0 and digital transformation, MicroNet digital control systems continue to evolve and integrate new technologies to meet more stringent industrial application requirements
10.1 Intelligent Upgrade
The new generation MicroNet control system has strengthened support for condition monitoring and predictive maintenance, helping users optimize equipment performance and reduce unexpected downtime by integrating more advanced diagnostic algorithms and data analysis functions.
10.2 Communication Protocol Extension
The system continues to expand its support for modern industrial communication protocols, including OPC UA, MQTT, and higher-level Ethernet protocols, ensuring seamless integration with factory information systems.
10.3 Network Security Enhancement
Faced with increasingly severe industrial network security challenges, Woodward continuously strengthens the security features of MicroNet control systems, including secure boot, communication encryption, and access control functions.

Email:wang@kongjiangauto.com