6.4 MOVILINK ® Read Example (Read firmware version, index 8300)
WRITE.req user data:
Request reference = 0x01
Request ID = 0x40
Axis = 0x00
No. of parameters = 0x01
Attribute = 0x10(READ)
No. of elements = 0x00
Parameter number = 0x206C(8300 dec)
Subindex = 0x0000
Positive response READ.res:
Response ID = 0x40
Format = 0x43
No. of values = 0x01
Value=0x311C7289 (823947913 → firmware version 823 947 9.13)
6.5 MOVILINK ® Write example (volatile write IPOS variable H0, index 11000, value 12345)
WRITE.req:
Attribute = 0x30(WRITE volatile)
Parameter number = 0x2AF8
Value = 0x00003039(12345 dec)
6.6 PROFIdrive Write Example (non-volatile write fixed set point n11, index 8489)
WRITE.req:
Request ID = 0x02
Attribute = 0x10
Parameter number = 0x2129
Value = 123(0x7B)
Attention: The Change parameter of PROFIdrive will be written to EEPROM, and frequent operation may reduce its lifespan. For high-frequency parameter modification, MOVILINK should be used ® WRITE volatile。
6.7 DP-V1 Error Code (Telegram Layer)
The meaning of Error Class Error Code
0xB (access) 0x0 Invalid index (e.g. DS47 does not exist)
0xB 0x5 status conflict (0xB5), please retry READ
0xB 0x7 invalid range (DS47 header error)
0xC (resource) 0x2 Resource busy
Running MOVITOOLS via PROFIBUS ® MotionStudio
7.1 Hardware and software requirements
Hardware: Siemens CP5512 (PCMCIA) or CP5611 (PCI) PROFIBUS master card.
software
STEP7 V5.3 SP3 or higher (optional)
SIMATIC NET Softnet DP Driver (V6.0+)
MOVITOOLS ® MotionStudio V5.20+
7.2 Configuration steps
Install drivers and software.
Select the CP card in "Set PG/PC Interface" and set the parameters (baud rate, station address, uncheck "Unique Master Station").
Diagnostic test: Click "Test" to confirm OK, and click "Read" to list all devices on the bus.
Start MOVITOOLS ® MotionStudio, Open the SEW communication server.
Add PROFIBUS communication channel by drag and drop, configure as C2 master station.
Perform unit scan (F5), locate online devices, switch to online mode to perform parameter reading and writing, oscilloscope monitoring, etc.
7.3 Common Problems
The bus terminal resistance is not set correctly.
The PC address conflicts with an existing master station.
Checking 'PG/PC is the only master on the bus' prevents coexistence with C1 master station.
The baud rate does not match the actual bus rate.
Fault diagnosis
8.1 Diagnostic Process
Problem 1: The frequency converter is not working on PROFIBUS (BUS FAULT is on)
Check cable connections and terminal resistance.
Is the checkpoint address within the range of 1-125.
Check if the GSD file is correct and if the configuration has been downloaded.
Check if the main station is running.
Problem 2: The frequency converter can communicate but cannot be controlled
Check if P100/P101 is set to FILDBUS (or SBus).
Use P094~P097 to check if the process data is received correctly.
Check if the terminal enable signal has been provided.
Check if SFC14/15 is used in the program to ensure data consistency.
8.2 Fault code list (optional)
Possible causes and countermeasures for fault code names
28 fieldbus timeout, master-slave communication interruption check, master station communication, extend monitoring time
37 Watchdog Error System Software Error Contact SEW Service
45 initialization error reset after self check failure, power off and restart. If it repeatedly occurs, send it for repair
111 system error (gateway): The device on SBus cannot be addressed or the DFP itself is faulty. Check the SBus wiring and terminal resistance, and power on again
Technical Data Summary
9.1 DFP21B for MOVIDRIVE ® MDX61B
Parameter values
Order number 824 240 2
Power consumption 3 W
Baud rate 9.6 k~12 Mbaud automatic detection
Connector 9-pin Sub-D, compliant with IEC 61158
Station address 1-125 (DIP switch)
GSD file SEW_6003.GSD/SEWA6003.GSD
DP identification number 6003 hex (24579 dec)
Maximum PD quantity of 10 words
Diagnostic data 8 bytes
9.2 DFP21B is used for gateway mode (MOVITRAC) ® B / UOH11B)
Parameter values
External power supply DC 24V (-15%/+20%), Imax ≤ 200 mA, Pmax=3.4 W
Baud rate is the same as DP
GSD file SEW_6009.GSD
DP identification number 6009 hex (24585 dec)
The maximum number of SBus slave stations is 8
Each slave station has a PD number of 3 characters (fixed)
9.3 Environment and Dimensions
Working temperature: 0 ° C~+55 ° C
Storage temperature: -25 ° C~+70 ° C
Protection level: IP20
UOH11B shell dimensions (width x height x depth): approximately 83 x 75 x 22.5 mm (can be installed on DIN rails)