Full range calibration (negative direction):
Input -5V (± 5V range) or -10V (± 10V range) to all channels;
Adjust the potentiometer until the average digital value of all channels is -32000;
Accuracy verification: Enter+5V/+10V again to verify the numerical deviation:
PPX: 505-6108A: allowable deviation of ± 129/± 128;
PPX: 505-6108B: allowable deviation of ± 81/± 80;
Restore wiring: After calibration is complete, power off, remove the calibration equipment, restore on-site wiring and module installation positions, and reconfigure I/O addresses.
5.3 Calibration steps for output module (PPX: 505-6208A/6208B)
Power outage preparation: Turn off the controller and user power, disconnect the module load from the on-site wiring, and retain the user power wiring;
Load connection: Connect calibration loads to all output channels of the module (voltage channel connected to a 5.1k Ω resistor, current channel connected to a 100 Ω resistor);
Power on preheating: Turn on the controller and user power, wait for 30 minutes for the module to reach operating temperature;
Device connection: Connect programming devices and controllers to ensure that digital data can be written to the module;
Full range output: Write a digital quantity of 32000 to all channels (corresponding to 10V/20mA full range output);
Reference channel selection: Measure the current output values of all channels, calculate the average value, and select the channel with the output value closest to the average value as the reference;
Current calibration: Use a non-metallic screwdriver to adjust the calibration potentiometer so that the reference channel current output is 20.000mA (25 ℃);
Accuracy verification:
Voltage output: All channels must be 10.000V ± 50mV;
Current output: All channels must be 20.00mA ± 0.1mA;
If the deviation exceeds the tolerance, repeat steps 6-8;
Restore wiring: After calibration is completed, power off, remove the calibration load, and restore on-site wiring and module configuration.
5.4 Daily maintenance and troubleshooting
5.4.1 Key points of daily maintenance
Cleaning module: Clean the module panel and terminal block with a dry soft cloth every 3 months to avoid dust accumulation;
Wiring inspection: Check the tightening of terminal block screws every 6 months to prevent loose wiring caused by vibration;
Power inspection: Regularly check the user power supply (20-28VDC) of the output module to ensure that the ripple is ≤ ± 0.4VDC;
Fuse maintenance: When the output module fuse (0.5A fast melting, model PPX: 2587679-8009) burns out, it is necessary to first investigate the cause of overvoltage/overcurrent before replacing the fuse.
5.4.2 Common troubleshooting
Possible causes of malfunction, troubleshooting steps, and solutions
Module Good LED not lit (input module) Base power failure, module self diagnosis failure 1. Measure whether the base power supply voltage is normal; 2. Check if the module is correctly inserted into the slot; 3. Disconnect all wiring and reinstall. 1. Repair the power supply of the base; 2. Re plug and unplug the module; 3. Module self diagnosis failure requires return for repair
Module Good LED not lit (output module) Base power failure, user power failure, blown fuse, self diagnosis failure. 1. Measure the base and user power supply; 2. Check the status of the fuse; 3. Check if the module wiring is short circuited. 1. Repair the power supply; 2. Replace the fuse; 3. After eliminating the short circuit, power on again; 4. Self diagnosis failure requires return for repair
Input module reading error, wiring error, signal noise, calibration deviation, signal source out of range. 1. Check the wiring by referring to the pin diagram; 2. Check if the grounding of the shielding layer is correct; 3. Verify whether the output of the signal source is within ± 5V/± 10V or 0-20mA; 4. Recalibrate module 1. Correct wiring; 2. Optimize shielding and wiring; 3. Adjust the signal source to the effective range; 4. Complete calibration
The output module outputs abnormal loads beyond the range, digital input errors, calibration deviations, and unstable user power supply. 1. Measure whether the load resistance/capacitance meets the requirements; 2. Check if the digital output of the controller is correct; 3. Recalibrate the module; 4. Measure the user's power ripple. 1. Replace the load that meets the requirements; 2. Repair the digital output of the controller; 3. Complete calibration; 4. Replace the stable power supply
PLC reports non fatal module configuration error, module and controller communication failure. 1. Check the I/O configuration parameters (WX/WAY quantity); 2. Check if the module is in good contact with the base; 3. Restart the controller. 1. Correct the configuration parameters; 2. Re plug and unplug the module; 3. If the error persists after restarting, it needs to be returned for repair
Environmental and Safety Parameters (Appendix B)
6.1 Environmental adaptation parameters
Parameter indicators
Working temperature 0-60 ℃ (32-140 ℉)
Storage temperature -40-70 ℃ (-40-158 ℉)
Relative humidity 5% -95% (non condensing)
Vibration resistance sinusoidal vibration: 10-57Hz, 0.15mm peak to peak value; Random vibration: 57-150Hz, 1.0g