Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Complete Guide to SV-iG5A Inverter

F: | Au:FAN | DA:2026-04-28 | 825 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:

SV-iG5A Inverter Engineering Practice: A Complete Manual from Fault Codes to System Optimization

In industrial automation sites, frequency converters are the core equipment driving motors, and LS Power's SV-iG5A series, with its compact design, flexible I/O configuration, and dual-mode capability supporting V/F and Sensorless vector control, has a large inventory of devices in small and medium power applications. As equipment ages, engineers often face issues such as downtime, parameter loss, communication abnormalities, and how to choose replacement parts. This article provides an immediately usable technical guide from the perspective of frontline maintenance, focusing on hardware installation, parameter debugging, typical fault handling, and preventive replacement strategies for SV-iG5A.

Safety and installation: an uncompromising foundation

Before starting any operation, it must be clear that the internal DC bus capacitor of SV-iG5A can still maintain dangerous voltage after power failure. The manual clearly requires that "after cutting off the input power, wait for at least 10 minutes until the LED keyboard display goes out" before conducting maintenance. In addition, due to the presence of ESD sensitive components inside, electrostatic protection measures must be taken before contacting the PCB.

Installation environment requirements:

Environmental temperature: -10 ℃~50 ℃, no freezing; Humidity below 90%, no condensation.

Altitude not exceeding 1000 meters, vibration ≤ 5.9m/s ² (0.6G).

It must be installed vertically (top up) to ensure smooth ventilation of the heat dissipation duct.

When multiple units are installed side by side, sufficient clearance should be reserved (see the dimension diagram in the manual). If a fan is required for forced ventilation in the enclosed cabinet.

Grounding key:

The grounding impedance of 200V level models should be lower than 100 Ω, and 400V level models should be lower than 10 Ω.

Special grounding terminals must be used and cannot be replaced with casing screws. The grounding wire diameter varies from 3.5mm ² to 22mm ² depending on the capacity.

Prohibited items for main circuit wiring:

It is strictly prohibited to connect the input power to the U, V, and W output terminals, otherwise the internal IGBT will be instantly damaged.

It is prohibited to install power factor compensation capacitors, surge suppressors, or RFI filters on the output side.

When the total length of the motor cable exceeds 50m, the carrier frequency (H39) should be reduced: ≤ 5kHz for 50-100m and ≤ 2.5kHz for over 100m to avoid overcurrent misoperation caused by distributed capacitance in the line.

These basic rules are the prerequisite for the long-term stable operation of the equipment, and any negligence may lead to IGBT explosion or control board failure.


Control terminal wiring and signal type selection

The control terminal block of SV-iG5A provides 8 multifunctional inputs (P1~P8), analog inputs (V1, I, VR), analog outputs (AM), and relay outputs (3A/3B/3C). The first challenge that engineers often encounter is the choice of PNP/NPN.

NPN/PNP switching:

When using an internal 24V power supply, short-circuit the CM terminal to the 24 terminal to form NPN mode (low level effective).

When using an external 24V power supply, the positive terminal of the external power supply should be connected to terminal 24, the negative terminal should be connected to CM, and the common terminal of the multifunctional input terminal should be connected to the negative terminal of the external power supply, which is PNP mode (high level effective).

This setting is clearly illustrated on the inside of the terminal cover plate, and incorrect configuration can cause the input signal to be unrecognizable.

Analog input configuration:

The V1 terminal can accept 0~10V or -10~10V signals, and the mode can be selected through parameter Frq (A104).

The I terminal receives a 0-20mA signal and has an internal sampling resistor of 250 Ω.

The VR terminal provides a 12V/100mA power supply and can be connected to an external 1-5k Ω potentiometer for frequency setting.

For the detection of 4-20mA signal loss, it is necessary to set I16 (A410) to 1 or 2 and select the fault response behavior in I62 (continue running, free stop, slow down stop, or run at a preset frequency).

Typical definition of multifunctional terminal:

Factory default P1=Fx (forward rotation), P2=Rx (reverse rotation), P3=Jog, P4~P6 for multi-stage low/medium/high speed, P7/P8 for multi-stage acceleration and deceleration selection. In practical applications, it is often modified to:

External fault input (18 or 19): Emergency stop is achieved through normally open/normally closed contacts.

Speed up/down (UP/DOWN): achieve stepless adjustment, combined with F63 to save power-off memory.

Second motor selection (12): Switch between different motor parameter groups (H81~H90).

The function of each terminal can be independently set through I17~I24, and they can be different from each other.

Core parameter analysis and debugging pitfalls

The parameters of SV-iG5A are divided into four groups: DRV (driver group), FU1 (function 1 group), FU2 (function 2 group), and I/O group. Keyboard operation supports inter group jump and direct parameter number jump, proficient mastery can greatly shorten debugging time.

Frequency setting and operation instruction source (drv and Frq):

Drv (A103) determines the source of the running instruction: 0=keyboard RUN/STOP key; 1=Terminal Fx/Rx; 2=Terminal Fx/Rx and Fx is "enabled for operation", Rx is reverse selection; 3=RS485 communication.

Frq (A104) determines the frequency source: 0=keyboard numeric setting; 1=Keyboard potentiometer; 2=V1(0~10V); 3=V1(-10~10V); 4=I(0~20mA); 5=V1+I superposition; 6=V1(0~10)+I; 7=RS485; 8=numerical quantity UP/DOWN; 9=Communication options.

Common error: Setting drv=1 (terminal control) but not short circuiting Fx-CM, motor does not turn; Or Frq=0 but no frequency input on the keyboard.

Acceleration and deceleration time and multi-stage settings:

ACC (A101) and DEC (A102) are used for basic acceleration and deceleration, with a unit of 0.1 seconds and a range of 0-6000 seconds.

When different acceleration and deceleration slopes are required, I34~I47 can be set as multi-stage acceleration and deceleration times of 1-7, and selected through the "multi-stage acceleration and deceleration low/medium/high" combination of the multifunctional input terminal.

Note: H70 determines the reference frequency for acceleration and deceleration time -0 represents the maximum frequency (F21) as the reference, 1 represents the frequency command change as the reference, and the latter is more accurate in dynamic adjustment.

V/F mode and torque boost:

F30 can choose linear, square, or user-defined V/F curves. For fan and pump loads, a square curve can save energy. For heavy load startup, it is necessary to manually set F28 (forward torque boost, 0-15%) and F29 (reverse boost). If F27=1 (automatic torque boost), it will automatically adjust according to the load, but the response may lag.

Sensorless vector control (H40=3):

After activation, the motor parameters need to be self-tuning (H41=1), and the system will automatically measure the stator resistance (H42) and leakage inductance (H44). The maximum frequency of this mode can be extended to 300Hz, but attention should be paid to the mechanical strength of the motor. Simultaneously, it is necessary to set the speed loop P/I gain (H45/H46) and torque limit (H47). Practice has shown that the load-carrying capacity of this mode is better than V/F at low frequencies (<5Hz).

PID control (H49=1):

Used for constant pressure water supply, tension control, etc. The feedback source is selected through H50 (I or V1), and H58 selects the unit (Hz or%). The P/I/D parameters H51~H53 need to be debugged according to different situations: generally, H51 is set to a small value (such as 100) and gradually increased until the system no longer oscillates; H52 points usually take 1-2 seconds; Differential H53 is used in fast response scenarios and is prone to introducing noise. In addition, H54=1 is a process PID, which can directly output frequency based on feedback and given difference. The sleep/wake function (H61~H63) can prevent the water pump from running idle at low frequencies.


Selection of Braking Resistors and Dynamic Braking

The SV-iG5A internal braking unit is already built-in in models below 22kW, but the braking resistor needs to be externally connected. The manual provides resistance values and power selection tables for 100% and 150% braking torque (see section 7.5 of the original text). For example:

200V 0.75kW: 200 Ω/100W for 100% braking, 150 Ω/150W for 150% braking.

200V 22kW: 8 Ω/2800W for 100% braking, 6 Ω/3600W for 150% braking.

The ED% of the resistor is generally 5%, and the continuous braking time does not exceed 15 seconds. During installation, the resistor must be connected to terminals B1 and B2. It is absolutely forbidden to short-circuit B1-B2, otherwise it will damage the internal brake pipe.

H75 and H76 are used to limit the utilization rate of the braking resistor: when H75=1, the proportion of braking action time to the entire operating cycle is limited by H76 to prevent the resistor from overheating. In practical applications, if frequent deceleration occurs, it is recommended to increase the resistance power level or use an external braking unit.

In depth investigation of typical fault codes

When the keyboard displays a fault code, the vast majority of cases are not due to hardware damage to the inverter, but rather external parameter or wiring issues. The following are the high-frequency faults that occur on site and the corresponding handling paths.

OC/OC2 (overcurrent)

Trigger condition: The output current exceeds the rated value by about 200%.

Common reasons:

The acceleration and deceleration time is too short, and the motor inertia is large. Solution: Add ACC/DEC.

The insulation damage of the motor cable causes a short circuit between phases or relative to ground. Solution: Shake test insulation and replace cable.

The mechanical brake is not opened or the load is stuck. Solution: Check the brake control circuit.

The output side contactor shakes during operation. Solution: Check the auxiliary contacts.

Attention: OC2 specifically refers to IGBT through short circuit, which is usually caused by module damage or drive circuit failure, and the frequency converter needs to be replaced.

OV (overvoltage)

Trigger condition: The DC bus voltage exceeds 400V (200V level) or 800V (400V level).

Main reason: The deceleration time is too short, and the regenerative energy of the motor is injected back. Solution: Extend deceleration time, install braking resistors or braking units. In addition, transient surges in the power supply can also cause OV, so check if there is a capacitor bank connected to the input side.

LV (low voltage)

Trigger condition: The bus voltage is below 180V (200V level) or 360V (400V level).

Reason: Input phase loss, insufficient power capacity (if starting a large motor directly), loose wiring terminals. If it occurs instantaneously during operation, the "instantaneous power failure restart" function of H22 can be enabled, setting 0-10 automatic restart attempts (H26) and restart waiting time (H27).

OH/IOL/OLT (overheating/overload)

OH: The temperature of the heat sink exceeds 85 ℃. Check if the cooling fan is stuck, if the air duct is blocked, and if the ambient temperature is too high. When the fan malfunctions, the keyboard displays "FAN", and H78 can choose to continue running or stop for protection.

IOL: The frequency converter is overloaded and usually operates at 150% per minute. Need to increase the capacity of the frequency converter or reduce the load.

OLT: Motor overload detected by internal electronic thermal overload relay. Need to check the settings of F51 (one minute overload multiple), F52 (continuous current), and F57/F58. If the motor is a constant torque load but operates at low speed for a long time, an independent fan needs to be added.

ETH (motor thermal overload)

Attention: This protection is based on the output current calculation of the frequency converter. It will fail when driving multiple motors or when the number of poles is greater than 4. In this case, an external thermal relay needs to be installed on each motor.

GF (Ground Fault)

The frequency converter has detected that the output leakage current to the ground exceeds the internal threshold. The common reasons are that the motor winding is damp or the cable insulation is reduced. You can first disconnect the motor wire and run the frequency converter without load. If GF still reports, it may be a fault with the Hall sensor or motherboard.

PO (Output Phase Loss)

Triggered when any output phase current is missing. Check if the motor wire is loose and if the contactor is not engaged. For low-power motors (0.4kW), false alarms may occur at low carrier frequencies. It is recommended to lower the H39 or increase the I54/I55 detection threshold appropriately (although the manual does not disclose the adjustment method, it is recommended to replace spare parts for testing).

Communication error (Err)

When using RS485 communication, check whether the station numbers, baud rates, and parity bits of I60~I65 are consistent with the main station. Setting I62 to 0 can maintain the last frequency in case of communication loss, while setting it to 2 will slow down and stop the vehicle.


Preventive maintenance and component replacement cycle

Although SV-iG5A is durable, its internal electrolytic capacitors and cooling fans will age over time and temperature. Based on manual maintenance suggestions:

Typical failure phenomena of component replacement cycle

Cooling fan noise increases over the past 3 years, reports FAN faults, and frequently generates OH

The 4-year capacity decrease of the DC bus capacitor in the main circuit resulted in LV tripping and large voltage ripple

Abnormal parameter storage and chaotic keyboard display of electrolytic capacitors on the control board after 4 years

The relay's indefinite contacts are stuck or unable to engage

Attention to replacement operation: Be sure to perform it after power off and discharging. To replace the fan, open the bottom cover (press both sides and pull out), and refer to the original label for the model. For naturally cooled models (such as SV004iG5A-2, 0.4kW 3-phase) without fans, it is necessary to ensure good natural convection inside the cabinet.

Parameter backup: Before replacing the control board or upgrading software, it is necessary to read all parameters through RS485 (using the DriveView software provided by LS) or manually record key values. The new control board needs to set the same parameter group and perform H93=1 initialization, and then write them one by one.


Upgrade and Alternative Options

For the discontinued SV-iG5A, if the main control board is damaged and cannot be repaired, the following can be considered:

Directly replace with models of the same series that can still be purchased (such as the iG5A improved version or the next generation iS7 series). However, it is important to note the differences in base size and wiring diagram.

Using communication option modules (DeviceNet or Ethernet, requiring the purchase of a communication type host with the suffix "FB"), connect the frequency converter to the upper network to achieve remote monitoring and batch parameter download.

The remote keyboard (model 64100022, etc.) can lead the operation panel to the cabinet door for easy debugging. When using for the first time, execute H91 (read parameters to remote keyboard memory), otherwise the keyboard will not display; Write and execute H92.

EMC filter installation: To meet CE or C-Tick radiation standards, LS original FF or FE series power filters must be installed. Installation key: The filter is tightly attached to the input side, the output cable and input cable are routed separately, and a ferrite core is installed on the output side of the frequency converter (the three-phase wire passes through twice). The leakage current of the filter is relatively large. If a leakage protector is used at the front end, a sensitivity of 100mA or above should be selected, otherwise it will jump when powered on.

  • National Instruments NI 6587 LVDS Digital I/O Module
  • National Instruments PCI-6225 Data Acquisition Card
  • National Instruments NI-9262 Analog Output Module
  • National Instruments NI 9235 Quarter Bridge Input Module
  • National Instruments PXIe-8301 Remote Control Module
  • National Instruments PXI-4071 FlexDMM Module
  • NI-9234 Sound and Vibration Input 779680-01
  • NI 9229 Isolated Analog Input Module
  • NI cDAQ-9178 USB CompactDAQ Chassis
  • National Instruments NI 9220 143613B-06L Analog Input Module
  • NI 9229 Analog Input Module
  • NI 9246 Analog Input Module
  • NI PXIe-1071 PXI Express Chassis
  • National Instruments 9225 780159-01 Analog Input Module
  • NI cDAQ-9171 USB CompactDAQ Chassis
  • NI PXIe-8840 Embedded PXI Controller
  • Bonfiglioli A202 UH35 FIA 39.6 Right Angle Reducer
  • Bonfiglioli BN 90 LA 4 Gearmotor 1.5kW i=14.1
  • Bonfiglioli BN71A4 Motor with C313PP71 Gearbox
  • Bonfiglioli MP 130 1 4 STD 114A CD Planetary Gear Head
  • Bonfiglioli LC155 1 10 STD Gearbox
  • Bonfiglioli Vectron ACU401-13 FA Inverter
  • Bonfiglioli AEC500-31A Solar Inverter
  • Bonfiglioli BN63B6 Geared Motor VF44P
  • Bonfiglioli Vectron ACT410-23 Inverter
  • Bonfiglioli FR FRIZ 11/90 Clutch
  • Bonfiglioli A/11.90 B3 Clutch Brake
  • Bonfiglioli 50.180.3000 Servo Motor
  • Bonfiglioli NFF 14 112 EE Clutch
  • Bonfiglioli BMD 65 Permanent Magnet Motor
  • Bonfiglioli MP 080 2 20 STD 73A1 CD Planetary Gearbox
  • Bonfiglioli VF/VF30/63 P1 1520 Gearbox
  • Bonfiglioli M3SA4 FD with X F202 H35 10.0 Gearbox
  • Bonfiglioli ACU401-19A Frequency Inverter 5.5kW
  • Lafert B6306P-02276 Servo Motor with Bonfiglioli A102
  • Bonfiglioli ACU401-09FA Frequency Inverter 1.1kW
  • ProMinent Sigma S1CBH12035 with Bonfiglioli BN56B4
  • Bonfiglioli TR 080 2 20 STD Planetary Gearbox
  • Bonfiglioli ACT400-040A Frequency Inverter 15kW
  • Bonfiglioli BE 132 MA 4 Electric Motor 7.5kW
  • Bonfiglioli W86 U30 P100 Gearbox
  • Bonfiglioli MP105 2 25 Planetary Gearbox
  • Bonfiglioli BE160L4 Motor 15 kW
  • BONFIGLIOLI TMP-105 2 25 15 19 40 70 90 Planetary Gearbox
  • Bonfiglioli Vectron ACU401-18 FA Inverter
  • BONFIGLIOLI BE80B4 Motor with A302 UH35 76.5 P80 VA Gearbox
  • Bonfiglioli Vectron VCB400-180 Inverter
  • Bonfiglioli P63B14B3 Motorization Encoder
  • Bonfiglioli Vectron ACT201-13FA Inverter
  • Bonfiglioli F202 H30 P90 Gearbox
  • Bonfiglioli BN71A4 C313 P P71 Gearmotor
  • Bonfiglioli ACT201-11FA Frequency Inverter
  • Bonfiglioli ACU410-21 3 FA Inverter 7.5kW
  • Bonfiglioli RA0 60/00 Gear Reducer i=182
  • Alpha VDS 063-MF1-10-141-BE Planetary Gear 20018280
  • Stöber FDR 71B/10 Gearmotor 0.37kW
  • Stöber DW0-2000-037-4 Gearbox 0.25kW
  • Bonfiglioli M3SA4 FD R with X F252 H35 16.6 Gearbox
  • Bonfiglioli BN90LA4 Adjustable Gear Motor 1.5kW
  • Alpha LP 090-MO1-5-111-000 Planetary Gearbox
  • Bonfiglioli 335 M3 C Planetary Gear Motor
  • Bonfiglioli TR060 2 18 STD 50C CD 14 S1 OR SB KE Gearbox
  • Bonfiglioli MP1GD3036L001 Gearbox
  • Bonfiglioli BN90LA4 Gear Motor 1.5 kW
  • Bonfiglioli A302 UH35 P90 Gearbox
  • Bonfiglioli ACU410-31A5 Inverter
  • BONFIGLIOLI BMD 118 14 4500 400 165 SS TC1 RES2 P1N S1N CUS JB00013358
  • Bonfiglioli A302 UH40 P90 Reducer
  • Bonfiglioli ACT201-05FA Inverter
  • Mannesmann Demag 4APB71-4-G08-PR Gear Motor with Bonfiglioli MVF63/F
  • BONFIGLIOLI W63 U P80 B5 Gearbox 2G20012741
  • Bonfiglioli BE80B4 Motor with A202 Gearbox
  • BONFIGLIOLI VECTRON KEYPAD 179675500 KP500
  • Bonfiglioli RA0 60/00 Gear Reducer i182
  • Bonfiglioli C212 F P90 VV Gearbox i=9.6
  • Bonfiglioli MP105 Servomotor Gear
  • Mannesmann Demag 4APB71-4-G08-PR Getriebemotor with Bonfiglioli MVF 63/f
  • Bonfiglioli Vectron ACT401-12 FA Inverter
  • Bonfiglioli BN 80A4 COD.830820106 Motor 0.55 kW IMB5
  • Bonfiglioli TR060 Gearbox
  • Silectron Bonfiglioli FT1000-0.75S RFI Filter
  • Trasmital Bonfiglioli 710C3B50F177G34W1A52VAG Drive
  • Bonfiglioli MAC800-D1 Motorreductor
  • Bonfiglioli VF 63 V HS Worm Gearbox
  • Bonfiglioli BN90LA4 Adjustable Gear Motor 1.5kW
  • Bonfiglioli ACT 400-018 FA Frequency Inverter
  • Bonfiglioli RAO50DNP90B5-I220 Gear Unit i=200
  • Bonfiglioli ACT 401-13FA Frequency Inverter SIACT513010001
  • Bonfiglioli ACU210-18 3 FA Active Inverter 4kW
  • Trasmital Bonfiglioli 709C3B50F177G34W1A52VAG Drive
  • Bonfiglioli BN27C4 Gear Motor 0.09 kW
  • Bonfiglioli BN71A4 Electric Motor
  • Bonfiglioli Vectron VCB400-370 Inverter
  • Bonfiglioli Vectron ACU401-18FA Inverter
  • Bonfiglioli LC120 2 40 STD Gearbox
  • Bonfiglioli BN63B6 Gear Motor 0.12 kW
  • Bonfiglioli T56BN/4 Asynchronous Motor
  • AEB Atlant D712-4B5 Motor with Bonfiglioli MVF 49F1 Gearbox
  • Bonfiglioli VF110 A P100B14 Worm Gear
  • Trasmital Bonfiglioli Raupengetriebe i 1:122 2174688 2T705C3122002 Travel Drive
  • Bonfiglioli ACT 401-21A Frequency Inverter
  • Bonfiglioli VF44 U14 Worm Reducer B03181367918
  • Bonfiglioli VF49 L1 P1 P63B5 Worm Gear i=45
  • Bonfiglioli S2U230S-03F Inverter 0.4kW
  • Ferag 5690512 Uiker TR90L4 Motorreductor with Bonfiglioli C212 F9.6
  • Bonfiglioli LC120250STD80A1CD14KE Gearbox
  • Bonfiglioli W63U38 P80 B14 V5 Gearbox
  • Bonfiglioli VF49A-28-P80-B14 Worm Gearbox
  • Bonfiglioli BN71B4 W63U64P75 Gearmotor
  • Alpha VDS 063-MF1-10-141-BE Planetary Gearbox
  • Bonfiglioli BN71B4 MVF49 F1 Gearmotor i=36
  • Bonfiglioli BN 63 B6 Gear Motor 0.12kW
  • Bonfiglioli SPL400 17F SynPlus Drive 3.7kW
  • Bonfiglioli ACU 401-25A Frequency Inverter
  • Esa 3M2209B5 M71Q Motor with Bonfiglioli MVF49 Gearbox
  • Ferag 5690512 UIKER TR90L4 Gear Motor with Bonfiglioli C212
  • Bonfiglioli A302 UH35 P90 Bevel Gearbox
  • Bonfiglioli GVX1000-1.5-S Inverter Drive 1.5kW
  • Bonfiglioli W63 U 15.0 P80 B14 B Worm Drive
  • Bonfiglioli KP500 Control Panel
  • Bonfiglioli C302PP71 Speed Reducer
  • Bonfiglioli BN71B4 Motor con MVF49 Reductor
  • Bonfiglioli BN71B4 Motor with MVF49 Gearbox i36
  • Bonfiglioli SYN10S 22001AF Inverter 0.2 kW
  • Motor Power Esa 3M2209B5/M71Q with Tachometer and Bonfiglioli MVF49 Gearbox
  • Bonfiglioli SYN10 S 220 01 AF Inverter
  • MEZ UD 1104 2.5 kW BONFIGLIOLI Trasmittal 300L19 Gear Motor 300L19.00HZP90AW0A
  • Bonfiglioli Vectron ACT W 401-39 D Inverter