Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

TOSHIBA VF-AS3 inverter RS485 communication function

F: | Au:FAN | DA:2025-11-17 | 1030 Br: | 🔊 点击朗读正文 ❚❚ | Share:

TOSHIBA VF-AS3 inverter RS485 communication function

Basic Information and Security Standards for Documents

1. Scope of application and core purpose

Applicable equipment: Toshiba VF-AS3 series full specification frequency converter, covering 200V level (0.4-55kW) and 400V level (0.4-280kW, including IP55 protection type), supporting 2 independent RS485 communication interfaces (Connector1/Connector2).

Core purpose: To achieve three major functions through RS485 bus - remote control (run/stop, frequency setting, torque adjustment), parameter reading and writing (internal parameter configuration of frequency converter), and status monitoring (output frequency/current/voltage, fault code, terminal status), supporting master-slave synchronous control between frequency converters without relying on PLC or upper computer.

2. Safety and usage restrictions

Mandatory safety requirements:

It is prohibited to plug and unplug RS485 communication cables with power on, and it is forbidden to connect Ethernet signals to the RS485 interface, otherwise it may cause the communication module to burn out or the frequency converter to malfunction.

Communication timeout parameters (F803/F823) must be set to avoid device loss of control during communication interruption. After timeout, "continue operation", "trip immediately", or "trip after deceleration" can be set (default to continue operation).

The limit for writing EEPROM is 100000 times (for parameter storage media), and there is no limit for writing RAM. It is recommended to use the P command to write frequently modified parameters (such as frequency commands) to RAM, and avoid writing frequently to EEPROM for parameters that do not need to be stored.

Usage restrictions:

The length of communication cables should match the baud rate (recommended ≤ 100m at 19200bps and ≤ 50m at 38400bps), and repeaters should be added for long distances.

The same RS485 bus can connect up to 32 devices, and the frequency converter number (F802) must be unique (0-247) and must not be duplicated.

image.png

Hardware wiring and transmission specifications

1. Definition of communication interface pins

VF-AS3 is equipped with two RS485 interfaces (Connector1/Connector2), both of which are RJ45 interfaces. The pin functions are as follows (key pins are bolded):

(1) Connector1 (default 2-wire system, non switchable)

Pin number, signal name, function description, wiring requirements

1/2/6- Reserved pins must not be connected to any cables, otherwise communication signals may be short circuited

4 RXA+/TXA+non-polar transmission and reception data positive terminal is connected to bus A line (usually red), and all devices are interconnected through this pin

5 RXB -/TXB - Non polarized transmission and reception data negative terminal connected to bus B line (usually blue), this pin is interconnected for all devices

7 Power pins are prohibited from connection to avoid power conflicts and burning interfaces

All devices with SG signal ground are interconnected with SG pins, and ultimately grounded at a single point (ground resistance ≤ 4 Ω)

(2) Connector2 (supports 2-wire/4-wire system, [F829] parameter switching)

Pin number 2-wire system function ([F829]=0) 4-wire system function ([F829]=1) wiring requirements

1/2- Reserved pins suspended, wiring prohibited

3- TXA+(transmitting data positive end) is only used by the 4-wire master station and connected to the RXA slave station+

RXA+/TXA+(transmit/receive positive terminal) RXA+(receive data positive terminal) 2-wire system is the same as Connector1; 4-wire system connected to the main station TXA+

5 RXB -/TXB - (transmit/receive negative terminal) RXB - (receive data negative terminal) 2-wire system is the same as Connector1; 4-wire system connected to the main station TXB-

6-TXB - (transmitting data negative terminal) is only used by the 4-wire master station and connected to the RXB slave station-

7 Power pins are prohibited from connection

8 SG signal ground interconnected with all equipment SG, single point grounding

2. Wiring specifications and hardware configuration

(1) Cable requirements

Shielded twisted pair cables must be used, with a conductor cross-sectional area of ≥ 0.22mm ² (AWG24) and a characteristic impedance of 100-120 Ω (matching RS485 bus impedance). The shielding layer needs to be grounded at both ends (if cross device grounding is required, equipotential bonding wires should be used to avoid ground current).

The distance between communication cables and the main circuit cables of the frequency converter (3-phase power supply and motor wires) should be ≥ 20cm. Parallel wiring or sharing of the same cable tray is prohibited to reduce electromagnetic interference (EMI).

(2) Required resistor configuration (cannot be omitted)

The stable operation of RS485 bus requires two types of resistors, and all nodes must be configured with:

Terminal resistance: 120 Ω/1/2W, only connected between the A+/B - pins of devices at both ends of the bus (such as the leftmost and rightmost frequency converters), to suppress signal reflection and avoid data transmission distortion.

Up and down resistors: 510 Ω/1/2W, each device's A+pin is connected to a 510 Ω resistor to+5V (or the positive terminal of the power supply), and the B - pin is connected to a 510 Ω resistor to GND. The purpose is to enhance the bus driving capability and avoid communication packet loss when weak signals occur.

(3) 2-wire and 4-wire wiring examples

2-wire system (default, recommended): A+(4-pin) interconnection, B - (5-pin) interconnection, SG (8-pin) interconnection for all devices, with 120 Ω terminal resistors connected at both ends of the bus and pull-down resistors connected at each node.

4-wire system (requires [F829]=1): The TXA+(3-pin)/TXB - (6-pin) of the master station is connected to the RXA+(4-pin)/RXB - (5-pin) of all slave stations, and the slave stations have no transmit pin (no response). The rest is the same as the 2-wire system, suitable for master-slave unidirectional communication and high reliability scenarios.

3. Transmission specification parameters

Transmission parameter support options default values note

Half duplex transmission method - can only receive or send data at the same time to avoid conflicts

Synchronization mode start and end synchronization - identify the beginning and end of frames by "3.5 byte blank time" (9600bps ≈ 4ms, 19200bps ≈ 2ms, 38400bps ≈ 1ms)

The baud rate is 9600bps/19200bps/38400bps. After modifying 19200bps, it needs to be powered off and reset to take effect. All bus devices must be consistent

No parity check/even parity check/odd parity check. After modifying the parity check, it needs to be powered off and reset to take effect. It is recommended to use even parity check (with strong anti-interference ability)

8-bit data bit (ASCII: JIS X0201; Binary/MODBUS: fixed 8-bit) - no options, non modifiable

Stop bit reception: 1 bit; Sending: 2 bits - compatible with upper computer 1/1.5/2 bit stop bit settings, no adaptation required

Error detection Toshiba protocol: checksum (optional); MODBUS-RTU: CRC16 (required) - When verifying an error, the frequency converter does not respond, and the upper computer needs to resend it


Detailed explanation of communication protocol (dual protocol support)

VF-AS3 supports two communication protocols, which can be switched through parameters [F807] (Connector1)/[F827] (Connector2). The default is the "Toshiba Inverter Protocol", and two protocols (different interfaces) can be enabled simultaneously.

1. Toshiba inverter protocol (native protocol, with the most comprehensive functions)

Supports ASCII, Binary, and block communication modes, accessing inverter parameters through a "communication number" (4-digit hexadecimal). The command set covers read, write, and inter inverter communication, making it suitable for Toshiba device networking.

(1) ASCII mode (suitable for PC/PLC, with strong readability)

Frame format (computer → frequency converter): (INV-NO CMD communication number DATA&SUM) CR

Initial code: "(" (28H), final code: ")" (29H)+CR (0DH), cannot be omitted.

INV-NO: Inverter number (2-digit ASCII, 00-99, "* *" represents broadcast).

CMD: Command code (R=Read, W=Write RAM+EEPROM, P=Write RAM, G=Read (2-wire system specific)).

Communication number: 4-digit hexadecimal (e.g. FD00=output frequency, FA01=frequency command).

SUM: checksum (2-digit ASCII, optional), calculated as "the last two digits of the sum of all ASCII codes between the header and&".

Example: Set the frequency to 60Hz (communication number FA01, 60Hz=1770H)

Command: (00PFA011770) CR (00=inverter number, P=write to RAM, 1770=hexadecimal corresponding to 60Hz).

Response: (00PFA011770) CR (The frequency converter returns the same command, confirming successful writing).

(2) Binary mode (suitable for microcontrollers/embedded systems, high transmission efficiency)

Frame format (computer → frequency converter):/INV-NO CMD communication number DATA SUM

Header code: "/" (2FH), no tail code, SUM (1 byte) is required.

INV-NO: Inverter number (1-byte hexadecimal, 00H-3FH, FFH=broadcast).

CMD: Command code (52H=R, 57H=W, 50H=P, 53H=S (between frequency converters)).

Communication number: 2-byte hexadecimal (high-order, such as FD00=output frequency).

SUM: checksum (1 byte), calculated as the last 8 bits of the sum of all bytes from the header to DATA.

Example: Read output frequency (communication number FD00)

Command: 2F 52 FD 00 82 (2F=/, 52=R, FD00=communication number, 82=SUM).

Response: 2F 52 FD 00 17 70 05 (1770H=6000 → 60.00Hz, 05=response SUM).

(3) Block communication mode (efficient batch read/write)

Core advantage: A single communication can simultaneously write 2 parameters and read 5 parameters, reducing the number of communication times and suitable for batch configuration or centralized monitoring scenarios.

Parameter preset: You need to first set the "block write parameters" (such as FA00=run command, FA01=frequency command) through [F870]/[F871], and set the "block read parameters" (such as FD00=output frequency, FD03=output current) through [F875] - [F879].

Frame format: Computer sends X command (58H), frequency converter sends Y command (59H), example:

Computer command: 2F 58 02 05 C4 00 17 70 D9 (02=write 2 parameters, 05=read 5 parameters, C400=forward command, 1770=60Hz).

Inverter response: 2F 59 05 00 64 00 17 70 1A 8A 24 FD 00 3D (returns 5 read parameter results, 64=100 → 60Hz, 1A8A=6794 → 67.94% current, etc.).

(4) Broadcast communication

Only supports write commands (W/P), does not support read commands, suitable for batch configuration of all devices.

ASCII mode: INV-NO is set to "* *" (such as (* * PFA011770) CR), only the device numbered 00 responds, and other devices do not respond when executing commands.

Binary mode: INV-NO is set to FFH, and only the device numbered 00 responds to avoid bus conflicts.

2. MODBUS-RTU protocol (compatible with third-party devices)

Only supports MODBUS-RTU subset (binary transmission), does not support ASCII mode, suitable for networking with third-party PLCs, touch screens, and other devices. The core instructions are as follows:

Instruction code (Hex) function description applicable scene frame format (computer → frequency converter)

03H Read Keep Register reads one or more parameters (indirect read ≤ 5, direct read ≤ 8) inverter number+03H+communication number (high-order)+read word count (high-order)+CRC16

Write a single hold register in 06H and write one parameter (such as frequency instruction, run command): frequency converter number+06H+communication number (high-order first)+write data (high-order first)+CRC16

10H write multiple hold registers, write 2 or more parameters (such as block write preset parameters), inverter number+10H+communication number (high-order)+write word count (high-order)+data byte count+write data+CRC16

Write and read multiple registers in 17H, simultaneously write parameters+read parameters (such as write frequency+read output current), inverter number+17H+read communication number+read word count+write communication number+write word count+data byte count+write data+CRC16

2BH reads model information, manufacturer, model, and version (such as "TOSHIBA" and "VFAS3-2037P"), inverter number+2BH+MEI type (0EH)+equipment code+object code+CRC16

(1) CRC16 Calculation Rule (Required)

The CRC16 of MODBUS-RTU is a 16 bit checksum, and the calculation steps are as follows:

Initialize the CRC register to FFFFH;

XOR the data byte by byte with the CRC register;

Shift each byte by 1 bit to the left. If the lowest bit is 1, XOR the CRC register with polynomial A001H;

Repeat step 3 8 times to process all bytes;

The final CRC value is stored at the end of the frame with "low bits first, high bits second".

Example: The CRC16 of the command "01 03 FD 00 00 01" is B5A6H, and the complete command is "01 03 FD 00 01 B5 A6".

(2) Example: Read output frequency (communication number FD00)

Inverter parameters: Number 1 (01H), baud rate 19200bps, even parity.

Computer command: 01 03 FD 00 00 01 B5 A6 (01=number, 03=read, FD00=communication number, 0001=read 1 parameter).

Inverter response: 01 03 02 17 70 B6 50 (02=number of data bytes, 1770H=6000 → 60.00Hz, B650=CRC16).

image.png

Core function: master-slave communication between frequency converters

Without the need for an upper computer, synchronous control of one master and multiple slaves can be achieved through the RS485 bus, which only supports Toshiba inverter protocol. The main station sends S command (53H), and the slave station does not respond when receiving commands, avoiding bus conflicts.

1. Master slave parameter configuration (key parameters)

Example Setting of Character Core Parameter Configuration Options (45Hz Output from the Station)

Master station [F806]/[F826] (master-slave mode) 3=frequency command, 4=output frequency, 5=torque command, 6=output torque [F826]=3 (frequency command)

Main station [F805]/[F825] (transmission waiting time) 0.00-2.00s (default 0.00s) 0.01s (to avoid the main station sending too fast)

Slave station [F806]/[F826] (master-slave mode) 0=0Hz in case of fault, 1=continue operation in case of fault, 2=emergency stop in case of fault [F826]=0 (fail safe)

From station [F823] (communication timeout) 0.1-100.0s (default 0.0s disabled) 1.0s (tripped when cable disconnected)

Slave [FMOd] (frequency command source) 21=Connector1, 22=Connector2 22 (same interface as the master station)

Slave [FH] (maximum frequency) 0.0-400.0Hz 90.0Hz (target maximum frequency)

2. Speed proportional control logic

The frequency of the slave station is calculated according to the proportion of the master station's instructions, and supports two modes: "no correction" and "two-point correction":

(1) No calibration mode (F810=0)

Calculation formula: Slave frequency (Hz)=(Master command value (%) x Slave maximum frequency (Hz))/10000

Main station command value: 1%=100 (e.g. 50%=5000), main station frequency command=(actual frequency of main station x 10000)/maximum frequency of main station.

Example: The maximum frequency of the main station is 60Hz, and the actual output is 30Hz → Main station command=(30 × 10000)/60=5000 (50%); The maximum frequency of the slave station is 90Hz → the slave station frequency=(5000 × 90)/10000=45Hz.

(2) Two point correction mode ([F810]=1, non-linear ratio)

Preset two parameters: [F811]=Point 1 command value (%), [F812]=Point 1 frequency (Hz); [F813]=Point 2 command value (%), [F814]=Point 2 frequency (Hz).

Calculation formula: Slave frequency=Point 1 frequency+(Main station instruction - Point 1 instruction) × (Point 2 frequency - Point 1 frequency)/(Point 2 instruction - Point 1 instruction)

Example: Point 1 (0% → 10Hz), point 2 (100% → 80Hz), master station instruction 50% → slave station frequency=10+(50-0) × (80-10)/(100-0)=45Hz.

3. Fault handling

Main station tripping: The main station sends the command s (73H), and the slave station sets the action according to [F806]/[F826] (0=0Hz, 1=continue operation, 2=emergency stop).

Communication interruption: The communication timeout (Err5) is triggered by the slave station, and the action (such as tripping) is set according to [F824]. The master station is not affected (the status needs to be fed back through the FL fault terminal of the slave station).


Detailed explanation of communication related parameters

The communication function of the frequency converter requires the configuration of a "communication parameter group" (F8xx series), and some parameters need to be reset after power failure to take effect. The key parameters are as follows:

Parameter number, parameter name, function description, adjustment range, default value, effective method

F800/F820 RS485 baud rate setting communication rate 0=9600bps, 1=19200bps, 2=38400bps 1 (19200bps) power off reset

F801/F821 RS485 checksum setting verification method 0=no verification, 1=even verification, 2=odd verification 1 (even verification) power off reset

F802 frequency converter number setting bus address 0-247 0 immediately

F803/F823 communication timeout setting timeout detection duration 0.0 (disabled), 0.1-100.0s 0.0s immediately

F804/F824 timeout operation timeout device action 1=continue running, 4=trip immediately, 6=trip immediately after deceleration, 1=trip immediately

F806/F826 master-slave communication mode setting master-slave role master station: 3-6; Slave: 0-20 (Slave) Power off reset

F807/F827 communication protocol selection Toshiba/MODBUS 0=Toshiba protocol, 1=MODBUS-RTU 0 power-off reset

F829 RS485 (2) wiring type 2-wire/4-wire switching 0=2-wire system, 1=4-wire system 0 immediately

F830 MODBUS continuous address direct read whether to skip empty parameter 0=skip, 1=do not skip 0 immediately

F870/F871 block write parameter 1/2 setting block communication write parameter 0=disabled, 1=FA00 (run command), etc. 0 power off reset

F875-F879 block read parameters 1-5 set block communication read parameters 0=disabled, 1=FD01 (status), etc. 0 power off reset


Troubleshooting and Appendix

1. Common faults and solutions

Troubleshooting steps for possible causes of fault phenomena

Communication unresponsive 1. Baud rate/checksum/protocol mismatch; 2. Wiring error (A+/B - reversed connection, SG not connected); 3. The frequency converter number does not match; 4. Uninnected terminal/pull-up/pull-down resistor 1. Unify all device parameters (such as 19200bps+even parity+Toshiba protocol); 2. Check the A+/B - wiring to ensure SG interconnection; 3. Confirm that INV-NO is consistent with [F802]; 4. Install 120 Ω terminal resistors (at both ends) and 510 Ω pull-up and pull-down resistors (at all nodes)

Err5 tripped (communication timeout) 1. Communication cable disconnected; 2. The main station did not send data; 3. The timeout period is too short; 4. The slave station did not receive the command from the master station. 1. Check the continuity of the cable; 2. Confirm that the main station sends commands normally (such as once per second); 3. Increase [F823] (e.g. set to 1.0s); 4. Verify the master and slave station interfaces (if both are using Connector2)

Write parameter error (N0000): 1. During operation, write prohibited parameters (such as maximum frequency [FH]); 2. Parameter locking ([F700]=2/4); 3. Password setting ([F738]) 1. Write prohibition parameter after shutdown; 2. Set [F700]=0 (unlock); 3. Clear the [F738] password

Data transmission error (garbled code) 1. Electromagnetic interference (parallel wiring with the main circuit); 2. Cable over distance; 3. The terminal resistor is not connected. 1. Adjust the cable routing and keep it away from the main circuit; 2. Shorten cables or add repeaters; 3. Connect a 120 Ω terminal resistor

2. Appendix Key Information

(1) Response time calculation

Total response time=data communication time+frequency converter processing time (maximum 10ms).

Data communication time=(bytes x bits)/baud rate, bits=1 (start bit)+8 (data bit)+1 (check bit)+2 (stop bit)=12 bits (default).

Example: 19200bps, 8-byte command → communication time=(8 × 12)/19200=5ms, total response time ≈ 15ms.

(2) Corresponding Table of Inverter Models and FB05 Parameters

[FB05] The parameter is used to identify the frequency converter model, and some common models correspond to the following relationships:

Inverter model, voltage level, power FB05 (decimal), FB05 (hexadecimal)

VFAS3-2037P 200V 3.7kW 9 9

VFAS3-4055PC 400V 5.5kW 42 2A

VFAS3-4220PCE 400V(IP55) 22kW 147 93

(3) ASCII code table

Provide JIS X0201 ASCII code mapping, such as "0"=30H, "A"=41H, "d"=64H, for ASCII mode command writing and data parsing.

image.png

  • Basler DECS-250-CGCM-LN2SA1C Digital Excitation Control System
  • Valmet Automation PLC Module A413171
  • Valmet Automation 542852-3A Rack-Mount Cross Connect Panel
  • Valmet Marine Damatic M851565 Main Keyboard
  • Valmet TIU 6 Printed Circuit Board A413110
  • Metso Valmet U4440253V1.1 RMI CPU 300
  • Metso Valmet A413016 Ver.12 NCU2
  • Valmet M851565 Damatic Keyboard
  • Valmet ATB16-4 16 Channel Relay Card
  • Valmet Metso A413331 SPU Power Supply
  • Valmet PUD 10B Automation Control Rack
  • Valmet MT917 ABMB DMU PCB I/O Module
  • Valmet M851565 Damatic Keyboard Mkb2
  • Valmet EDS-518A-MM-SC Ethernet Gateway
  • Valmet 542836-6A PCB Card
  • Valmet ATB16-4/2 Terminal Board 9144047
  • Valmet ATB16-4 Controller Board 0-50°C 4-20mA Analog Output
  • Valmet 542852-3A Slot Rack Chassis Module
  • Valmet A413026 Ver.M1 FBC Board
  • Valmet IQ Basis Weight SH Sending Assembly A418081
  • Valmet PMB 2R Monolithic Backplane 8-Slot PCB 542821-5A and -5B
  • Valmet ATB16-4 16-Channel Relay Card Controller Board 22195028
  • Valmet Diff-EL SL6NK227SF0 Pressure Transmitter 0-380 mBar
  • Valmet A413110 TIU6 Board Ver.M1
  • Neles Automation A413278 Control Module
  • Valmet BCUTB Terminal Module 10101006 11091002
  • Valmet Senso 160 Measuring Station Display 160.2
  • Valmet AIU 1A Analog Input Unit M851245
  • Valmet IQ Web Caliper Sensor A420734
  • Valmet M851040/M8510401 Memory Board
  • Valmet AN35S1MC02RA Valve
  • Valmet M851121 M2 Cross Connect Panel
  • Valmet AIU-8 Simulator Board 421522-1A
  • Metso BIU 82 D200533 Binary Input Unit
  • Valmet M851121 M2 Module Rack
  • Valmet A413383 PC Board Module
  • Valmet N0542 NO54 ABMB PCB - 545200-3A Board
  • Valmet Metso IOP304 Input Module 181503
  • Valmet PDP601 Distributed Processing Unit 181585
  • Valmet A413084 CPU Board - Processor Module for Automation Systems
  • Valmet AIU 16T Analog Input Module M8512081 M1
  • Valmet AIU 16 Analog Input Module 545100-3A and 545100-3B
  • Metso Valmet BIU4 A413146 Binary Input Unit
  • Valmet AIU-8 Simulateur Board 421522-1a Analog Simulator
  • Valmet BIU8A Binary Input Unit 542803-3B M851222 M1
  • Valmet IQ Web Color DH Photoelectric Sensor A418182 2.04
  • Valmet A413200 AIU-8 Simulator Board 191151 421522-1A
  • Valmet Automation SCU M851006 System Control Unit Module
  • Valmet 857565/851565 Damatic Keyboard IP40 5V Operator Interface
  • Valmet A413077 FBC2 Module Rev 06 Field Bus Controller
  • Valmet DMU 2 PCB Module 545142-3A DM Data Management Unit
  • Valmet AIU16T PCB Card M851208 Analog Input Module
  • Valmet A413181 PLU Board
  • Valmet m851006 SCU Module
  • Valmet Metso 181226 Digital Input Module
  • Valmet AIU16T Analog Input Module - 16-Channel 65421466-2B MT924 V1.3
  • Valmet WIN3136875 Slide Clutch
  • Metso Valmet TIU61 A413111 Temperature Input Unit
  • Valmet MC12S Slitter Motor
  • Valmet A413139 AOH4 Board - Analog Output High Module
  • Valmet A409001 BIU85 Board
  • Valmet A413063 DMU Board
  • Valmet A413325 IPU I/O Power Unit
  • Valmet M851004 M2 CPU Module
  • Valmet IOP345 Digital Input Module
  • Metso Valmet A413215 Communication Board
  • Valmet DIFF-EL 80 M1 Transmitter
  • Valmet A413001 CPU Module
  • Valmet M899520 TDC-2 Module
  • Valmet A409001 BIU85 Board
  • Metso Valmet A413005 CPU Module
  • VALMET PUD 10 B Process Automation Rack with CPU SCU Module
  • Valmet A413091 GDU1 Board
  • VALMET M851006 M2 SCU Module
  • Lyngso Valmet Marine 990.896.000 Position Loop Card
  • Valmet Cooking Liquor Measurement 3417H
  • VALMET ABMB MT831 PCB Card
  • Valmet Automation A413325 IPU I/O Power Unit
  • Valmet Metso Consistency Transmitter Smart Pulp M2
  • VALMET METSO A413274 Connection Module
  • VALMET PI33S1KSA02RSA-ELI26 Switch
  • VALMET ND9103HN-CE07-K05 Intelligent Valve Controller
  • VALMET PMB 2R 16 Slot Backplane PCB Card
  • NELES VALMET A413135 AOU 4 Output Module
  • Metso Valmet A413345 FPU Power Unit
  • VALMET A413171 PIC Module
  • VALMET A413620 Repeater Module
  • Valmet M851521 Memory Card
  • Valmet DIFF-EL 140 M1 Transmitter
  • Valmet A413064 DMU Module
  • Valmet IOP371 I/O Bus Extender Module
  • Valmet Cooking Liquor Measurement 3400 Model 3417H
  • Metso Valmet A413043 CPU Module – Industrial Processor
  • Valmet BIU4 M851221 Binary Input Module
  • Valmet PMB 1S CPU SCU Rack Module
  • Valmet A413248 Controller Module
  • Valmet PDP601 Distributed Processing Unit
  • VALMET M851004 M2 CPU Printed Circuit Board Module
  • Metso Valmet A413045 Ver.05 CPU Module
  • Valmet A413181 Ver.05 PLU1 Board
  • Lyngso Valmet ATB16 Controller Board
  • VALMET AIU 16 Analog Input Unit 545100-3A/3B
  • VALMET PUD 10 B Power Supply PCB Rack Module
  • Valmet MS-50V/120V Bearing Unit
  • Valmet PDP603 Distributed Processing Unit – DPU Module
  • Valmet A413110 TIU Board – Terminal Interface Unit
  • Valmet S420154 I/O Backplane PCB – Printed Circuit Board
  • Valmet A413173 Industrial Control Module
  • Valmet A413044 CPU Module
  • Valmet A4IU1 Analog I/O Module
  • Valmet A413325 IPU Power Unit – PLC Module
  • Valmet M851002 CPU Module – Central Processing Unit
  • Valmet PUD10B Power Supply Board
  • Valmet K00990 Master CPU Electronic Assy
  • Valmet Metso IOP345 Input Module
  • Metso Automation T545215 Board
  • Valmet Metso IOP304 Input Module
  • Valmet 542844-6A SCU Module
  • Metso A413043 Ver.11 Valmet CPU Module
  • Valmet Automation BIU 8A Input Module
  • Metso A413044 Ver05 Valmet CPU Module
  • VALMET 542821-5A Control System Rack Module
  • Metso A413005 Ver.04 Valmet CPU Module
  • Valmet M851207 AIU16 Card
  • Valmet BIU8 Binary Input Unit
  • VALMET 547070-2B CPU Printed Circuit Board Module
  • Valmet Automation A413325 Power Module
  • VALMET AUTOMATION A413135 AOU4 Module