The CML25.1-3N-400-NN-NNC1-NW is a control hardware unit within the Rexroth IndraControl L25 family, the low-performance tier of the IndraMotion control platform. It occupies a position between a standalone PLC and a full-scale motion controller, offering deterministic program execution and integrated drive communication in a compact DIN-rail form factor. The type code specifies a SERCOS III interface configuration, distinguishing it from L25 variants that use PROFIBUS or configurable fieldbus options.
At the center of the CML25.1-3N-400 is a Renesas SH7785 processor from the SH4 family. This 32-bit RISC architecture is paired with 12 MB of combined code and data memory, a capacity that accommodates user programs, motion function libraries, and runtime data structures for moderate axis counts. The processing time is specified in the range of 35 microseconds for 1000 mixed instructions, a figure that reflects the deterministic execution behavior expected in motion and logic control applications. The controller supports up to 16 axes, allowing it to coordinate multi-axis machinery through the SERCOS III real-time bus.
The L25 platform is positioned as the entry point in the IndraMotion controller lineup, with the L45 and L65 models offering progressively higher memory and performance. The L25’s 12 MB user memory is therefore a deliberate constraint that defines the boundary of its application scope: it is intended for machines with moderate program complexity and axis counts, where the full resources of a higher-tier controller would be underutilized.
The “3N” segment of the type code identifies the integrated SERCOS III interface. SERCOS III is a real-time Ethernet-based fieldbus designed for motion control, providing deterministic cyclic communication between the controller and drive devices. In the IndraControl L25 context, SERCOS III serves as the primary path for command values, feedback data, and drive parameter access. The “400” segment indicates the hardware variant, and the NNC1 suffix specifies the local I/O and interface configuration.
The controller provides an Ethernet TCP/IP interface for programming, diagnostics, and vertical integration with higher-level systems. A ready contact interface supports basic machine signaling. For local expansion, the L25 accommodates up to 256 I/O channels and as many as 63 inline modules. The inline module concept allows digital, analog, and technology modules to be added directly to the controller assembly, reducing cabinet wiring and distributing I/O acquisition close to the point of use. This scalability supports both centralized architectures, where I/O is concentrated at the controller, and distributed topologies, where modules are placed nearer to sensors and actuators.
The CML25.1-3N-400-NN-NNC1-NW operates within the IndraLogic or IndraMotion engineering environment, where motion control, PLC logic, and drive parameterization are configured in a unified project. The controller executes user programs that coordinate drive axes, process field data, and manage machine sequences. SERCOS III provides the real-time channel for motion commands and drive status, while Ethernet TCP/IP carries non-real-time data such as programming access, diagnostics, and HMI communication.
The L25 hardware supports an integrated real-time clock and non-volatile memory for retaining parameters and program data across power cycles. The controller’s firmware and runtime environment are matched to the hardware variant, and the NNC1 configuration defines the onboard interfaces without optional fieldbus cards. This fixed configuration simplifies hardware selection for systems where SERCOS III is the designated drive bus and where local I/O requirements fall within the stated channel and module limits.
The IndraControl L25 is oriented toward machine builders who require coordinated motion and logic control without the overhead of a PC-based or high-end rack controller. Typical applications include packaging machines, handling systems, assembly stations, and specialized production equipment with up to 16 axes. The controller’s DIN-rail mounting and inline I/O expansion suit control cabinets where space is limited and where the I/O count is moderate. The SERCOS III interface aligns the L25 with drive systems that use this real-time bus, completing a control chain that runs from the user program through the motion kernel to the drive power stage.