Features
PROFIBUS-DP Module (DIN 19245)
Transmission rate up 12 MBd
supports up to 126 slaves
Physical interface: RS485
Electrical isolation
Shared memory (256 KB) onboard, to minimize the use of basic unit memory.
Module can be removed or inserted during operation
Redundant operation, with redundant AC 800F
Description
The FI 830F module interfaces to the Profibus fieldbus. It provides functionality according to the PROFIBUS-DP V1 standard (DIN 19245 amendment 1) and supports baud rates up 12 MBd.
The module is the master on the Profibus line and allows connecting up to 126 Profibus slaves. Configuration and parameterization is carried out completely with Control Builder F — no additional external configuration tools are required.
Line redundancy can be achieved using an external device (RLM 01) which drives two Profibus lines in parallel. In conjunction with a second AC 800F the module can also operate in a redundant-master mode without limiting any other feature.
Front Panel Connections
Profibus 9-pin female connector (DIN 41652)
LED Displays
State
Off No supply power, module is isolated
Green Module is active and working properly
Orange Module has been identified by AC 800F, but has not yet been activated
Red Module powered up, but not yet identified, or an error has occurred Busy
Off Module is in passive state on the Profibus.
Green Module has token and, thus, is acting as the master
Technical Data
Power consumption In the active state, depends on the communication cycle time:
2.8 W
Max. output current 20 mA for bus termination/repeater supply
Output voltage 5 V, ± 5%
Overvoltage
protection +7.5 V / -5 V
either transmission line to GND.
Weight approx. 0.150 kg
email:1583694102@qq.com