4) PFC output over/Under voltage protection When the bus voltage inside the module exceeds the over/under voltage protection point, the module automatically shuts down for protection without output, and the protection indicator (yellow) on the panel of the module is on. When the PFC input overvoltage and undervoltage protection occurs, the module reports an alarm signal to the monitoring module for corresponding handling. 5) Fan Fault protection When the fan is faulty, the module generates a fan fault alarm, the fault indicator on the panel of the module blinks red, and the module shuts down without voltage output. After the fault is rectified, it automatically recovers to normal operation. When a fault event occurs, the module reports an alarm signal to the monitoring module for corresponding handling.
6) Short-circuit protection rectifier module adopts constant current protection mode, in the case of output short-circuit, the output current of the module remains constant, current ≤65A, effectively protect itself and external equipment; When the short circuit fault disappears, the module automatically recovers.
7) Output current imbalance When multiple rectifier modules are used in parallel in the system, the module with large current sharing error can automatically identify and light the protection indicator light (yellow light) on the panel of the module; If the output current of the module is seriously unbalanced, the module whose current equalization error is greater than 10A and the module has no output can automatically identify and light the fault indicator (red light) on the panel of the module. After the fault is rectified, it automatically recovers to normal operation. When a fault event occurs, the module reports an alarm signal to the monitoring module for corresponding handling.
8) Background communication interruption When the communication is interrupted, the protection indicator (yellow) of the module panel blinks. After the communication is restored, the protection indicator (yellow) on the panel of the module is restored. When the communication between modules is normal, the module automatically recovers. In order to protect the battery, when the module communication fails, the output voltage of the module changes to 53.5V (different voltages can be preset according to actual needs). 9) Module address conflict If the internal addresses of multiple rectifier modules on the power system are the same, the rectifier modules will generate an address conflict alarm, and the fault indicator (red) on the module panel will turn on. The rectifier module must be replaced.
10. The rectifier module has a built-in advanced digital signal processor DSP, which monitors and controls the operation of the whole module, and communicates with the external monitoring module through the CAN bus.
The details include:
1) You can control the on/off of the rectifier module through the monitoring module and set the output current slow start function and overvoltage protection reset mode of the module.
2) The output voltage, overvoltage point, output slow start time and current limiting point of the rectifier module can be adjusted through the monitoring module.
3) Send input voltage, output voltage, output current, current limiting point, temperature, overvoltage point to the monitoring module;
4) Send the on/off status to the monitoring module, and report the input protection, internal PFC over/under voltage protection, over temperature protection, over voltage off fault, fan fault, temperature power limit, input power limit, current imbalance, module address conflict and other fault information and technical parameters
1. Ambient conditions: Operating temperature: -5 ° C to 45 ° C, derated above 45 ° C Storage temperature: -40 ° C to 70 ° C Relative humidity: ≤95%RH, non-condensing Altitude: ≤2000m (derated above 2000m is required) Cooling mode: forced air cooling
2. Input feature: Input voltage range: 85Vac ~ 290Vac, single-phase three-wire rated input voltage range: 200Vac ~ 250Vac Power derated Input voltage range: 85Vac ~ 176VA Maximum static voltage when not working: 415Vac Rated input current: < 16A@3000W Maximum input current: < 19A@3000W/176Vac input impulse current: <30A Permissible input power grid frequency: 45 ~ 65Hz Rated input power grid frequency: 50Hz/60Hz 3 Output characteristics: Output DC voltage range: 42V to 58V Output DC current: 0A to 60.5A Voltage regulator Accuracy ≤± 0.5% Load adjustment rate ≤± 0.5% Voltage adjustment rate ≤± 0.1% upstroke amplitude ≤±1% 4. Output current limiting feature: stepless current limiting point 0A ~
Choose Xiamen control Smith after sale worry
Excellent product quality
Only cooperate with manufacturers of first-line brands in the industry
Imports/Products
Good pre-sale service
Communicated with customers repeatedly about product model, quality, price and delivery date
Work with the customer to determine the best solution
Address user concerns in advance
Business execution in place
Ordered products delivered on time
Make perfect delivery plan to ensure the time limit
Assist users to handle the acceptance procedures
email:1583694102@qq.com
wang@kongjiangauto.com