Pollution protection: Class G3 (ISA S71.04) pollution level, resistant to industrial dust, oil pollution and other environments;
Certification compliance: UL (US/Canada), ATEX (DEMKO), CE, RoHS certification, suitable for ordinary areas and potentially explosive environments (Ex certification).
4. Deployment and maintenance convenience
Hot swappable design: FBM modules can be directly plugged and unplugged without disconnecting external field equipment wiring or internal cables;
Online expansion: Supports adding new baseboards to the baseboard chain online, without the need for downtime in redundant HDLC fieldbus environments;
Fault diagnosis: Power supply faults can be indicated through three prompts: SMDH (System Management Interface) icon color change, system monitoring display, and alarm printing; FBM faults can be quickly located by controlling network feedback.
Compatibility and upgrade requirements
1. Software compatibility
Required software version: I/A Series software v8.8 or Foxboro Evo Control Core Services v9.0 or above;
Supporting tools: Corresponding versions of system configuration software (such as SMDH) are required for module configuration, fault monitoring, and maintenance.
2. Hardware compatibility
Control processor: Only supports FCP280, FCP270, and ZCP270, and requires corresponding sizing guidelines (such as FCP280 reference B0700FY) to confirm capacity;
Power supply: Supports four types of 24V DC power supplies: FPS480-24, FPS400-24, FPS240-24, and FPS120-24. The selection should be based on the enclosure power budget;
Terminal Component (TA): Different FBMs require dedicated TAs (such as TAs with relays for high voltage/high current digital outputs), and some TAs provide additional channel isolation functionality.
3. Upgrading Path for Existing Systems
The existing standard 200 Series subsystem can be directly upgraded to Compact 200 Series, with the following steps:
Remove the standard 200 Series horizontal bottom plate and replace it with a Compact 200 Series 16 slot bottom plate;
Confirm installation environment: Ensure sufficient horizontal DIN rails, power capacity, and heat dissipation space (1 fan tray is required for every 2 adjacent Compact baseboards, and 1 tray is required for every 1 baseboard when deployed separately);
Replace cable: Replace the terminal cable of the standard FBM with the dedicated cable corresponding to the Compact FBM (refer to the PSS document of each FBM);
Software adaptation: Upgrade to a compatible version of I/A Series or Foxboro Evo software to complete module configuration.

Application scenarios and industry adaptation
1. Core application scenarios
Continuous process control: continuous production processes in industries such as petrochemicals, chemical engineering, and power (such as reactor temperature/pressure control, pipeline flow regulation);
Batch production control: Batch production processes in industries such as pharmaceuticals, food and beverage (such as ingredient ratio control, batch data collection);
Discrete control: Discrete equipment control in manufacturing industry (such as valve switching, motor start stop, status monitoring);
Existing system upgrade: Performance upgrade and expansion needs of existing Foxboro 100/200 Series system users.
2. Scope of environmental adaptation
Ordinary industrial environment: factory workshop, control room, compatible with IP43/54 protection level;
Adverse environment: Class G3 pollution level, high temperature (60 ℃) environment, such as metallurgical plants and chemical plant sites;
Hazardous environment: Potential explosive atmosphere (ATEX certified), such as explosion-proof areas in the petrochemical industry.