LED Displays
Power
Green Internal supply voltage is available
Failure
Off Normal status
Orange Self test
Flashing orange Overtemperature occurred during operation
Red Hardware failure of the basic unit
Flashing red Software failure of the system
Run/Stop
Green Processing active
Flashing green Process was stopped and is now started
again
Red Processing inactive
Flashing red Process was active and is stopped now
Orange Self test
Off Software initialization
Prim/Sec In case of redundancy please see the
LED’s meaning in manual “Mounting and
Installation Instruction”.
For not redundancy the states are:
Orange Self test
Off Normal status
Operator Controls
Run/Stop switch Connected to LED
Toggle Prim/Sec For redundancy.
Toggles between primary and secondary
AC 800F (operational on primary AC 800F
only, and only if a secondary AC 800F is
available)
Reset Reset button
press and hold > 4 s for coldstart
Front Panel Connections
Power supply Two connectors for 24 V DC,
automatic input selection when used with
single power supply
Diag For diagnostics and optional radiocontrolled
clock
9-pin male connector
Fig. SD 802F
Power Supply SD 802F / SD 812F
Technical Data SD 802F
Input voltage 2 x direct current 24 V DC
permissible range 19.2 - 32.5 V DC
Input current at
nominal load 1.3 A at 24 V DC
Rated input power 31 W
Backup energy for
the event of
power failure > 20 ms
Fuse For each supply: subminiature fuse
3.15 AT, soldered
Output voltage 3.3 V DC (± 3%) typical
5 V DC (± 3%) typical
Output current 0.5 - 5 A
Current limit approx. 6 A
Automatic return to normal operation after
short circuit
Total output power max. 26.5 W
Weight 0.460 kg
Technical Data SD 812F
Input voltage 2 x direct current 24 V DC
permissible range 19.2 - 32.5 V DC
Input current at
nominal load 1.7 A at 24 V DC
Rated input power 41 W
Backup energy for
the event of
power failure > 20 ms
Fuse For each supply: subminiature fuse
3.15 AT, soldered
Output voltage 3.3 V DC (± 3%) typical
5 V DC (± 3%) typical
Output current 0.5 - 6.5 A to 3.3 V
0.5 - 5.5 A to 5.0 V
Current limit approx. 7.5 A
Automatic return to normal operation after
short circuit
Total output power max. 35 W
Weight 0.460 kg
Technical Data
Rated voltage 3.3 V / 5 V, ±3%, from CPU board
Power consumption max. 2.8 W
Thin Ethernet 10Base2
RAM and real-time-clock buffering time
PM 802F PM 803F
New battery inserted ≥ 1,5 years without buffering
After “Low” warning ≥ 10 days
Battery 3.6 V lithium battery, 950 mAh
(not in the delivery)
Weight approx. 0.150 kg (without battery)
June
Description
These communication modules provide Ethernet communications
to the system bus compliant with IEEE802.3 standard.
Communications module, to connect a commercial transceiver
with AUI connector (15-pin female plug DIN 41652).
LED Displays
State
Off No supply voltage, module is isolated
Green Power supply on, module identified and
ready to operate as configured.
Orange Power supply on,
module identified and either:
— normal transitory state after module
startup
— configuration mode of Boot Loader
Orange flashing Power supply on, module identified; module
not connected to proper bus structure.
Red Power supply on and either:
— module not yet identified (normal for
short time during module startup)
— error occurred during module test
Battery (PM803F)
Off AC 800F is active, EI 812F not active
=>buffering from power supply module
AC 800F is off (no watchdog of the batteries
voltage) =>buffering from battery.
Orange During battery recovery or start-up phase
Red Warning: battery low, no battery inserted,
insufficient electrical contact etc.
Green battery inserted and data protection provided.
Battery (PM802F)
Off Sufficient buffer battery voltage
email:1583694102@qq.com
wang@kongjiangauto.com