ABB Instrumentation'" 2600T Pressure Transmitter family
364Ax-Gx Instruction Manual
Configuration
Default configuration
The data default configuration at the product delivery is the following:
Damping: 1 second
Units: kPa
LRV: OkPa
URV: equal to URL
Transfer functio! linear
Hardware sei : Write protect mode in OFF, Failsafe direction High
Low saturation current: 3.8 mA
High saturation current: 20.5 mA
Low fail current: 3.7 mA
High fail current: 22 mA
LCD Display: Set to display the PV value.
Easy Setup
To facilitate commissioning the 364 Display has the capability to run a sequence of predefined setup steps
with the main configuration settings.
When you start the Easy Setup you must continue up to the end to exit.
To start the Easy Setup:
Navigate the Digital LCD Integral Display menu, select Easy Setup.
= Digital LCD Integral Display Keys sequence to start the Easy Setup: 1
Caution — Risk
Only qualified and authorized specialist personnel should be charged with installation, electrical connection, commissioning, and maintenance of the transmitter.
Qualified personnel are persons who have experience in in stallation, electrical wiring connection, commissioning, and operation of the transmitter or similar devices, and hold the necessary qualifications such as:
Training or instruction, authorization to operate and mai according to safety engineering standards for electrical circui aggressive media
Training or instruction in accordance with safety enginee ring standards regarding
maintenance and use of adequate safety systems in devices or systems ,high pressures, and For safety reasons, ABB draws your attention to the fact that only s ufficiently insulated tools conforming to DIN EN 60900 may be used.
Since the transmitter may form part of a safety chain, we recommend replacing the device immediately if any defects are detected.
In case of use in H.A. Non sparking tools only must be employed.
Warning - General risks
The device can be operated at high levels of pressure and with aggressive media.
As a result, serious injury or significant property damage may occur if this device is
operated incorrectly.
Prior to using corrosive and abrasive materials for measurement purposes, the operator
must check the level of resistance of all parts coming into contact with the materials to be
measured.
Transport and storage
After unpacking the pressure transmitter, check the device for transport damage.
Check the packing material for accessories.
During intermediate storage or transport, store the pressure transmitter in the original packaging only.
For information on permissible ambient conditions for storage and transport, see "Te chnical data". T he
storage time is indefinite, however, the warranty conditions stipulated in the order confirmation of the supplier
are valid.
364Ax-Gx Instruction Manual
Mounting the transmitter
Testing Impulse piping
To ensure proper proper pipe laying, the following points must
be observed:
+ Keep the impulse piping as short as possible and avoid
sharp bends.
+ Route th e impulse piping so thatno deposits can
accumulate. Angles of inclination should
not be less than 8 % ascending or descending.
+ Theimpu Ise piping should be blown through with
compressed air or better yet flushed
through with the measuring medium before connection.
+ Completely bleed the impulse piping if the medium is a fluid.
+ Lay the impulse piping so that gas bubbles (when measuring
fluids) or condensate (when measuring gases) can flow
back into the process line.
+ When measuring steam, make sure that hot steam cannot
flow back into the process connection (hydraulic seal, e.g., a siphon is filled with water b efore
installation).
+ Check the tightness of the connection. or calibration input, and provide space for the housing cover
to be removed for electrical wiring and maintenance