Core features and structure of the product
1. Core design and maintenance free advantages
Vacuum arc extinguishing system:
The arc extinguishing chamber adopts air insulation, which can be freely contacted and the insulation components are easy to clean in harsh environments;
The upper bracket of the arc extinguishing chamber is fixed, the lower bracket is axially guided, and the supporting components absorb external forces and contact pressure during opening and closing;
Maintenance free cycle: Under normal conditions (IEC 62271-1), it supports 10000 operating cycles without lubrication or adjustment.
Spring energy storage operating mechanism:
Energy storage method: electric energy storage (standard, motor voltage 24-240V DC/AC) or manual energy storage (with dedicated handle, order number 3AX15 30-4A/B/C);
Opening and closing control: remote electric (closing soleoid voltage 24-240V DC/AC), local mechanical/electric (to prevent accidental closing, switch equipment interlock needs to be connected);
Operation sequence: Supports standard sequence O-3min-CO-3min-CO (normal current), CO-30min-CO (short-circuit current), and some models support O-0.3s-CO-15s-CO (≤ 31.5kA).
2. Key functions and safety design
Free release mechanism: in accordance with IEC 62271-100, when receiving a disconnection command during the closing process, the contact immediately returns to the disconnection position and remains in place to avoid continuous disconnection ("pump effect");
Interlocking system:
Electrical interlocking: The auxiliary contacts of the circuit breaker control the electromagnetic lock of the isolation switch, which can only be operated when the circuit breaker is opened;
Mechanical interlocking: detecting the position of the circuit breaker through sensors to prevent on load opening and closing, and adapting to drawer type components;
Release signal control: When the NO contact is opened, it instantly closes, triggering the alarm system. Local control requires a series cut-off switch (distinguishing between automatic/manual opening).
Technical parameters and environmental adaptation
1. Core electrical parameters (classified by voltage level)
Voltage level Rated lightning impulse withstand voltage (kV) Rated short-time power frequency withstand voltage (kV) Rated short-circuit breaking current (kA) Rated normal current (A) Pole distance (mm)
7.2kV 60/75 20/32 50/63 1250-4000 210/275
12kV 75/95 28/36 50/63 1250-4000 210/275
17.5kV 95/110 36/42 50/63/72 3150-8000 275/300
24kV 125/145 50/60 50/63/72 3150-8000 275/300
36kV 170/185/195 70/85/95 31.5/40 1250-4000 350
40.5kV 185/195 85/95 31.5/40 1250-4000 350
2. Environmental and installation restrictions
Climate environment: Complies with IEC 60721-3-3, with specific levels as follows:
Key requirements for environmental type level
Climate environment 3K4 low temperature -5 ℃, humidity ≤ 95%/day, ≤ 90%/month
Biological environment 3B1 is free from mold and insect erosion
Mechanical environment 3M2 anti vibration and impact
Chemical active substance 3C2 is resistant to slightly corrosive gases (without freezing/wind blown precipitation)
Mechanical active substance 3S2 requires regular cleaning of insulation components
Elevation and insulation correction:
When the reference altitude is 1000m, the insulation level needs to be corrected according to the altitude coefficient K a, with the formula: U ≥ U 0 × K a; Example: At 2500m, K a=1.2. If a 75kV lightning impulse withstand voltage is required, a 90kV reference insulation level should be selected.
Current carrying capacity: The reference temperature is 40 ℃ (for open type switchgear), and the rating can be increased when the temperature is below 40 ℃. For example, the carrying current of 6300A can be increased by about 15% at 20 ℃ (refer to the current temperature curve in the document).

Selection and Configuration Rules
1. Order number structure (16 digits)
Main circuit section (4-8 bits): Define voltage, short-circuit breaking current, rated current, pole spacing, for example:
3AH3 305-6:3 (main group), A (subgroup), H (series), 3 (version), 305-6 (36kV, 40kA, 2500A, 350mm pole spacing);
Secondary equipment section (bits 9-16): Define the combination of release devices, operating voltage, and auxiliary switches, for example:
9-position (release): A (1 shunt release), M (2 shunt releases+1 undervoltage release);
10 positions (closed soleoid): B (24V DC), F (220V DC), K (230V AC);
Option code: End with "- Z" and add a 3-digit code (e.g. Z A20:64 pole plug gold-plated).
2. Core options and auxiliary equipment
Option Category Model/Code Function Description Applicable Scenarios
Automatic tripping device with shunt release (connected to protective relay, 24-240V DC/AC) for overcurrent protection
When the undervoltage release voltage is less than 35% of the rated value, the circuit breaker (24-240V DC/AC) provides abnormal voltage protection
Current transformer operation release without auxiliary power supply, time division switch (0.5/1A rated current), remote and no power supply scenario
Auxiliary switch 6NO+6NC standard, providing regular control requirements for opening and closing status signals