1. 239 Relay Features
The GE Multilin 239 relay is designed to fully protect three phase AC motors against
conditions which can cause damage. In addition to motor protection, the relay has
features that can protect associated mechanical equipment, give an alarm before
damage results from a process malfunction, diagnose problems after a fault and allow
verification of correct relay operation during routine maintenance. Using the ModBus serial
communications interface, motor starters throughout a plant can be connected to a
central control/monitoring system for continuous monitoring and fast fault diagnosis of a
complete process.
One relay is required per motor. Since phase current is monitored through current
transformers, motors of any line voltage can be protected. The relay is used as a pilot
device to cause a contactor or breaker to open under fault conditions; that is, it does not
carry the primary motor current. When the over temperature option is ordered, up to 3
RTDs can be monitored. These can all be in the stator or 1 in the stator and 2 in the
bearings. Installing a 239 in a motor starter for protection and monitoring of motors will
minimize downtime due to process problems.
2 Typical Applications
Versatile features and simple programming controls make the 239 an ideal choice for
motor and equipment protection in a wide range of applications. In addition to basic
electrical protection for motors, the 239 can protect against common faults due to process
problems, such as:
1. Mechanical protection of pumps using the undercurrent feature to detect loss of
suction or a closed discharge valve.
2. Mechanical protection of fans against loss of air flow in mines or flow in steam
generating boilers using the undercurrent feature.
3. Electrical protection of compressor motors from excessive run up time caused by an
open outlet using the start timer.
4. Mechanical protection of gears, pumps, fans, saw mill cutters, and compressors
against mechanical jam using the mechanical jam trip feature.
5. Safety to personnel from shock hazard using the ground fault feature to detect
winding shorts from moisture.
6. Protection of motors and equipment from operator abuse using the thermal memory
lockout.
Cost savings are provided using versatile features such as:
1. Diagnostic information after a trip to identify problems and bring the process back on
line quickly.
2. Fault indication of ground fault without shutdown to warn that corrective
maintenance is required.
3. Simplified spare parts stocking and initial specification design using one universal
model for many motor sizes, applications and settings.
4. Serial communication using the popular Modbus protocol to remotely monitor all
values, program setpoints, issue commands and diagnose faults to minimize process
disruptions.
5. Output of motor current suitable for programmable controller interface (4 to 20 mA).
MODIFICATIONS
• MOD 500: Portable test/carrying case
• MOD 501: 20 to 60 V DC / 20 to 48 V AC control power
• MOD 504: Removable terminal blocks
• MOD 505: Enhanced start protection
• MOD 506: Custom programmable overload curve
• MOD 509: Directional ground sensing with 120 V AC polarizing voltage
• MOD 512: 1 AMP Ground CT input
• MOD 513: Class 1 Division 2 operation
• MOD 517: Australian Mines approval
ACCESSORIES
• 239PC Windows software (supplied free)
• Phase and ground CTs
• RS232 to RS485 converter (required to connect a computer to the 239 relay(s) to run
239PC)
• RS485 Terminating Network
• 2.25” collar for limited depth mounting (1009-0068)
• Large size (8.5 x 11”) instruction manual (free upon request)
CONTROL POWER
• 90 to 300 V DC / 70 to 265 V AC standard
• 20 to 60 V DC / 20 to 48 V AC (MOD 501
1. MODEL NO: The model number shows the configuration of the relay. The model
number for a basic unit is 239. RTD and AN will appear in the model number only if the
RTD option or Analog Output option is installed. H will appear in the model number if
conformal coating is required.
2. SUPPLY VOLTAGE: Indicates the 239 power supply input configuration. The 239 shown
above can accept any AC 50/60Hz voltage from 70 to 265 V AC or DC voltage from 90
to 300 V DC.
3. TAG#: This is an optional identification number specified by the customer.
4. MOD#s: These are used if unique features have been installed for special customer
orders. These numbers should be available when contacting GE Multilin for technical
support. Up to five MOD#s can be installed into the 239.
5. SERIAL NO: Indicates the serial number for the 239 in numeric and barcode format.
The following table shows the revision history of the 239. Each revision of the instruction
manual corresponds to a particular firmware revision in the 239. The instruction manual
revision is located on the first page of the manual as part of the manual P/N (1601-00XXRevision).
The 239 firmware revision is loaded in the relay and can be found by scrolling to
the display message A3: PRODUCT INFOFIRMWARE VERSIONSMAIN PROGRAM
VER.
When using the manual to determine relay features and settings, ensure that the revision
corresponds to the 239 firmware revision using the table below. For a large instruction
manual (8.5” × 11”) the part number is 1601-0067; for a small instruction manual (5.5” ×