Protocol type: RTU
Equipment number: 1
Baud rate: 19200
Stop position: 1
Checkpoint: None
3.3 Printer Settings
OpView supports connecting printers through parallel ports to output alarm logs. The printer needs to be configured as:
Baud rate: 9600
Checkpoint: None
Data bits: 8
Stop position: 1
3.4 Initial Settings
After power on, OpView will perform diagnostic tests for approximately a few minutes. If communication with the 5009 controller fails, it may take up to 20 minutes to display the application interface. It is recommended to set the date and time of OpView when using it for the first time. Please refer to page 14 of the manual for specific steps.
Detailed explanation of the operation interface
4.1 Main Menu
The main menu is the hub for accessing other function screens and includes the following key function buttons:
Local/Remote Switching: Used to enable or disable the remote control panel.
Emergency Shutdown (ESD): Adopting a two-step verification process to prevent misoperation.
Alarm log: Directly access the alarm record interface.
Configure password: After entering the password, you can enter the application manager for advanced settings.
4.2 Core Function Screen
(1) Turbine Start Screen
According to the configuration of the 5009 controller, three startup modes are displayed:
Idle/Rated Mode
No idle mode (manual up/down only)
Auto Start Sequence
This screen provides functions such as startup status display, speed setting adjustment, and valve limiter control.
(2) Turbine Run Screen
Display turbine type and application configuration in a graphical manner, supporting:
Frequency control arm/release
Load sharing enabled/disabled
Synchronizer control
Run time statistics
(3) Turbine Control Screen
Allow direct input of set values and input specific numerical values through a pop-up keyboard. Support:
Set value up/down adjustment
Enable/disable remote settings
Valve requirement display
(4) Valve Calibration Screen
After meeting the system license conditions (turbine shutdown, speed below 1000 RPM) and entering the calibration password, valve calibration can be performed. Support:
Valve position adjustment (fast/slow)
Minimum/maximum mA setting
Calibration parameter saving
(5) PID Control Screen
Display all configured PID outputs and set values in the form of a bar chart for easy observation of the interaction between various control loops.
(6) Trend&Dynamics Screens
Provide a one minute trend chart (sampled per second), supporting:
PID parameter adjustment (proportional, integral, derivative)
Trend resolution adjustment
Dynamic parameter saving
4.3 Alarm Management System
OpView provides complete alarm recording function:
Alarm log: displays current alarms (red with asterisks) and historical alarms.
Alarm confirmation and reset: Manage alarm status through ALM ACK and RESET buttons.
Print output: Supports real-time output of alarm events by connecting to a serial printer.
Alarm History: Stores the last 500 alarm records and cannot be cleared.

Password and permission management
OpView adopts a three-level password permission system to prevent unauthorized access:
SUPVAR level password: 1113, used to access the application manager.
Tuning/valve calibration level password: 1111, used for dynamic adjustment and valve calibration.
5009 user level password: 5009, regular operation permissions.
It is recommended to set the permissions to the 5009 user level during normal operation to protect system security.
Fault diagnosis and maintenance recommendations
6.1 Communication Fault Handling
If the screen displays' LOST COMMUNICATION ', please check:
Is the communication cable connected correctly
Does the port setting of the 5009 controller match the communication parameters of OpView
Does the communication distance exceed the standard limit
6.2 Electrostatic protection measures
Contact the grounding surface before operation to release static electricity
Avoid using plastic, vinyl, or foam materials near circuit boards
Use anti-static packaging bags when replacing circuit boards
6.3 Regular maintenance
Regularly check the reliability of communication connections
Update OpView time and date settings
Backup alarm logs and historical data