1.1.2 “Fail-freeze” function
Pos: 3.10 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Sicherheitsfunktion "blockierend" @ 10mod_1176211845484_3101.doc @ 76851
If the electrical power supply should fail, the positioner output 1 (and
2, if applicable) is closed and the pneumatic actuator stops
(“freezes”) the valve in the current position. If compressed air supply
should fail, the positioner depressurizes the actuator.
Pos: 3.11 /Überschriften/1.1/2-spaltig/Bedienung @ 10mod_1176211172234_3101.doc @ 76704
1.2 Operation
Pos: 3.12 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Bedienung (Kommunikationsmöglichkeit) @ 10mod_1173184631054_3101.doc @ 71160
The positioner has a built-in operating panel providing a 2-line LCD
and 4 pushbuttons for optimal local configuration, commissioning and
operational monitoring.
Alternatively, the appropriate configuration program and the available
communication option can be used.
Pos: 3.13 /Überschriften/1.1/2-spaltig/Kommunikation @ 10mod_1176211201546_3101.doc @ 76725
1.3 Communication
Pos: 3.14 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kurzbeschreibung/Kommunikation @ 10mod_1176212225390_3101.doc @ 76893
The standard TZIDC model has a local communication interface (LKS
connector). Additionally, a “HART communication” option for
communication via the 20 mA signal is available. Both
communications are based on the HART Protocol.
Pos: 3.15 /Überschriften/1.1/2-spaltig/Ein-/Ausgänge @ 10mod_1176211233015_3101.doc @ 76746
1.4 Inputs and outputs
Pos: 3.16 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kurzbeschreibung/Ein-/Ausgänge @ 10mod_1176212290390_3101.doc @ 76914
In addition to its input for the analog position set point the TZIDC
positioner is equipped with a digital input which can be used to
activate various protective functions in the device via the process
control system. A digital output allows you to output collective alarms
or fault messages.
Pos: 3.17 /Überschriften/1.1/2-spaltig/Modularer Aufbau @ 10mod_1176211317984_3101.doc @ 76767
1.5 Modular design
Pos: 3.18 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/ModularerAufbau @ 10mod_1173184783043_3101.doc @ 71181
q
The TZIDC basic model can be enhanced at any time by retrofitting
optional equipment. Option modules for analog or digital position
feedback or a shutdown-module can be installed. Additionally, a
mechanical position indicator, proximity switches or 24 V
microswitches are available for indicating the position independently
of the mother board function
3.1.2 Adjustment parameters
Pos: 7.8 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Justageparameter @ 10mod_1176214397515_3101.doc @ 77364
The TZIDC positioner has a special function for automatic adjustment
of the parameters.
Additionally, the control parameters can be set automatically (in
adaptive control mode) or manually to optimally adapt them to the
process requirements.
Tolerance band
When reaching the tolerance band the position is considered as
corrected. From this point on, the position is further slowly readjusted
until the dead band is reached. The factory setting for this
parameter is 0.3 %.
Dead band (sensitivity)
When reaching the dead band, the position is held. The factory
setting for this parameter is 0,1 %.
Actuator spring action
Selection of the sensor shaft rotating sense (looking into the open
case), if the valve is moved to the safe position by the actuator spring
(actuator is depressurized via Y1/OUT1).
For double-acting actuators the actuator spring action corresponds to
pressurizing the pneumatic output (OUT2).
Display 0 ... 100 %
Adjusting the display (0 ... 100 %) according to the direction of action
for opening or closing the valve