3.1 General
Pos: 7.4 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Betrieb/Allgemeines @ 10mod_1176214294328_3101.doc @ 77292
Microprocessor-based position control in the TZIDC provides for
optimal results. The positioner features high-precision control
functions and high operational reliability. Due to their elaborate
structure and easy accessibility, the device parameters can be
quickly adapted to the respective application.
The total range of parameters includes:
- Operating parameters
- Adjustment parameters
- Monitoring parameters
- Diagnosis parameters
- Maintenance parameters
Pos: 7.5 /Überschriften/1.1.1/2-spaltig/Betriebsparameter @ 10mod_1176214001500_3101.doc @ 77145
3.1.1 Operating parameters
Pos: 7.6 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Betriebsparameter @ 10mod_1176214346265_3101.doc @ 77343
The following operating parameters can be set manually if required:
Signal
Signal min. 4 mA, max. signal 20 mA (0 ... 100 %)
freely selectable for split-range operation
min. range 20 % (3.2 mA)
recommended range > 50 % (8.0 mA)
Action (positioning signal)
Increasing: Signal 4 ... 20 mA = position 0 ... 100 %
Increasing: Signal 20 ... 4 mA = position 0 ... 100 %
Characteristic curve (travel = f {signal})
Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1 or freely
configurable with 20 reference points.
Travel limit
The positioning travel, i.e. the stroke or angle of rotation, can be
reduced as required within the full range of 0 ... 100 %, provided that
a minimum value of 20 % is observed.
Shut-off function
This parameter can be set separately for each end position. When
the respective configured limit value is exceeded, the shut-off
function causes immediate travel of the actuator until reaching the set
end position.
When the shut-off value is set to “0”, the position is further controlled,
even in the respective end position.
Travel time prolongation
This function can be used to increase the max. travel time for full
travel. This time parameter can be set separately for each direction.
Important
This function can only be used with the pneumatics with the
safety function “fail-safe”.
Switching points for the position
This parameter allows you to define two position limits for signaling
(see option “Module for digital position feedback”).
Digital output
The alarms generated in the TZIDC positioner can be polled via the
digital output as a collective alarm.
The desired information can be selected via the operator panel or
remotely via the configuration program.
The output can be set to “active high” or “active low”, as required.
Digital input
For the digital input, one of the following safety options can be
selected. You may use the operator’s panel or configuration program
to select an option.
- No function (default)
- Move to 0 % position
- Move to 100 % position
- Hold previous position
- disable local configuration
- Disable local configuration and operation
- Disable any access (no local or remote access via a PC)
The selected function is activated once the 24 V DC signal is no
longer applied (< 11 V DC).
Pos: 7.7 /Überschriften/1.1.1/2-spaltig/Justageparameter @ 10mod_1176214036515_3101.doc @ 77166
3.1.2 Adjustment parameters
Pos: 7.8 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Justageparameter @ 10mod_1176214397515_3101.doc @ 77364
The TZIDC positioner has a special function for automatic adjustment
of the parameters.
Additionally, the control parameters can be set automatically (in
adaptive control mode) or manually to optimally adapt them to the
process requirements.
Tolerance band
When reaching the tolerance band the position is considered as
corrected. From this point on, the position is further slowly readjusted
until the dead band is reached. The factory setting for this
parameter is 0.3 %.
Dead band (sensitivity)
When reaching the dead band, the position is held. The factory
setting for this parameter is 0,1 %.
Actuator spring action
Selection of the sensor shaft rotating sense (looking into the open
case), if the valve is moved to the safe position by the actuator spring
(actuator is depressurized via Y1/OUT1).
For double-acting actuators the actuator spring action corresponds to
pressurizing the pneumatic output (OUT2).
Display 0 ... 100 %
Adjusting the display (0 ... 100 %) according to the direction of action
for opening or closing the valve.
Pos: 7.9 /Überschriften/1.1.1/2-spaltig/Betriebsüberwachungsparameter @ 10mod_1176214071453_3101.doc @ 77187
3.1.3 Monitoring parameters
Pos: 7.10 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Betriebsüberwachungsparameter @ 10mod_1176214447375_3101.doc @ 77385