Dynamic input always remains 0. Sensor serial sequence error, signal type mismatch. Confirm if sensor output is normal; Check the signal type settings (A/B/C and inversion) in Pluto Manager
The safety output cannot be set to ON. The reset condition is not met, and the dual channel difference timeout check reset button is pressed; Monitor TCfault or EDM feedback signals
Gateway without communication DIP switch setting error, inconsistent baud rate, check node address and baud rate; Check the grounding of the cable shielding layer
When the IQ terminal is used as an output, the indicator light does not light up. IQ is not configured as an output or load short circuit check Pluto Manager setting; Measure output voltage
Regular maintenance:
Check the response time of all safety inputs and outputs every six months to ensure compliance with safety distance calculations.
Use Pluto Manager's "monitoring" function to record changes in I/O status and proactively detect signal jitter.
For applications that use silent lights, regularly test the light disconnection detection function (through current monitoring or function block fault output).