Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

How to troubleshoot YOKOGAWA ADMAG TI series AXW electromagnetic flowmeter (25-1800mm)?

来源: | 作者:FAN | 发布时间 :2025-10-30 | 431 次浏览: | Share:



How to troubleshoot YOKOGAWA ADMAG TI series AXW electromagnetic flowmeter (25-1800mm)?

Equipment Fundamentals and Safety Standards

1. Equipment positioning and scope of application

The AXW electromagnetic flowmeter is a pipeline type electromagnetic flow measurement device suitable for continuous measurement of fluid flow with a diameter of 25-1800mm (1-72 inches). It is divided into integrated flowmeter (sensor and transmitter integrated) and split type device (remote sensor+remote transmitter, such as AXW4A, AXG1A, AXFA11), and needs to be used with Yokogawa designated analyzer/communication tools (such as Modbus, PROFIBUS PA, EtherNet/IP and other communication protocols).

2. Core security principles

(1) Maintain operational safety

Personnel qualifications: Only authorized personnel from Yokogawa can carry out repairs, and wiring and maintenance must be carried out by professional engineers; Two or more people are required to cooperate in using the trolley during transportation (the equipment is heavy to avoid falling and injuring people).

Power supply and anti-static: Power off and wait for more than 20 minutes before maintenance (to prevent residual electric shock caused by capacitors); Wear an anti-static wristband when touching the circuit board to avoid damaging components due to static electricity.

Environment and fluid protection: The surface of the equipment may be hot to the touch under high-temperature fluid conditions, and it is necessary to prevent burns; Avoid contact with fluids and residual gases during maintenance of toxic fluids; Do not open the cover in damp environments (loss of protection level).

(2) Equipment protection requirements

Cover and sealing: When opening/closing the cover, check the threads and O-ring for damage/foreign objects. The O-ring should be regularly coated with silicone grease, and any damage should be replaced in a timely manner; Unused cable entrances need to be sealed with Yokogawa specific plugs (otherwise the protection level will be lost).

Grounding and power supply: protective grounding terminals are required (functional grounding terminals cannot be used as substitutes); An external 15A circuit breaker (compliant with IEC60947 standard) should be installed and labeled as a "power-off device".


Routine inspection and model confirmation

1. Regular inspection items

Key Points for Periodic Inspection of Inspection Content

Check for condensation and moisture inside the terminal box once a year to prevent short circuits in the circuit

Tighten the pipeline joint screws twice a year to prevent fluid leakage or equipment loosening from affecting the measurement

Electrode and lining inspection should be set as needed (such as for viscous/abrasive fluids) to check for electrode scaling and lining wear (to avoid measurement errors)

2. Model and specification confirmation

Identification location: The model, suffix code, serial number, instrument coefficient, and other information are marked on the nameplate of the equipment casing (the nameplate styles of integrated flow meters, remote sensors, and remote transmitters are different, as shown in Figure 2.1-2.6 of the manual).

Key information: Confirm that the model is consistent with the order, and provide the model and serial number during repair; Device information (such as sensor serial number and software version) can be viewed through device parameters (refer to the corresponding communication manual).

Equipment adjustment and maintenance operations

1. Adjustment of cable entry direction

Depending on the type of device, there may be differences in the adjustment method, and power off is required first. The core steps are as follows:

Equipment type, caliber range, tool requirements, adjustment angle range, key considerations

Integrated flow meter+small caliber remote sensor 25-450mm (1-18 inches) No. 5 hex wrench -90 °,+90 °,+180 ° (one step every 90 °). It is forbidden to loosen the screws on the opposite side of the cable inlet; Tighten 4 bolts diagonally after adjustment

Large caliber remote sensor (Style S1) 500-1800mm (20-72 inches) with 1.5 hex wrench and 46 hex wrench -140 ° to+180 °. First loosen the hex nut, then loosen the neck screw, adjust and tighten in sequence

Large caliber remote sensor (Style S2) 500-1800mm (20-72 inches) 5 # hex wrench -90 °,+90 °,+180 ° (one step every 90 °) integrated flowmeter, do not loosen the screws on the opposite side

Note: The cable entry direction cannot be adjusted for submersible and district heating/anti condensation types (optional code DHC).

2. Maintenance of transmitter

(1) Display unit adjustment (only supported by AXW4A, not supported by AXG1A)

Direction adjustment: After power off, use a No. 3 hex wrench to open the cover, loosen the 2 fixing screws of the display unit, rotate clockwise 90 ° (do not remove the connector), re tighten the screws, close the cover and lock it.

Display board replacement: After opening the cover, loosen the screws of the display board, unlock the connector according to the "UNLOCK" mark and pull it out. When installing the new board, align the interfaces to avoid cable entanglement, and torque the screws to 0.6 ± 0.05 N · m.

(2) Parameter backup and recovery

Backup location: Parameters can be backed up to the built-in memory of the display board, supporting "backup restore" (same device) and "copy" (same model/specification/software and hardware version device).

Matching requirements: When restoring/copying, it is necessary to ensure that the device model, communication code, motherboard/sensor board/display board software version, etc. are consistent (see Table 4.4 in the manual). For split type, sensor device information should be synchronized with transmitter parameters.

3. Hardware switch settings

According to the device type (integrated, AXW4A, AXG1A), the switch functions are different, and the core settings are as follows:

(1) Integrated and AXW4A remote transmitter

The switch is located below the display panel, including address switch, burn switch, write protection switch, etc. Key settings:

Key points for setting switch type functions

When the CPU of the burn switch (SW1-1) fails, the default current output direction is high output (>21.6mA); Option C1/C2 low output (<2.4mA)

Write protection switch (SW1-2) to prevent parameter overwrite ON: prohibit modification; OFF: Allow modification (effective in combination with software write protection)

Address switch (Address) device address (Modbus/PROFIBUS PA/EtherNet/IP) Modbus: 1-127 (0 automatically converted to 1); EtherNet/IP: Set IP segment 4 (1-244, all OFF/ON automatically converted to 210)

The line terminal switch (SW2) for Modbus bus terminal matching should be set to "Bus end" at both ends of the bus (SW2-1/2 both ON, 150 Ω resistor); Set the intermediate device to 'Not bus end'

(2) AXG1A remote transmitter

Only includes burn out switch (SW1-1) and write protect switch (SW1-2), with the same logic as AXW4A. It needs to be operated after opening the cover (using the corresponding tool) to avoid touching unrelated circuits.

image.png

Sensor inspection and health diagnosis

1. Excitation coil and insulation resistance inspection (only for remote sensors)

(1) Coil inspection

Step: After power off, disconnect the sensor terminal cable and use a multimeter to measure the continuity of the "EX1" and "EX2" terminals. If there is no continuity, the coil will be disconnected; Resistance ≥ 150 Ω is considered abnormal and requires contact with Yokogawa for maintenance.

(2) Insulation resistance inspection

The split coil circuit and signal circuit require a 500V DC insulation tester, with the following standards:

Precautions for Circuit Type Test Terminal Requirements

Coil circuit EX1 (excitation terminal) - C (common terminal) ≥ 1 M Ω. Fluid inside the pipeline can also be tested

Signal circuits C-A and C-B (signal terminals) ≥ 100 M Ω require emptying the pipeline and drying. Explosion proof type testing is prohibited

Note: The submersible and DHC types need to be measured at the cable terminal, not the sensor terminal.

2. Verification function (device health diagnosis)

(1) Functional positioning

Diagnosis of magnetic circuit, excitation circuit, calculation circuit, equipment status, and wiring connections can be done without dismantling the equipment, taking about 15 minutes to complete. It is recommended to perform it once every 1-2 years and operate it under full capacity (air traffic control may cause diagnostic abnormalities).

(2) Operation process

Parameter setting: Enter "Device setup ► Diag/Service ► Verification" through the display unit or communication tool, and set "Mode" (No flow/Flow) and "Execute" (execute/not execute).

Result judgment: After diagnosis, check the "Result", "Passed" is normal, and "Failed" needs to be checked according to the manual flowchart (if the magnetic circuit is abnormal, check the grounding, and if the wiring is abnormal, rewire); Cancelled "may be caused by alarms (such as air traffic control, signal overflow) or flow noise, and the alarm needs to be resolved first.


Troubleshooting

The manual provides troubleshooting flowcharts for three types of core faults, with the following key steps:

1. No display

First, confirm if there are any error prompts (through display or communication tools). If there are no errors, check if the sensor arrow is consistent with the flow direction (can be reinstalled or set with reverse flow parameters), if the sensor is full, and if the electrode adhesion detection function is enabled (wait for 4 minutes after enabling).

If the electrode resistance is greater than 4M Ω, the sensor needs to be removed to clean the electrode/grounding ring of foreign objects; If the verification function is still abnormal, the insulation resistance needs to be checked. If it is invalid, contact Yokogawa.

2. Zero point instability

Priority should be given to confirming that the pipeline is full, free of bubbles, and has no leaks; Check the grounding (the grounding ring is not corroded, the grounding wire is not broken), and perform the no current state verification function.

The conductivity of the fluid must meet the specifications (if unstable, control the temperature/flow rate); Equipment close to motors, transformers, etc. needs to be shielded or kept away from interference sources.

3. The displayed traffic does not match the actual amount

Check whether the parameters (instrument coefficient, caliber, etc.) are correct, whether the pipe is full, and whether the zero adjustment is performed in a no flow state; The signal cable needs to be insulated (to avoid contact between the shielding layer and the conductor).

The upstream straight pipe section must meet the installation requirements (refer to the installation manual); Insufficient conductivity or fluid fouling require cleaning of electrodes/liners. If ineffective, check insulation resistance or use a calibrator to determine transmitter/sensor failure.

image.png

  • Metso A413177 Digital Interface Control Module
  • METSO A413222 8-Channel Isolated Temperature Input Module
  • Metso A413313 Interface Control Module
  • METSO D100532 Control System Module
  • METSO A413310 8-Channel Digital Output Module
  • METSO A413659 Automation Control Module
  • Metso D100314 Process Control Interface Module
  • METSO A413665 8-Channel Analog Output Module
  • METSO A413654 Automation Control Module
  • Metso A413325 Interface Control Module
  • METSO A413110 8-Channel Analog Input Module
  • METSO A413144 Automation Control Module
  • Metso A413160 Digital Interface Control Module
  • METSO A413152 8-Channel Digital Input Module
  • METSO A413240A Automation Control Module
  • METSO A413146 Digital Interface Control Module
  • METSO A413150 Multi-Role Industrial Automation Module
  • METSO A413125 Automation Control / I/O Module
  • Metso A413111 Interface Control Module
  • METSO A413140 Automation Control Module
  • METSO 020A0082 Pneumatic Control Valve Component
  • METSO 02VA0093 Automation Control Module
  • METSO 02VA0153 Actuator Control Module
  • METSO 02VA0190 Automation Control Module
  • Metso 02VA0193 Pneumatic Control Valve Component
  • METSO 02VA0175 Valve Actuator Module
  • METSO D100308 Industrial Control Module
  • MOOG QAIO2/2-AV D137-001-011 Analog Input/Output Module
  • MOOG D136-002-002 Servo Drive or Control Module
  • MOOG D136-002-005 Servo Drive Control Module
  • MOOG D136E001-001 Servo Control Card Module
  • MOOG M128-010-A001B Servo Control Module Variant
  • MOOG G123-825-001 Servo Control Module
  • MOOG D136-001-008a Servo Control Card Module
  • MOOG M128-010 Servo Control Module
  • MOOG T161-902A-00-B4-2-2A Servo-Proportional Control Module
  • MOTOROLA 21255-1 Electronic Component Module
  • MOTOROLA 12967-1 / 13000C Component Assembly
  • MOTOROLA 01-W3914B Industrial Control Module
  • Motorola MVME2604-4351 PowerPC VMEbus Single Board Computer
  • MOTOROLA MVME162-513A VMEbus Embedded Computer Board
  • MOTOROLA MPC2004 Embedded PowerPC Processor
  • Motorola MVME6100 VMEbus Single Board Computer
  • MOTOROLA MVME162PA-344E VMEbus Embedded Computer Board
  • MOTOROLA RSG2PMC RSG2PMCF-NK2 PMC Expansion Module
  • Motorola APM-420A Analog Power Monitoring Module
  • MOTOROLA 0188679 0190530 Component Pair
  • Motorola 188987-008R 188987-008R001 Power Control Module
  • MOTOROLA DB1-1 DB1-FALCON Control Interface Module
  • MOTOROLA AET-3047 Antenna Module
  • Motorola MVME2604761 PowerPC VMEbus Single Board Computer
  • MOTOROLA MVME761-001 VMEbus Single Board Computer
  • MOTOROLA 84-W8865B01B Electronic System Module
  • Motorola MVIP301 Digital Telephony Interface Module
  • MOTOROLA 84-W8973B01A Industrial Control Module
  • MOTOROLA MVME2431 VMEbus Embedded Computer Board
  • MOTOROLA MVME172PA-652SE VMEbus Single Board Computer
  • Motorola MVME162-223 VMEbus Single Board Computer
  • MOTOROLA BOARD 466023 Electronic Circuit Board
  • Motorola MVME333-2 6-Channel Serial Communication Controller
  • MOTOROLA 01-W3324F Industrial Control Module
  • MOTOROLA MVME335 VMEbus Embedded Computer Board
  • Motorola MVME147SRF VMEbus Single Board Computer
  • MOTOROLA MVME705B VMEbus Single Board Computer
  • MOTOROLA MVME712A/AM VMEbus Embedded Computer Board
  • MOTOROLA MVME715P VMEbus Single Board Computer
  • Motorola MVME172-533 VMEbus Single Board Computer
  • Motorola TMCP700 W33378F Control Processor Module
  • MOTOROLA MVME188A VMEbus Embedded Computer Board
  • Motorola MVME712/M VME Transition Module
  • Motorola 30-W2960B01A Industrial Processor Control Module
  • MOTOROLA FAB 0340-1049 Electronic Module
  • Motorola MVME162-210 VME Single Board Computer
  • Motorola MVME300 VMEbus GPIB IEEE-488 Interface Controller
  • MOTOROLA CPCI-6020TM CompactPCI Processor Board
  • Motorola MVME162-522A VMEbus Single Board Computer
  • MOTOROLA MVME162-512A VMEbus Single Board Computer
  • MOTOROLA MVME162-522A 01-W3960B/61C VMEbus Single Board Computer
  • MOTOROLA MVME162-220 VMEbus Embedded Computer Board
  • Motorola MVME162-13 VMEbus Single Board Computer
  • MOTOROLA MVME162-10 VMEbus Single Board Computer
  • RELIANCE 57C330C AutoMax Network Interface Module
  • RELIANCE 6MDBN-012102 Drive System Module
  • RELIANCE 0-60067-1 Industrial Drive Control Module
  • Reliance Electric 0-60067-A AutoMax Communication Module
  • RELIANCE S0-60065 System Control Module
  • RELIANCE S-D4006-F Industrial Drive Control Module
  • Reliance Electric S-D4011-E Shark I/O Analog Input Module
  • RELIANCE S-D4009-D Drive Control Module
  • RELIANCE S-D4043 Drive Control Module
  • Reliance DSA-MTR60D Digital Servo Motor Interface Module
  • RELIANCE 0-60063-2 Industrial Drive Control Module
  • RELIANCE S-D4041 Industrial Control Module
  • Reliance Electric SR3000 2SR40700 Power Module
  • RELIANCE VZ7000 UVZ701E Variable Frequency Drive Module
  • RELIANCE VZ3000G UVZC3455G Drive System Module
  • Reliance Electric S-D4039 Remote I/O Head Module
  • RELIANCE 0-57210-31 Industrial Drive Control Module
  • RELIANCE 0-56942-1-CA Control System Module
  • Reliance Electric 0-57100 AutoMax Power Supply Module
  • RELIANCE 0-54341-21 Industrial Control Module
  • RELIANCE 0-52712 800756-21B Drive Interface Board
  • KEBA PS242 - Power Supply Module
  • KEBA BL460A - Bus Coupling Module
  • KEBA K2-400 OF457/A Operating Panel
  • KEBA T200-M0A-Z20S7 Panel PC
  • KEBA K2-700 AMT9535 Touch Screen Panel
  • KEBA T20e-r00-Am0-C Handheld Terminal
  • KEBA OP350-LD/J-600 Operating Panel
  • KEBA 3HAC028357-001 DSQC 679 IRC5 Teach Pendant
  • KEBA E-32-KIGIN Digital Input Card
  • KEBA FP005 Front Panel
  • KEBA BT081 2064A-0 Module
  • KEBA FP-005-LC / FP-004-LC Front Panel
  • KEBA SI232 Serial Interface
  • KEBA T70-M00-AA0-LE KeTop Teach Pendant
  • KEBA KEMRO-BUS-8 Bus Module
  • KEBA IT-10095 Interface Terminal
  • KEBA RFG-150AWT Power Supply Unit
  • KEBA C55-200-BU0-W Control Unit
  • KEBA Tt100-MV1 Temperature Module
  • KEBA E-HSI-RS232 D1714C / D1714B Interface Module
  • KEBA E-HSI-CL D1713D Interface Module
  • KEBA D1321F-1 Input Module
  • KEBA E-32-D Digital Input Card
  • KEBA C5 DM570 Digital Module
  • KEBA XE020 71088 Module
  • KEBA E-16-DIGOUT Digital Output Card