Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Anybus X-gateway Configuration Manual

来源: | 作者:FAN | 发布时间 :2026-05-07 | 14 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

The output data of the upper layer network (network → gateway) includes: control words (2 bytes)+application output data

The upper layer network input data (gateway → network) includes: status word (2 bytes)+application input data

The same applies to the lower level network

The gateway automatically forwards the output data of the upper layer application to the input data of the lower layer application, and vice versa. Control words/status words are used for operational control and status feedback between networks.

In the master slave configuration (such as PROFIBUS DP master in the upper layer and Modbus RTU slave in the lower layer), an additional Live List will be provided. This list is a 64 bit (8-byte) bitmap, with each bit corresponding to a slave node number (1-64). Bit=1 indicates that the slave is active, 0 indicates inactive or offline. This is very practical for the upper system to monitor the status of on-site equipment.


Status and Diagnostic System

4.1 Status Word

The status word is an important means for X-gateway to provide feedback on its own diagnostic information to the upper system. It is disabled by default and needs to be separately enabled for each network interface in the configuration interface. The length of the status word is 16 bits, and its meanings are as follows:

Name Description

The 15-12 gateway cycle counter successfully completes a bidirectional data exchange each time, and the counter increments by 1 (0-15 cycle)

The 11-8 universal error counter increments by 1 every time the gateway data exchange cycle exceeds 100ms

7-5 reserved -

4-3 main station mode (if applicable) indicates the current operating mode of the other main station (such as stop/run/clear, etc.)

2 initialization flag 1=The other network interface has been successfully initialized; 0=Initialization failed

1-0 operating status 1=the other side of the network is online/running; 0=The other network is offline/not running

By reading the status word, the upper system can real-time understand the health status of the opposite network and promptly detect issues such as initialization failure or communication timeout.

4.2 Control Word

The control word allows the upper system to manipulate the behavior of the gateway or the main station on the other side through one side of the network. By default, it is turned off and needs to be manually turned on. The control word length is 16 bits, where:

Bit 0 (LSB): Reset bit. When the bit is 1, the gateway will immediately restart and reinitialize the network interfaces on both sides. Usually used for remote fault recovery.

Bit 1-15: Master station mode control bit (only valid when the opposite side is the master station interface). The exact definition depends on the specific fieldbus, but the general rule is that if the control word is enabled, a valid value must be specified for these bits before the gateway can begin exchanging data. For example, for PROFIBUS DP master stations, it is usually necessary to set the mode to 'run' in order to initiate periodic data exchange.

4.3 Live List of Activity Sites

Only available when one side of the gateway is configured as the main station interface. After opening the Live List, the main station will forward the currently recognized activity status of its slave stations in bitmap form to the other network every cycle. This bitmap has a total of 64 bits and occupies 8 bytes. Bit 0 corresponds to node 1, and bit 63 corresponds to node 64 (node 0 usually represents the main station itself and is not included).

Notes:

Even if the master station supports more than 64 slave stations, the Live List only reflects the status of nodes 1-64.

The EtherNet/IP scanner interface does not provide a Live List, but can provide statistical information on configured connections, active connections, and incorrect connections. Please refer to the corresponding supplementary manual for details.


Error handling strategy

When one network side experiences offline or communication interruption, the gateway allows users to customize how the other network responds. This setting is completed through the Offline option in the configuration menu, which has two options:

Clear: Clear the data from the offline network direction and send it to the other side. For example, if the upper layer PROFIBUS network is offline, the gateway will output all 0 values to the lower layer Modbus. This can avoid executing old data, but may cause the device to stop.

Freeze: Keep the last received valid data unchanged and continuously forward it to the other side. Suitable for scenarios where the device is expected to maintain its current position or state, such as keeping a valve open.

In addition, for the scenario of connection loss for TCP/IP transport providers (such as HMS Transport Provider used by some configuration tools), Reboot after disconnection can also be set:

Enabled: Once the connection is lost, the gateway will automatically restart.

Disabled: Do not restart.

Configure the terminal through serial port for advanced settings

6.1 Enter the main menu

After correctly connecting the NULL modem cable and opening the terminal software (such as HyperTerminal, set 57600-8-N-1), power on the gateway. During the startup process, a series of self check messages will be displayed, and finally:

  • Siemens 6AG1214-1AG40-4XB0 PLC
  • OMRON CJ1W-AD081-V1 Analog Unit
  • OMRON C500-CPU11-E PLC CPU
  • OMRON NX-ECC201 EtherCAT Coupler
  • OMRON F300-A20S Camera Interface
  • Mitsubishi 80173-109-01 PLC Module
  • Fanuc A16B-2200-0141 PCB Board
  • Lenze EPL10200 PLC Module
  • OMRON CJ1M-CPU13 PLC CPU Unit
  • Yaskawa SGMPH-04AAA61D-OY Motor
  • OMRON NX-SOD400 Safety Output
  • Control Techniques V1800 Flux Vector Drive
  • Yaskawa SGDH-04AE-OY Servo Drive
  • OMRON NT-DRT21 DeviceNet Interface
  • OMRON C500-RM001-V1 Remote I/O Master
  • OMRON C500-AD006 Analog Input Module
  • OMRON 3G3MV-A4055 Inverter Drive
  • OMRON F150-C15E-3 Vision Mate Controller
  • OMRON CS1G-CPU44H PLC CPU
  • GE Fanuc DS6800CCIE1E1D CPU Module
  • Omron CP1L-M30DR-A PLC CP1W-CIF01 CPU Unit
  • Heraeus 585923 2M130 M8 Electrode Assembly Sensor
  • Omron C40P-EDT1-D C Series PLC Controller
  • Yaskawa SGMGH-09DCA6F-OY Servo Motor SGDH Driver
  • Datalogic SG-BWS-T4-MT Safety Control Unit Category 4
  • Pro-face PFXLM4301TADDC HMI Controller LT-4301M
  • Mitsubishi FX1N-60MR-DS PLC Main Unit 60 I/O
  • Omron NJ501-1320 Sysmac Database Connection CPU
  • Omron CJ1W-ETN21 Ethernet Unit CJ Series Module
  • Siemens 6ES7517-3AP00-0AB0 CPU 1517-3 PN/DP
  • Pasaban MTC-3052 Fast I/O PLC Module
  • Mitsubishi FX3U-128MR/ES-A PLC
  • OMRON CS1W-CLK21 Controller Link Unit
  • Yokogawa ADV151-E63 Digital Input Module
  • Allen Bradley MPL-B680B-M-X227 Motor
  • OMRON CJ1W-NC413 4-Axis Position Unit
  • Yaskawa SGMGH-30DCA6H-OY Servo Motor
  • Bosch 1070075337-101 Output Card
  • OMRON CQM1-CPU45-EV1 PLC CPU Unit
  • Siemens 6SE7090-0XX84-0AG1 CU3 Control Module
  • OMRON CQM1-TC101 Temperature Control Module
  • MOOG OEM-1030-422 Wind Energy PLC Controller
  • OMRON ZFX-C15 Vision Sensor
  • Square D 8702SCO2V02 Reversing Contactor
  • OMRON C20-LK201-EV1 PLC Link Adapter
  • OMRON NB7W-TW01B HMI PLC
  • Siemens 7ME6920-1AA10-1AA0 Flow Transmitter
  • Allen Bradley 1791-8BR Block I/O Module
  • OMRON CQM1-AD041 Analog Input Module
  • OMRON CJ1M-CPU21 PLC Module
  • Omron Z500-MC10E-001 Laser Profile Controller
  • Omron NA5-7W001B-V1 NA Series Programmable Terminal HMI
  • Allen-Bradley 1606-XLS960EE Power Supply 960W 24VDC
  • GE DS3800NEPB1F1E Power Excitation Board Mark IV
  • Yaskawa SGDH-04AE-OY Sigma-II Servo Drive 400W
  • Allen-Bradley 2711P-RBT7 PanelView Plus 7 Bezel
  • CCS PD3-3024-3-EI Digital Control Unit 3 Channel
  • Yaskawa CPU301 MP3300 Controller JAPMC-CP3301-2-E
  • Omron C40P-EDR-D PLC C Series P Type Controller
  • Omron NX-SID800 Safety Input Unit 8 PNP 24VDC
  • ABB SCC-C 23070-0-10232110 gas cooler
  • Sick LGTN101-521 CPU Module
  • Okuma 1911-2836 PLC Circuit Board
  • Mitsubishi Melsec PM-120M PLC
  • Omron F210-C15 Vision Mate Controller System
  • Siemens 7ML5110-1GD07-4AF3 Ultrasonic Level Gauge
  • ABB Pluto S46 V2 Safety Relay
  • Omron Z3RN-5A Optical Serial Link
  • Omron R7D-APA3H 30W Servo Drive
  • Giddings Lewis 502-03638-41R3 PLC Processor
  • Omron SCY-P1 Sequencer Controller
  • Siemens C98043-A7002-L1-13 PCB Board
  • SACS TECNICA Palletizer PC PLC Control System
  • AutomationDirect T1F-14THM PLC Module T1F14THM
  • OMRON C200H-AD003 Analog Input Unit PLC Module
  • Applied Materials 0010-A0000 Electricity Box PLC 200mm
  • ABB RVT-6 Power Factor Controller RVT6
  • Allen-Bradley 2094-BC01-MP5-M Kinetix 6000 Axis Module
  • OMRON FQM1S-MC233 Motion Controller PLC Module
  • OMRON C200H-SNT31 PLC Special I-O Module
  • Yaskawa SGMPH-04AAA61D-OY Servo Motor 400W 200V
  • Yaskawa SGMGH-09DCA6F-OY AC Servo Motor 850W 400V
  • REFU ELEKTRONIK SR17002 PLC Logic Module Circuit Board
  • Siemens 6DP1231-7AA PLC Board Module Industrial Control
  • ABB SACE ISOMAX S3 N 160 Molded Case Circuit Breaker
  • OMRON C120-SC024-V1 SYSMAC C120 Compact PLC Unit
  • OMRON CJ1W-SCU41-V1 Serial Communication Unit PLC Module
  • OMRON 3G3MX2-A4110-ZV1 MX2 Variable Frequency Drive
  • Yaskawa SGDH-04AE-OY Sigma-II Servo Driver 400W 200V
  • OMRON CQM1-AD041 Analog Input Module PLC I/O Unit
  • Delta Omega XML2-0060-45-4/S-A Servo Drive
  • Omron CJ1W-AD041 Analog Input
  • Omron CJ1W-NC271 Position Control Unit
  • Omron CJ1G-CPU45H PLC CPU
  • Omron CJ1W-EIP21 EtherNet/IP Unit
  • Omron F210-C15 Vision Mate Controller
  • Omron CQM1H-ADB21 Analog I/O Board
  • Omron GRT1-PRT PROFIBUS DP-V1 Adapter
  • Omron CP1H-Y20DT-D PLC CPU
  • TE.CO TFX 4G 1.5 Grey Cable 470m
  • Yaskawa SGDH-04AE-OY Servo Driver 400W 200V
  • OMRON CJ1H-CPU66H V4.0 PLC CPU
  • OMRON R7M-A10030-BS1 Servo Motor 200W 100V
  • OMRON FQM1-MMA21 Motion Controller
  • Yaskawa SJDE-08APA Servo Amplifier
  • OMRON CQM1-AD041 Analog Input Unit
  • Siemens OCI55 Dialogue Module Landis
  • OMRON F350-C10E Image Processing Unit
  • OMRON NT10S-SF121 HMI Terminal
  • SIEMENS 3RB1262-0LB31 Overload Relay
  • OMRON YASKAWA SGDS-02A12A Servo Drive
  • TE.CO TFX 4G 1.5 Grey Cable ST 500m
  • FANUC A16B-3200-0362 PCB Control Board
  • OMRON CQM1-ARM21 Analog Output Unit
  • Allen-Bradley 1788-EN2DN Ethernet DeviceNet Gateway
  • Siemens 3VL9440-7EE40 3VL4740-2AA46-0AA0 Circuit Breaker
  • OMRON CJ1W-AD041-V1 Analog Input Unit
  • OMRON CQM1-AD041 CQM1-IPS02 Analog Input Power Supply
  • Texas Instruments System 505 PLC 525-110 525-1102
  • OMRON CQM1-AD042 Analog Input Unit
  • Yaskawa SGDH-04AE-OY Servo Driver 200V 400W
  • CTI 2512 75W Power Supply for CTI 2500
  • Omron F300-B5 Image Processing Unit
  • Mitsubishi 15050-PR01A PLC Board
  • Omron CQM1-TC101 Temperature Controller
  • SCE M68-2000 2 Axis Motion Controller HW 2.3/B
  • Omron 3Z4SP-C22 Visual Positioning Sensor
  • Omron 3G3SV-BB007-E 0.75kW VFD