Introduction
The Woodward DSLC-2 digital synchronizer and load control is an advanced microcomputer control device designed specifically for three-phase AC generators, integrating multiple functions such as synchronization control, load sensing, load distribution, dead bus closure, reactive power/power factor control, and process control. This article is based on Woodward's official 37443J technical manual (software version 1.15xx), providing a comprehensive analysis of the core functions, technical features, installation configuration, and operational applications of the device. The aim is to provide engineers, technicians, and operations personnel with a detailed reference guide.
1、 Product Overview and Core Features
1.1 Product positioning
DSLC-2 is a direct upgrade product of Woodward's classic DSLC series, suitable for various grid connected or islanded operating generator sets. Its design supports parallel operation and control of up to 32 generator sets, achieving seamless communication between DSLC-2 and MSLC-2 (main station load control unit) through a dedicated Ethernet system.
1.2 Main functional modules
Synchronizer function:
Supports two modes: phase matching or slip frequency synchronization.
Capable of automatic dead bus closure, conducting locking negotiation through communication network to prevent multiple devices from closing simultaneously.
Integrated voltage matching, automatic reclosing, automatic resynchronization, and synchronization timeout alarm functions.
Load control function:
Support droop control, base load control, and equal power load distribution mode.
Provide adjustable ramp loading/unloading to achieve disturbance free switching.
Integrated reverse power protection, load switch, and frequency fine-tuning functions.
Process control function:
Cascade PID process controller, suitable for applications such as cogeneration, inlet/outlet control, pressure or liquid level control, etc.
Supports analog input (process signal) and internal digital reference, and can be remotely set.
Reactive power/power factor control function:
Control the reactive power or power factor of the generator in the grid connected system.
Support reactive power sharing (during islanding operation) and voltage fine-tuning function.
Provide voltage range alarm and high/low limit protection.
Communication and network functions:
Equipped with dual Ethernet ports (network A and B), supporting redundant communication.
Network A is dedicated to DSLC-2/MSLC-2 internal communication (UDP protocol).
Network B supports Modbus TCP/IP for communication with the upper computer (PLC/DCS).
Additionally, RS-485 interface is provided to support Modbus RTU protocol.
2、 System architecture and installation points
2.1 Hardware Installation
Dimensions: 227 mm × 250 mm × 84 mm, using panel installation method.
Environmental requirements: The working temperature range is -40 ° C to+70 ° C, and direct exposure to water sources, condensation environments, and strong electromagnetic interference should be avoided.
Power requirement: 12/24 VDC (range 8-40 VDC), it is recommended to use slow melting fuses (6A) or miniature circuit breakers for protection.
Grounding protection: It is necessary to connect a protective earth wire (PE) with a wire diameter of not less than 2.5 mm ².
2.2 Wiring specifications
Voltage measurement:
Generator voltage measurement supports 3-phase 4-wire (with neutral point), 3-phase 3-wire, and 3-phase 4-wire open delta connections.
Bus voltage measurement supports 1-phase 2-wire (phase to phase or phase to neutral point) and 3-phase measurement of auxiliary bus.
Attention: 120V and 480V input terminals cannot be used simultaneously, and the correct terminals should be configured according to the rated voltage of the PT secondary side.
Current measurement:
Support three-phase or single-phase current transformer input, ensuring that one end of the CT secondary side is grounded.
When wiring, attention should be paid to the power measurement direction and display symbol (positive for power generation, negative for reverse power).
Discrete input:
Supports positive or negative polarity signals, but all inputs must be of the same polarity.
The input functions include: operation, circuit breaker assistance, voltage rise/fall, load rise/fall, base load, unloading, process control, ramp pause, and section number selection.
Relay output:
There are a total of 12 relay outputs, including alarm, load switch, high and low limit, circuit breaker opening and closing, and voltage rise/fall.
The output contact capacity is 250VAC/DC, 2A.
Analog input/output:
Provide 3 analog inputs (remote load reference, process signal, reactive load).
2-channel analog output (speed bias, voltage bias), supporting multiple signal types such as 0-20mA, 4-20mA, 0-10V, etc., can be configured as voltage or PWM output through jumper wires.
2.3 Communication Interface
RS-232: Used to connect Woodward ToolKit configuration software.
RS-485: Supports Modbus RTU half duplex or full duplex communication.
Ethernet (RJ-45): Network A (UDP+Modbus TCP), Network B (Modbus TCP, optional redundant UDP).
The communication protocol supports Woodward Private Protocol (ServLink) and standard Modbus.

3、 Detailed explanation of software configuration and parameters
3.1 Configuration Tool - Woodward ToolKit
Version requirement: V6.4.1 or higher version is required.
Connection method: It can be connected through RS-232 serial port or Ethernet (recommended network A).
Function: Provides visual monitoring, parameter configuration, trend recording, diagnosis, and firmware management functions.
3.2 Analysis of Key Parameter Menu
3.2.1 Synchronizer Configuration (Menu 1)
Synchronization mode: optional shutdown, synchronization, allow, check, run, automatic shutdown, etc.
Phase matching/slip frequency: Users can choose according to their application requirements.
Dead bus closure: After activation, the device automatically detects the dead bus and negotiates closure permissions.
Phase angle compensation: configurable ± 180 ° compensation value, used to correct phase deviation caused by transformer wiring.
3.2.2 Load Control (Menu 2)
Frequency control mode: PID analog control, three position controller or off.
Load control modes: droop, base load, load distribution, process control, etc.
Slope rate: The loading, unloading, and lifting/lowering reference rates can be independently configured.
Load allocation gain: Adjust the response speed and stability of load allocation.
3.2.3 Process Control (Menu 3)
PID parameters: Proportional, integral, and derivative gains are adjustable.
Process reference source: internal settings or remote analog input.
High and low limit alarm: It can set the high and low limit values of the process signal and enable the alarm.
3.2.4 Reactive Power/Power Factor Control (Menu 4)
Control mode: reactive power control, power factor control, or shutdown.
Voltage control mode: PID analog control or three position controller.
Reactive power allocation gain: Adjust the reactive power allocation performance when multiple machines are connected in parallel.
3.2.5 System Configuration (Menu 5)
Equipment number: 1-32, must be unique.
Segment number configuration: Supports 8 bus segments, which can be input through discrete quantities or automatically recognized.
PT/CT parameters: The transformer ratio must be accurately set to ensure measurement accuracy.
Communication mode: Single network or redundant Ethernet mode.
3.2.6 Analog Input/Output (Menu 6)
Input signal type: optional current and voltage signals, supporting linear calibration.
Output signal range: Multiple standard signal ranges or custom ranges can be configured.
Filter constant: Optional filtering level, smooth output signal.
3.2.7 System Management (Menu 5.2)
Password protection: Supports 5 levels of access permissions (user, service, temporary debugging, debugging, super debugging).
Factory settings recovery: default parameters can be restored through password protection.
Indicator light test: One click test of the front panel LED status.
4、 Advanced features and application scenarios
4.1 Parallel connection and segmented control of multiple units
DSLC-2 supports up to 32 units+16 MSLC-2 to form a complex power grid.
Segmented operation: By using discrete inputs (DI13-DI20) to identify the status of bus segments, independent or parallel operation between different segments can be achieved.
Load distribution: During islanding operation, precise allocation of active and reactive power is achieved through Ethernet communication.
4.2 Redundant Communication and System Reliability
Dual network redundancy: Networks A and B can be configured in redundancy mode to improve communication reliability.
Lost member detection: When communication between devices in the network is interrupted, the system automatically switches to droop mode to avoid losing control.
System update function: Network devices can be re identified and reconfigured through parameter or discrete input triggering.
4.3 Safety and Protection Functions
Electronic electrostatic protection: All electronic components are sensitive to static electricity and must strictly comply with ESD protection regulations.
Alarm and protection: Provide multiple alarms and protections for frequency, voltage, load, process, reverse power, etc.
Security Warning:
The prime mover must be equipped with an overspeed (over temperature/over pressure) shutdown device independent of the control system.
It is prohibited to use or modify the equipment beyond the prescribed scope, otherwise it may result in personal injury, property damage, and warranty failure.
5、 Maintenance and Diagnosis
5.1 Daily Maintenance
Regular inspection: wiring tightness, power supply voltage, communication status.
Software update: Check and update device firmware through ToolKit (requires authorized personnel to operate).
Counter management: It can record the operating hours and active/reactive energy of the generator, and supports manual reset and preset.
5.2 Fault diagnosis
ToolKit diagnostic page: provides real-time status monitoring, alarm recording, communication status, and device overview.
LED indication:
Synchronization Enable LED: Green indicates readiness for synchronization, red indicates voltage frequency window not met.
CPU normal "LED: Green indicates device ready, red indicates fault, flashing indicates system update.
Communication diagnosis: can detect network A/B errors, device mismatches, phase rotation mismatches, etc.
