Check that the number of DSLCs in the activity matches the number of installations
Set the load distribution gain to 0.72
Verify load distribution performance
4.3 Process Control Adjustment
Set process control gain, stability, derivative, dead zone, and filter parameters
Select direct or indirect control actions based on process characteristics
Set process reference values
Adjust dynamic parameters to achieve stable process control
Set process high and low limit values and alarm functions
4.4 Reactive Power/Power Factor Control Adjustment
Verify that voltage matching adjustment has been completed
Set reactive power/power factor gain and stability parameters
Set rated reactive power and reference value
Adjust and control dynamic parameters
Set power factor dead zone to reduce response to minor changes
Enable voltage fine-tuning function (if necessary)

5、 Network Communication and Remote Monitoring
5.1 LonWorks Network Configuration
The DSLC control system uses Echelon's LonWorks technology for inter device communication, supporting load distribution, reactive power/power factor distribution, and dead bus closure permission management.
Network specifications:
Data rate: 1.25 Mbps
Network isolation: 1000Vrms (60 seconds) at 60Hz, 277Vrms (continuous)
Common mode range: 277Vrms
Electrostatic discharge: 15kV
Maximum number of nodes per bus: 64 (0 to+70 ° C), 32 (-20 to+85 ° C), 20 (-40 to+85 ° C)
Network bus length: 500m (-20 to+85 ° C), 150m (-40 to+85 ° C)
Maximum stub length: 300mm (-40 to+85 ° C), 600mm (0 to+70 ° C)
Network terminal: Terminals need to be installed on both ends of the network
Wiring requirements:
Use the recommended shielded twisted pair cable
Ensure that the bus length is less than 500m
The length of the stub is less than 300mm
Less than 32 network devices
Minimize exposed wires outside the shielding layer
Verify the shielding continuity of the entire network
Grounding shielding layer at the center position
Install terminals only on both ends of the network
Avoid wiring together with power cords or other high electrical noise circuits
5.2 Remote monitoring function
The DSLC control system provides complete remote monitoring functions through the LonWorks network, including:
Electrical parameter output:
Real time data such as voltage, current, power, and power factor are provided through three data structures (ELEC-PARAOUT1, OUT2, OUT3) with an update rate of 1 second.
Remote control input:
Net_demote_in: Network remote load or process control reference input
Net_decess_in: Network input from LonWorks compatible process transmitters
Net_iscrete_in: Network input from remote sequencer
Discrete input/output states:
The status of all switch inputs and relay outputs can be monitored through the network.
6、 Troubleshooting and Maintenance
6.1 Common problem diagnosis
Unit unable to power on:
Check the+24V power supply
Ensure the correct polarity of the power supply
Check if the software PROM is installed correctly
Unstable load control:
Check phase current and voltage calibration
Adjust the rated speed of the speed control unit
Change the load control mode
Unstable process control mode:
Ensure that the load control is set to proportional control
Dynamically adjust the process control again
Unstable reactive power/power factor control mode:
Dynamically adjust reactive power/power factor control again
Remove cross current compensation from the voltage regulator circuit
Incorrect load allocation during waiting:
Check if the rated load setting is correct
Adjust the rated speed of the speed control unit
6.2 Network Troubleshooting
The number of DSLCs in the activity is incorrect:
Check if all DSLC controlled network addresses are unique
Verify whether the network cabling complies with specifications
Check the impact of each DSLC control on the network one by one
Network communication error:
Check if the network cabling installation complies with the specifications
Verify if the network is overloaded
Check if there are any equipment malfunctions affecting network communication
6.3 Service Options
Woodward offers a variety of product and service options:
OEM and packager support: Obtain services through original equipment manufacturers or device packagers
Woodward Business Partner Support: Obtain services through a global network of independent business partners
Factory repair options: including replacement/exchange, uniform rate repair, and uniform rate remanufacturing
Return to equipment maintenance:
Contact the full-service distributor in advance to obtain return authorization and shipping instructions
Attach a label containing complete information when transporting goods
Packaging control equipment according to specifications to prevent transportation damage
7、 Safety precautions
7.1 Warning and Notice
Important definition:
Danger: Indicates a dangerous situation that, if not avoided, may result in death or serious injury
Warning: Indicates a dangerous situation that, if not avoided, may result in death or serious injury
Attention: Indicates a dangerous situation, which may result in minor or moderate injury if not avoided
Notice: Indicates the potential danger of property damage
Important: Specify operation prompts or maintenance suggestions