Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Emerson DeltaV M Series Virtual I/O Module 2 (VIM2)

来源: | 作者:FAN | 发布时间 :2025-08-22 | 655 次浏览: | Share:


Emerson DeltaV M Series Virtual I/O Module 2 (VIM2)

Basic Overview

The DeltaV M Series Virtual I/O Module 2 (VIM2) is an industrial grade I/O simulation and integration device launched by Emerson Process Management. It has two core functions: one is to work with MYNAH Technologies' MiMiMiC simulation software to achieve non-invasive simulation of DeltaV M Series I/O cards and digital bus field devices, supporting comprehensive testing of control strategies and system configurations; The second is to serve as an integrated platform for high-speed Ethernet I/O devices, driven by Modbus TCP/IP or Ethernet/IP protocols, to achieve signal reading and writing between the DeltaV system and devices (such as PLCs, motor control centers, weighing instruments, etc.) in the factory Ethernet I/O network. Its design is compatible with the DeltaV system architecture and can be seamlessly integrated into existing control networks.


Core advantages

(1) Non invasive DeltaV I/O simulation capability

Comprehensive simulation support: It can perform non-invasive simulation on all DeltaV M-series I/O modules (including traditional I/O, Foundation fieldbus, Profibus DP, DeviceNet, ASi bus, and serial cards) without modifying control strategies to complete DeltaV configuration testing; Simultaneously supporting simulation of all DeltaV digital buses and Foundation fieldbus function blocks, it can verify the effectiveness of fieldbus control configuration.

Efficient simulation performance: A single controller can simulate up to 64 DeltaV I/O modules, with fast and efficient simulation execution speed, which can make the DeltaV controller mistakenly believe that it is communicating with real I/O, ensuring that the test results are close to the actual operating scenario; It also supports I/O automatic detection and precise testing of controller load, providing data support for system optimization.

Supporting simulation software: It needs to be used in conjunction with MYNAH's MiMiC simulation software (software needs to be purchased separately). This software can provide dynamic simulation function for DeltaV system software acceptance testing and operator training - through simulation I/O and on-site equipment, simulate the real reaction of the process to the control system output signal, and the simulation I/O driver updates are synchronized with the MiMiC software version and can be quickly upgraded through the simulation network.

(2) Powerful Ethernet I/O integration capability

High capacity device access: A single VIM2 can simulate 4 DeltaV serial cards, supporting 128 serial card datasets for 32 network devices in single-mode configuration and 16 devices in redundant configuration. Ethernet communication is efficient and stable, meeting the large-scale equipment integration requirements of factories.

Flexible network configuration: supports user-defined IP addresses and can adapt to almost all factory network architectures (requiring the same IP subnet as Ethernet I/O devices); Simultaneously supporting 1:1 redundant configuration - by adding a second VIM2 to form a redundant pair, simulating 4 pairs of redundant DeltaV serial cards, the main and backup cards automatically switch (consistent with the switching logic of DeltaV serial cards), and the operator can obtain switching notifications through the display interface or manually control the switching in DeltaV Diagnostics.

Multi protocol compatibility: Supports two mainstream industrial Ethernet protocols and adapts to different device types:

Modbus TCP/IP: As a master, it supports 9 types of function codes, including reading coil status (Code1) and writing multiple registers (Code16). It can function as both a master and slave (up to 32 slave stations or 16 master stations+16 slave stations are supported in single-mode mode; only the master station is supported in redundant mode, up to 16 slave stations are supported).

Ethernet/IP: As a scanner (initiator), it supports CIP protocol functions such as UCMM (connectionless) messages, Class 3 (connected) messages, and Class 1 (I/O) connections, and is compatible with the Ethernet/IP specifications defined by the Open DeviceNet Vendor Association.

(3) Usability and system compatibility

Seamless DeltaV Integration: The VIM2 is recognized by the DeltaV M series controller as four DeltaV serial cards. During debugging, serial dataset configuration can be completed through the DeltaV Explorer (consistent with conventional serial card configuration). Ethernet I/O signals can be directly used for the DeltaV control module, displayed on the DeltaV Operate graphical interface, or stored in the DeltaV historical database without the need for additional interface development.

Intuitive configuration tool: Comes with the VIMNet Explorer application (integrated with DeltaV v12 and above, or provided with MYNAH driver), supports "plug and play" configuration - completes VIM2 debugging, primary and backup redundancy settings, and Ethernet I/O network parameter configuration (such as IP address, subnet mask, gateway, device node address, etc.) through graphical drag and drop operations. It also supports driver firmware upgrades and type replacements (only supports loading one Ethernet I/O driver at a time).

Modular and flexible installation: Adopting the same installation method as the DeltaV controller, it can be installed in the controller slot of a 2-wide horizontal carrier or a 4-wide vertical carrier (located on the left side of the DeltaV controller), using standard DeltaV power supply. The design is durable and can operate stably for a long time.

Details of Function Implementation

(1) Implementation of I/O simulation function

Hardware coordination: The VIM2 hardware preloads the I/O simulation driver and communicates with the MiMiC software through the simulation network. After disconnecting the real I/O card from the control system, the MiMiC driver directly writes simulation signals to the I/O subsystem of the DeltaV controller.

Simulation data management: A single simulated process controller corresponds to one MiMiC dataset, and a MiMiMiC server can support up to 32 datasets (ports). Each dataset can accommodate 4000 MiMiMiC simulation labels, meeting the requirements of large-scale process simulation.

Technical Support: Technical support for I/O simulation drivers and MiMiC software is provided by MYNAH Technologies and requires separate contact with the supplier for service.

(2) Implementation of Ethernet I/O Integration Function

Drivers and configurations: Ethernet I/O drivers (such as Modbus TCP/IP master drivers, Ethernet/IP scanner drivers, etc.) need to be purchased separately from MYNAH. After loading the drivers, the DeltaV controller can automatically detect the debugged VIM2 (serial cards identified as slots 57-60 or 61-64 in single-mode configuration, and redundant pairs identified as slots 57-64 in redundant configuration).

Redundancy mechanism: The redundant VIM2 needs to be installed on independent 2-wide carriers, equipped with independent power supplies, and monitored for the status of the main and backup devices through dedicated redundant link cables (included in the redundancy kit) - the main VIM2 continuously communicates with industrial Ethernet devices, while the backup VIM2 sends intermittent signals to maintain communication integrity and ensure uninterrupted switching between the main and backup devices.

Configuration tool requirements: VIMNet Explorer needs to run on a workstation connected to the Ethernet I/O network (which can be a DeltaV workstation with a third network card or a non DeltaV workstation), support Windows XP/7 system, and complete connection configuration through the RJ45 Ethernet interface at the bottom of VIM2.

Hardware specifications

Category specific parameters

The power requirement is supplied by the DeltaV system power supply, supporting 2-wide horizontal carriers or 4-wide vertical carriers (single-mode configuration only)

Electrical protection built-in 3.0A non replaceable fuse, maximum current 750mA (5VDC)

Typical power consumption of 4.0W, maximum value of 5.4W

Storage and Size: User Memory 16MB; Size: 4.1cm (width) x 15.9cm (height) x 10.7cm (depth), Weight: 278g

Installation method: Install in the right slot (horizontal carrier) or vertical carrier of the power/controller carrier

Environmental parameters: Operating temperature: 0 ° C~60 ° C (32 ° F~140 ° F), Storage temperature: -40 ° C~85 ° C (-40 ° F~185 ° F); Relative humidity ranging from 5% to 95% (without condensation); The air pollutant level complies with ISA-S71.04-1985 G2 level; Shock resistance (normal operation): 10g half sine wave, continuous for 11ms; Vibration resistance (working limit): 1mm peak to peak value at 5Hz~16Hz, 0.5g at 16Hz~150Hz

LED indicator light - green (power): indicates connection to DC power supply

-Red (Error): Indicates the existence of an error status

-Green (Active): indicates that VIM2 has been debugged and is in an active state

-Green (Standby): Not used

-Yellow flashing (Network): indicates normal network communication

-Yellow flashing (Ctlr IO): indicates that DeltaV I/O bus communication is normal

-Alternating flashing (parity) except for the power light: device recognition triggered by the ping command on the user interface software

External Interface - Factory Ethernet: 1 10BaseT 8-pin RJ-45 connector

-Redundant link: 1 10BaseT 8-pin RJ-45 connector (redundant kit includes dedicated cable)

Ethernet I/O Capacity - Analog DeltaV Serial Card: 4

-Number of datasets: 128 per unit

-Number of device nodes: 32 single mode slave stations (or 16 master+16 slave stations), redundant 16 slave stations


DeltaV Authorization and Configuration Rules

DST counting rule: The DeltaV software authorization requirement (DST counting) for the VIM2 register is consistent with the serial card register - a single DeltaV serial card dataset can contain up to 100 values (Boolean, 8-bit/16 bit values), and if it is a floating-point or 32-bit value, it can contain up to 50 values; If a single dataset is referenced by only one module, it is counted as one DST; If referenced by multiple modules, the DST count is equal to the number of referenced modules.

DST type differentiation: The numerical count used to control the function block is "Control DST", and the numerical count used only for graphic display or historical data acquisition is SCADA value, not included in DST count.

Ordering and matching requirements

(1) VIM2 and redundant package

M-Series Virtual I/O Module 2 (Single Mode) VE4026 Single VIM2 Device, requires separate carrier and power supply

Redundant M-series Virtual I/O Module 2 VE4027 includes 2 VIM2 devices and 1 redundant link cable

(2) Supporting products that need to be purchased separately

MiMiC simulation software MYNAH Technologies is used for I/O simulation and requires the purchase of both MiMiC basic license and DeltaV Railbus driver package

Modbus TCP/IP Master Driver MYNAH Technologies for Ethernet I/O Integration (Modbus Protocol)

Ethernet/IP scanner driver MYNAH Technologies for Ethernet I/O integration (Ethernet/IP protocol)

Universal Ethernet/IP scanner driver MYNAH Technologies adapts to non-standard Ethernet/IP devices

(3) Installation and software prerequisites

Hardware support: Each VIM2 requires one power/controller carrier (refer to the M-series horizontal carrier data sheet) and one dedicated DeltaV system power supply (refer to the M-series power supply data sheet).

Software version: Supports DeltaV v10.3 and above, and recommends using DeltaV v12 and above (VIMNet Explorer tool provided with this version of software).

Technical Support: The VIM2 hardware is supported by Emerson, while the technical support for MiMiC simulation software and Ethernet I/O drivers is provided by MYNAH Technologies


  • RELIANCE 0-57170 Industrial Drive System Component
  • Reliance Electric S-D4030-A Remote I/O Head Module
  • RELIANCE 0-57406-E Industrial Control Module
  • RELIANCE 57401-2 Control Interface Module
  • RELIANCE 57421 Electrical Control Component
  • Reliance Electric 57401 Remote I/O Head Module
  • RELIANCE S-D4007 Industrial Control Module
  • ABB SACO16D1-AA Digital Annunciator Unit
  • RELIANCE 803.65.00 Control Board for Industrial Systems
  • Reliance Electric 57C404C AutoMax Processor Module
  • RELIANCE 0-57C411-2 Industrial Control Module
  • RELIANCE 0-57C408-B Heavy-Duty Industrial AC Motor
  • Reliance Electric 0-57C406-E AutoMax Power Supply Module
  • RELIANCE 0-57C407-4H Industrial Control Module
  • RELIANCE 0-57C405-C Industrial Duty AC Electric Motor
  • Reliance Electric 0-57C404-1E AutoMax Processor Module
  • RELIANCE 0-57C402-C Drive Control Module
  • RELIANCE 0-57C400-A High-Performance Industrial AC Motor
  • Reliance Electric 0-51378-25 Digital Interface Board
  • RELIANCE S-D4041B Drive Control Module
  • RELIANCE INSPECTOR VCIB-06 Vibration Calibration Instrument
  • Reliance Electric S-D4043C Remote I/O Head Module
  • RELIANCE S-D4012 Drive Control Module
  • Reliance Electric 805401-5R Printed Circuit Board
  • RELIANCE ELECTRIC 0-60029-1 Drive Control Module
  • REXROTH VT-HNC100-1-23/W-08-C-0 Digital Axis Control
  • REXROTH VT-HNC100-4-3X/P-I-00/G04 Digital Axis Controller
  • REXRTOH VEP40.3CEN-256NN-MAD-128-NN-FW Industrial Embedded PC
  • Rexroth 0608820116 ErgoSpin CC-AS300-070 Tightening Tool
  • REXROTH MHD093C-058-PG1-AA Synchronous Servo Motor
  • REXRTOH VT-HNC100-1-22/W-08-C-0 Industrial Touch Monitor
  • Rexroth MSK060C-0600-NN-S1-UP1-NNNN IndraDyn S Servo Motor
  • REXRTOH VT3024 Industrial Monitor
  • Rexroth MHD041B-144-PG1-UN Synchronous Servo Motor
  • Rexroth VT-HNC100-1-23/W-08-S-0 Digital Axis Control
  • Rexroth VT-HNC100-1-23/M-08-P-0 Controller
  • REXRTOH VT-HNC100-1-22/W-08-0-0 | Hydraulic Valve Block Assembly
  • Rexroth 4WE6Y62/EG24N9K4 + HSZ10-26916-AA/G24N9K4M01 Assembly
  • Rexroth MHD095C-058-NG1-RN Hydraulic Motor
  • Rexroth 4WE6Y62/EG24N9K4 + HSZ10-26916-AA/G24N9K4M01 Assembly
  • Rexroth SYHNC100-NIB-2X/W-24-P-D-E23-A012 Controller
  • REXRTOH BTV04.2GN-FW | Bus Terminal Valve with PROFINET
  • Rexroth BGR DKC02.3-LK SCK02/01 ECODRIVE3 Control Assembly
  • Rexroth MKD025B-144-KG1-UN Servo Motor
  • REXRTOH R901325866+R900775346+R901273425A | Drive System Component Set
  • Rexroth CSH01.1C-SE-EN2-NNN-NNN-NN-S-XP-FW Drive Controller
  • REXRTOH DDS2.1W200-D | Digital Servo Drive
  • Rexroth VT3002-2X/48F Card Holder for Proportional Amplifiers
  • Rexroth VDP40.2BIN-G4-PS-NN Proportional Valve
  • REXRTOH MSK070D-0450-NN-M1-UP1-NSNN Servo Motor
  • Rexroth MSK070C-0150-NN-S1-UG0-NNNN IndraDyn S Servo Motor
  • Rexroth MSK050C-0600-NN-M1-UP1-NSNN Servo Motor
  • Rexroth MSK030C-0900-NN-M1-UP1-NSNN Servo Motor
  • Rexroth TV 3000HT PUMF Hydraulic Pump Module
  • REXRTOH R911259395 | Drive System Control Module
  • Rexroth VT-VSPA1-1-11 Proportional Amplifier Card
  • Rexroth VT3006S35R1 Proportional Valve Module
  • REXRTOH VT3006S34R5 Hydraulic Valve | Directional Control Valve
  • Rexroth VT3000S34-R5 Proportional Amplifier Card
  • Rexroth SL36 Servo Motor Controller
  • REXRTOH SE200 0608830123 | Inductive Proximity Sensor
  • Rexroth RAC 2.2-200-460-A00-W1 Main Spindle Drive Controller
  • Rexroth PSM01.1-FW Power Supply Module
  • REXRTOH PIC-6115 | Programmable Industrial Controller
  • Rexroth MDD112D-N030-N2M-130GA0 Digital AC Servo Motor
  • Rexroth HDS03.2-W075N Drive Controller Module
  • REXRTOH DKC03.3-040-7-FW Servo Drive | Digital Motion Controller
  • Rexroth DKC02.3-200-7-FW ECODRIVE3 Servo Drive Controller
  • Rexroth CSB01.1N-AN-ENS Control System Module
  • REXRTOH 0608830222 | Genuine Automation Component
  • Rexroth 0608830174 ErgoSpin Tightening System Control Module
  • Rexroth 0608820103 Industrial Hydraulic Control Component
  • REXRTOH 0608820069 Industrial Automation Component
  • Rexroth 0608800048 ErgoSpin Tightening System Control Module
  • Rexroth 0608801006 Industrial Hydraulic Control Component
  • REXRTOH SYHNC100-NIB-24-P-D-E23-A012 Encoder | Synchronous Serial Interface
  • Rexroth 0608720040 ErgoSpin Tightening System Control Module
  • REXRTOH SYHNC100-NIB-2X/W-24-P-D-E23-A012 Controller
  • ABB CP555 1SBP260179R1001 HMI Operator Terminal
  • HIMA K9212 Fan Assembly | Safety System Cooling Unit
  • WATLOW CLS208 Digital Temperature Controller
  • Watlow CLS2163C1-110200000-CLS204204-C10000AA-CLS208208-C10000AE Multi-Loop PID Controllers
  • WATLOW PPC-TB50 Power Controller
  • WATLOW PPC-TB50 30280-00 Temperature Controller
  • Watlow NLS300-CIM316 Communication Interface Module
  • WATLOW MLS300 Limit Controller
  • WATLOW CAS 16CLS/CAS Temperature Controller
  • Watlow CAS200 CLS216 16-Loop Thermal Controller Module
  • WATLOW CLS208 C10000CP Power Controller
  • WATLOW ANAFAZE LLS200212 CLS208 Temperature Control System
  • Watlow ANAFZE PPC-TB50 CLS208 Multi-Loop Controller
  • WATLOW ANAFZE 997D-11CC-JURG Power Controller
  • WATLOW ANAFAZE PPC-TB50 Temperature Controller
  • ABB SUE3000 1VCF750090R0804 High-Speed Transfer Device
  • ABB TET106 11355-0-6050000 Temperature Module
  • ABB PPD512 A10-15000 Power Panel Display
  • ABB PPD113B01 3BHE023784R1023 AC 800PEC Control Module
  • ABB PFEA113-65 Tension Controller 3BSE050092R65
  • ABB PFEA112-20 3BSE050091R20 Fieldbus Adapter Module
  • ABB PFEA111-65 3BSE050091R65 Tension Electronics PFEA111
  • ABB PFEA111-65 Tension Controller 3BSE050090R65
  • ABB PDD500A101 Operator Display Panel | Industrial HMI Interface
  • ABB KP2500 Process Control System Controller
  • ABB CP405 A0 Operator Panel 1SAP500405R0001
  • ABB AX411/50001 Digital Input Module
  • ABB 500TRM02 1MRB150011R1 Procontrol P13 Bus Terminal Module
  • ABB 500TTM02 Temperature Module 1MB150021R0116
  • ABB 500TRM02 1MRB150011R0001 Terminating Resistor Module
  • ABB 500SCM01 1MRE450004R1 Control Module
  • ABB 500SCM01 1MRB200059/C 1MRB150044R0001 Station Control Module
  • ABB 500SCM01 1MRB150004R00011MRB200059/C Control Module
  • ABB 500PSM03 1MRB 150038 R1 894-030375D 136-011100H Power System Module
  • ABB 500PSM03 1MRB150038 R1 894-030375D 136-011100H Power Supply Module
  • ABB 500PSM02 1MRB150015R1 AD-272.100.20-01 AZ:C Power Supply Module
  • ABB 500PB101 1MRB178009R00011MRB200064/C Power Supply Module
  • ABB 500MTM02 1MRK001967-AA 1HDF 930512 X010 Module
  • ABB 500MTM02 1MRB150020R1102 1HDF 930512 X010 Motor Module
  • ABB 500MTM02 1MRB150020R0712 Touch Module
  • ABB 500MBA02 1MRB150003R0003 1MRB200053/M Bus Coupling Module
  • ABB 500MBA01 1MRB150003R00021MRB200053/L Motor Control Module
  • ABB 500MBA02 1MRB150003R000/B Analog Output Module
  • ABB 500CSP04 HE401314/0002 1MRB150051R2 Control Processor Module
  • ABB 500CPU05 1MRB150081R1/E CPU Module
  • ABB 500CPU03 1HDF700003R5122 Central Processing Unit
  • ABB 500CMP04 HE401314/0001 1MRB150051R1 Central Processor Module
  • ABB 500CIM05 1MRB150077R1/B PROFIBUS DP Interface Module
  • ABB 500BI001 1MRB150005R0001 1MRB200060/E Binary Input Module
  • ABB 500BI001 1MRB150005R1/J Procontrol P13 Bus Interface Module