Attachment installation: If auxiliary contacts, undervoltage release and other accessories need to be installed, they must be connected correctly according to the wiring diagram to ensure that the accessories match the main function of the circuit breaker. After the wiring is completed, the reliability of the accessory action needs to be checked.
3. Check after installation
Mechanical inspection: Manually operate the circuit breaker to close and open, and the action should be smooth without any jamming. The handle position should be clear (with clear identification of the closing, opening, and energy storage status).
Electrical inspection: Confirm that the wiring is not loose, the phase sequence is correct, and the insulation resistance test is qualified (using a 500V megohmmeter, insulation resistance value ≥ 1M Ω).
4. Operating instructions
Closing operation: After ensuring that there are no faults in the circuit, manually turn the handle to the "closing" position, and hear a "click" sound to indicate that the closing is in place; If equipped with an electric operating mechanism, press the control button to complete the closing and observe that the mechanism operates normally.
Opening operation: When opening normally, turn the handle to the "opening" position. After the fault is opened, the fault needs to be checked first, and the release device needs to be reset before closing.
Release adjustment:
Overload release: Adjust the set current within the range specified in the manual based on the load characteristics of the line (not exceeding the rated current of the circuit breaker) to ensure delayed release in case of overload.
Short circuit release: The instantaneous release setting current is adjusted according to the calculated value of the short-circuit current in the distribution system, ensuring quick disconnection during a short circuit and avoiding the expansion of the fault.
Ground fault release (if equipped): Adjust the ground fault action current and delay, and coordinate with system protection.
Maintenance and upkeep requirements
1. Daily maintenance cycle
Regular inspection: Under normal operating conditions, conduct a routine inspection every 6 months; In harsh environments (high dust, high humidity, frequent operation), reduce to once every 3 months.
Annual maintenance: Conduct comprehensive maintenance once a year, synchronized with power outage maintenance of the distribution system.
2. Maintain projects and operations
Appearance inspection: Check whether the circuit breaker casing and operating handle are damaged or discolored, and whether there are any signs of heating on the terminals (such as oxidation or burnt black).
Mechanical performance inspection: Operate the closing and opening of the circuit several times to check whether the action is smooth and whether the tripping mechanism is sensitive; The energy storage mechanism (if any) can reliably maintain energy after storage and act quickly when released.
Electrical performance inspection:
Measure insulation resistance to ensure there is no insulation aging or moisture damage.
To check the accuracy of the release action, it can be tested by simulating overload and short circuit conditions (professional equipment is required, and blind testing on site is prohibited).
Cleaning requirements: Use a dry brush or compressed air (pressure ≤ 0.4MPa) to remove dust from the surface and terminals of the circuit breaker. It is prohibited to use wet cloths or organic solvents for cleaning.
3. Maintain taboos
Non professionals are prohibited from disassembling core components such as circuit breakers, arc extinguishing chambers, and release devices. Disassembling them will cause the product to lose its protective function and cannot guarantee sealing.
It is prohibited to change the setting parameters of the release during maintenance (unless there is a clear load adjustment requirement and it is operated by professional personnel).
During the maintenance process, it is necessary to cut off power throughout the entire process and hang a "under maintenance, no closing" sign to prevent others from making mistakes.

Troubleshooting and Solutions
1. Common faults and their solutions
Possible causes and solutions for the fault phenomenon
Unable to close 1. The fault has not been resolved and the release has not been reset; 2. The operating mechanism is stuck; 3. The auxiliary contacts have not been reset; 4. Power failure of electric operating mechanism: 1. Check for short circuit and overload faults, and manually reset the release; 2. Check if there are any foreign objects in the organization, clean them and test them; 3. Check the auxiliary contact wiring and repair the poor contact of the contacts; 4. Check the power supply of the operating mechanism and restore power supply
Wrong tripping (tripping when there is no fault) 1. Overloaded tripping device setting current is too low; 2. There is harmonic interference in the line; 3. The release device is damaged; 4. Excessive ambient temperature leads to misoperation of the release device. 1. Adjust the setting current again according to the actual load current; 2. Investigate harmonic sources and install filtering devices if necessary; 3. Replace the damaged release device; 4. Improve ventilation conditions and reduce environmental temperature
Email:wang@kongjiangauto.com