MITSUBISHI MDS-B servo troubleshooting

F: | Au:FANS | DA:2026-05-26 | 291 Br: | 🔊 点击朗读正文 ❚❚ | Share:

MITSUBISHI MDS-B Series Servo Drive Maintenance and Troubleshooting Guide

System Overview and Security Upgrade Background

The Mitsubishi MDS-B series servo/spindle drive system is a comprehensive upgraded version of the MDS-A series, with core improvements aimed at meeting European safety standards (LVD) and enhancing system integration. This series consolidates the traditional rectifiers scattered in various servo and spindle drive units into independent power supply units (CV), significantly reducing heat generation and installation volume.

For engineers transitioning from the MDS-A series to the MDS-B series or facing maintenance difficulties with outdated MDS-A equipment, understanding the hardware changes, wiring differences, alarm codes, and parameter compatibility of the MDS-B series is crucial. This article will systematically outline the key points of drive replacement, fault diagnosis, and safety configuration based on the MDS-B series technical specification manual.



Selection and replacement precautions for power supply unit (MDS-B-CV)

2.1 Capacity Calculation Formula

When using a power unit to drive multiple servo/spindle motors, the capacity must meet the following conditions:

Single servo shaft: power unit capacity>∑ (spindle motor output)+∑ (servo motor output)

Two or more servo axes: power unit capacity>∑ (spindle motor output)+0.7 × ∑ (servo motor output)

Note: Motor output refers to the rated output power (kW) of the motor, not the capacity of the drive unit. The spindle motor shall have a rated output of 30 minutes.

For example, if the spindle motor is 7.5kW and the three servo motors are 2kW, 1kW, and 1kW respectively, the calculated value is 7.5+0.7 × (2+1+1)=10.3kW, and an 11kW power supply unit (MDS-B-CV-110) should be selected.

2.2 Special Requirements for MDS-B-CV-370

MDS-B-CV-370 (37kW) is a newly added high-capacity model that requires the installation of external contactors and cannot share contactors with other power units. Its surge charging sequence is different from other CVs, and sharing a contactor can cause damage. The setting rules for the rotary switch (SW1) are as follows:

When using a contactor: SW1=0 or 3

When not using a contactor: SW1=1 or 5 (CV-370 is prohibited from being set to 1 or 5)

When the external emergency stop function is enabled: SW1=4 (contactor valid) or 5 (contactor invalid)

2.3 Configuration principles for multiple power supply units

When the total power exceeds 38kW, two or more power units need to be used:

The first power unit is responsible for the spindle motor power (≤ 38kW)

The second power unit is responsible for the remaining spindle power plus 0.7 times the total servo power

Key limitation: The AC reactors of each power unit must be independent and cannot be shared. Contactors can be shared in principle, but CV-370 must be independent. When connecting the busbars (L+, L -, L11, L21), they must be wired independently and cannot be short circuited or interconnected.


Main circuit wiring specifications and wire diameter selection

3.1 Power input wire diameter (reference value)

Recommended wire diameter for power unit capacity (IV/IV)

CV-37/CR-37 IV3.5SQ or HIV2SQ

CV-55/CR-55 IV5.5SQ or HIV3.5SQ

CV-75 / CR-75 HIV5.5SQ

CV-110 IV14SQ or HIV8SQ

CV-150 IV22SQ or HIV14SQ

CV-185 IV30SQ or HIV22SQ

CV-220~260 IV38SQ or HIV30SQ

CV-300~370 IV60SQ or HIV38SQ

3.2 L+, L-Bus Wire Diameter (Unified Method)

To simplify spare parts, the bus wire diameter can be uniformly selected according to the capacity of the power unit:

CV capacity wire diameter

≤37kW IV3.5SQ / HIV2SQ

55~75kW IV5.5SQ / HIV3.5SQ

110~150kW IV14SQ / HIV8SQ

185~220kW IV22SQ / HIV14SQ

260~300kW IV38SQ / HIV22SQ

370kW IV60SQ / HIV50SQ

3.3 EC Directive Compliance Wiring Points

All terminals must be crimped with insulated tubes to prevent short circuits between adjacent terminals

The protective grounding (PE) terminal must be wired separately and cannot be shared by multiple wires

The power input side needs to be equipped with non fuse circuit breakers and electromagnetic contactors that comply with EN/IEC standards

The U, V, and W output phase sequence of servo/spindle drives must strictly correspond to motor terminals A, B, and C

It is strictly prohibited to install phase capacitors or surge absorbers on the motor output line

Analysis and Handling of Common Alarm Codes

4.1 Power Supply Unit (CV) Alarm

Common Reasons and Countermeasures for Removing the Meaning of Alarm Number LED Display

63 3 Auxiliary regeneration abnormality (transistor continuously conducting) PR (power supply re powering on) Regeneration transistor failure, power supply unit needs to be replaced

65 5 Surge Relay Abnormal PR Surge Resistance Short Circuit Relay Not Closed, Check Contactor and AC Reactor

67 7 missing phase PR input power supply R/S/T, one phase is open circuit, check the power supply line

69 9 grounding fault PR motor or power line short circuit to ground, need to be checked with a megohmmeter

73 J regeneration PR (needs to be controlled for more than 15 minutes to reset). If the regeneration energy exceeds the capacity of the power unit, it is necessary to increase the regeneration resistance or reduce the acceleration and deceleration frequency

  • Basler Electric BE1-700 Digital Protective Relay
  • Basler Electric SR8A-2B01B3A Static Voltage Regulator
  • Basler Electric SR4A-2B01B3E Static Voltage Regulator
  • Basler Electric 9017709102 PC Board
  • Basler Electric SR4A-2B01B3A Static Voltage Regulator
  • Basler Electric PRS-250 Veri-Sync Relay
  • Basler Electric 9066800102 Excitation Support System
  • Basler Electric BE1-87G Generator Differential Relay 9 1708 18 100
  • Basler Electric 36T865-2 BE03752001 Power Supply
  • Basler Electric M-300 149D940G02 Power Supply
  • Basler Electric ACA2040-25GM 4Mp 25Fps Area Scan Camera
  • Basler BE1-87G-S1A-A1C-A0N0 Differential Relay
  • Basler SR8A-2B06B3E Static Regulator SR8A2B06B3E
  • Basler SCP-210 Frequency Controller 9095400100
  • Basler BE1-59-A3E-A1J-N1N3F Overvoltage Relay BE159A3EA1JN1N3F
  • Basler 9 2011 11 100 Bracket Mounted Terminal Unit
  • Basler 9 1606 00 101 Voltage Regulator
  • Basler CBS-377 Current Boost System 9109600102
  • Basler 8650C72 Exciter Control Module PCB Rev 5
  • Basler C2EE1PA0N1F BE1-32R Reverse Power Relay
  • ADLINK HPCI-14S12U - Industrial Control Backplane 12PCI Backplane PCI-14S Passive Backplane
  • ADLINK PCIe-GIE74C - image acquisition card 4-CH GigE Vision PoE+ Frame Grabber
  • ADLINK PCI-8164 - control card 4-Axis Advanced Motion Controller Board
  • ADLINK PCIe-U304 - 4 Port USB3 PCIe Frame Grabbers USB Screw Hole Card
  • ADLINK PCI-9112 - Multi-Function Data Acquisition Card DAQ Card
  • ADLINK PCI-7432 - 51-12013-0A50 4-CH Isolated Numérique I/O PCI Cartes Digital I/O Card
  • ADLINK PCA-6106P3-0C1 REV.C1 - backplane 6-Slot Passive Backplane Board
  • ADLINK PCI-7224 - 24-CH Opto-Isolated Digital I/O PCI Board
  • ADLINK CPCI-7433R(G) - Digital Input Board Rear I/O CompactPCI Card
  • ADLINK EBP-13E4 - 51-46703-0A30 Industrial PC Backplane Passive Backplane
  • ADLINK PCIE-HDV62 - Image acquisition card High Definition Video Frame Grabber
  • ADLINK EBP-13E4 - 51-46703-0A30 Industrial Backplane Board Passive Backplane
  • ADLINK 90111-B1 / CPCI-6770 - PCB CPU MODULE CompactPCI Single Board Computer
  • ADLINK PCI-7248 - DATA ACQUISITION PCI CARD 48-CH Parallel Digital I/O Board
  • ADLINK PCI-7230 - 51-12003-0a50 board PCI7230 32-CH Isolated Digital I/O Card
  • ADLINK PCI2A000CB - 51-20000-0B30 Multi-Function DAQ Card Baseboard
  • ADLINK PCI-8134-005 - 4-Axis Motion Controller Card
  • ADLINK PCI-7224 - 24-CH Opto-Isolated Digital I/O PCI Card
  • ADLINK PCI-7434 - 64-CH Isolated Digital Output Card
  • ADLINK PCI-8132 - motion control card 2-Axis Servo & Stepper Controller
  • ADLINK PCI-8134 - Motion Controller PCI Card 4-Axis Controller Board
  • ADLINK PCI-8164 - Motion Control Card 51-12406-0A40 4-Axis Controller
  • ADLINK 51-12001-0C20 - Circuit Board Data Acquisition Interface Module Hardware
  • ADLINK NuPR0-840 - industrial control motherboard Full-Size PICMG CPU Board
  • ADLINK PCI-7444 - 51-12023-0A10 card 128-CH Isolated Digital Output Board
  • ADLINK PCI-1612B - data acquisition card 4-Port RS-232/422/485 Serial Communication Card
  • ADLINK PCI-6208V 009 - 8/16-CH 16-Bit Analog Output Cards PCB-I-E-482=6BX3
  • ADLINK NUPRO-935A/LV - industrial control motherboard Full-Size PICMG SBC Board
  • ADLINK PCI-9114DG - Multi-Function DAQ Card Data Acquisition PCI Card
  • ADLINK ACL-7130 - Data acquisition card Isolated Digital I/O Board
  • ADLINK ABX-6300D-4E1-BP - board ABX6300D4E1BP Video Interface Expansion Card
  • ADLINK CPCI-6940 - CPCI-6940/D1539/M16-0(EA)-000E 6U CompactPCI Processor Board
  • ADLINK NuPRO-760 - industrial control motherboard Half-Size PICMG SBC CPU Board
  • ADLINK IMB-M42H (G)-0020 - industrial control motherboard LGA1155 Micro-ATX Mainboard
  • ADLINK RTV-24 / PCI-MP4S - 51-12519-1C30 4-Channel Real Time Video Capture Board
  • ADLINK PCI-8134 - 4-Axis Servo & Stepper Motion Controller Card
  • ADLINK MXC-6101D - V.PC000.002.ST.00 Box PC Configurable Embedded Computer
  • ADLINK PCI-8134A - 51-12421-0A10 Motion Control Card 4-Axis Controller Card
  • ADLINK DIN-100S / DIN-100SA1 - Technology SCSI-II TB 100-PIN Terminal Block Board
  • ADLINK DIN-812M001 / DIN812M001 - 51-14034-0A1 51140340A1 Terminal Module Breakout Interface
  • ADLINK PCI-8164 - Servo motion control 4-Axis Advanced Controller Card
  • ADLINK PCIe-GIE64 - Acquisition card GigE Vision PoE+ Frame Grabber
  • ADLINK M-302 - Industrial control motherboard ATX PC Board Mainboard
  • ADLINK PCI-8134 - Motion Controller PCI Card 4-Axis Controller Board
  • ADLINK PCI-RTV24 - Image capture card Analog Video Frame Grabber
  • ADLINK PCI-8102 - Motion control card 2-Axis Servo & Stepper Controller Board
  • ADLINK PCI-9112 REV.B1 - Card Multi-Function Data Acquisition Card
  • ADLINK HSI-DI32-M-N / HSL-TB32-M-DIN - Discrete I/O MODULE Distributed Automation Module System
  • ADLINK PCI-7296 - IO card REV.A3 96-CH Parallel Digital I/O Card
  • ADLINK DIN-814P-A4 / 814Y - terminal board Motion Control Interface Block
  • ADLINK DIN-814P-A4 - 51-14056-0A10 PCB-I-E-2736=ZA01 Screw Terminal Board Breakout
  • ADLINK M-322 - motherboard Industrial Control Computer Mainboard
  • ADLINK NUPRO-406 REV:B1 - industrial control motherboard Full-Size PICMG CPU Board
  • ADLINK AMP-204C - card DSP-Based 4-Axis Advanced Pulse-Train Controller
  • ADLINK HPCI14S REV.B1 - industrial computer baseboard 14-Slot Passive Backplane
  • ADLINK PCI-7250 - 8-CH Relay Output & 8-CH Isolated DI PCI Card
  • ADLINK EBP-13E2 - baseplate Passive Backplane Industrial Computer Chassis Board
  • ADLINK LPCI-3488A - PCI-GPIB card 51-12801-0A30 acquisition card IEEE-488 Interface Board
  • ADLINK PCI-6216V-GL - 51-12201-0C30 16-CH 16-Bit Voltage Analog Output Card
  • ADLINK ACL-8454 - 16-CH Isolated Digital I/O & 4-CH Counter Card
  • ADLINK HPCI-9S7U - backplane Passive Backplane Compatible with NuPRO-A301 852 841 842
  • ADLINK DAQ-2010-007 - Simultaneous-Sampling Multi-Function Data Acquisition Card
  • ADLINK MP-C154 - 51-64205-0A10 Motion Control Card 4-Axis Controller Board
  • ADLINK MXE-202/mSSD16B/WiFi-BT - Matrix Rugged I/O Platform Embedded Fanless Computer
  • ADLINK CM-920-R-17 - PC/104-Plus Single Board Computer Module Intel Celeron M
  • ADLINK PCI-7250 NSMP - 8-CH Relay Output & 8-CH Isolated DI Card
  • ADLINK PCI-8164 - 4-Axis Motion Controller PCI Card W/ Cable and Breakout Box
  • ADLINK EMX-100 - Ethernet-based 4-axis Motion Controllers Distributed Motion Module
  • ADLINK PCI-8134A - Press control card 4-Axis Motion Controller Board
  • ADLINK M-845EG REV:3.2 - industrial motherboard Pentium 4 Socket 478 Micro-ATX
  • ADLINK PCI-9114A Rev A2 DG - card High-Resolution Multi-Function Data Acquisition Board
  • ADLINK IEC-915GV - REV 1.1 Industrial motherboard Socket 478 CPU Board
  • ADLINK PCI-9111DG(G) - Data Acquisition Card Multi-Function DAQ Card
  • ADLINK HPCI-15S10 REV:B2 - Industrial computer base plate Passive Backplane Board
  • ADLINK NuPR0-840 / NuPR0-840DV - industrial control motherboard Full-size PICMG CPU Board
  • ADLINK RTV-24 / PCI-MP4S - 51-12519-1C30 4-Channel Real Time Video Capture Board
  • ADLINK NUPRO-780 - industrial control motherboard Pentium III Single Board Computer
  • ADLINK PCI-7296 - 0050 card 96-CH Opto-Isolated Parallel DIO Card Set
  • ADLINK NUPRO-780 - industrial control motherboard PICMG Full-Size SBC
  • ADLINK PCI-7248 - 51-12006-0A3 002 Pci 7248 48-CH Parallel Digital I/O Card
  • ADLINK PCI-7230 - 32-CH Isolated Digital I/O Card
  • ADLINK AMP-204C - motion control card 4-Axis Advanced Controller Board
  • ADLINK PCI-1714UL - Card Ultra High-Speed 4-CH Simultaneous Sampling DAQ
  • ADLINK NuPRO-E330 - industrial computer equipment motherboard PICMG 1.3 SHB SBC
  • ADLINK AMP-204C - DSP-Based 4-Axis Advanced Pulse-Train Motion Controller Module
  • ADLINK PCI-7256 - 001 51-12206-0A2 REV.A2 LPCI-7256 16-CH Latching Relay Output Card
  • ADLINK ND6050 - NUDAM DIGITAL I/0 MODULE Distributed I/O Unit
  • ASEM BM100 - Box PC Embedded Fanless Industrial Computer
  • ADLINK PCI-7250 - PCI Acquisition Card 8-CH Relay Output & Isolated DI Board
  • ADLINK PCI-8164 - Servo motion control 4-Axis Controller Card
  • ADLINK NuPRO-A40H - Industrial Motherboard 51-41807-1A30 OSP LGA1155 H61
  • ADLINK ADMAX X300 SERVER - 51066010-0A30 motherboard Multi-Processor Mainboard
  • ADLINK CMe-GIE62+ - 51-32903-0A30 control card PC/104-Plus GigE Vision Frame Grabber
  • ADLINK NUPRO-780 - industrial control motherboard Full-Size PICMG SBC CPU Board
  • ADLINK ETX-AT-N270-18/GKTEL - 51-71111-OB10 motherboard ETX CPU Module Board
  • ADLINK DIN-812M - interface module Terminal Block Connection Board
  • ADLINK IMB-M42H - industrial control motherboard LGA1155 Micro-ATX Mainboard
  • ADLINK PXIS-2508 - 8-slot 3U PXI Instrument Chassis Power Hardware Assembly
  • ADLINK AMP-208C - Motion Control card DSP-Based 8-Axis Pulse-Train Controller
  • ADLINK PCI-9111 / PCI-9111DG - Multi-Function Data Acquisition Card DAQ Board
  • ADLINK IEEE-488 GPIB card - Bus Interface Controller Communication Board
  • ADLINK RTV-24 - 51-12519-1C30 image acquisition card Video Frame Grabber Card
  • ADLINK TB-24P/24-01 - Board 24 Way Screw Terminal Breakout Board
  • ADLINK HSL-DI16DO16-DB-NN - 51-23015-0A40 Distributed Discrete I/O Module Set
  • ADLINK PCI-7442 - switch quantity card data acquisition card 64-CH Isolated Card
  • ADLINK ACL-7130 REV. B2 - industrial control capture card Isolated Digital I/O PCI Card
  • ADLINK PCI-6S / PCI6S - Backplane 6-Slot Passive Backplane Chassis Board
  • ADLINK ACL-8113A - card Isolated Digital Input Card