Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

HITACHI S10VE Programmable Controller

来源: | 作者:FAN | 发布时间 :2025-12-30 | 367 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

HITACHI S10VE Programmable Controller

Usage Notes

■ Installation

The programmable controller employs electronic circuit and processor technologies. Note the following in particular:

● When constructing a system, make sure that conditions including the maximum rating, operating power supply voltage range, heat dissipation characteristics, and installation conditions are within the guaranteed operating range described in this manual. Hitachi bears no responsibility for failures or accidents that arise from use of the product outside the guaranteed range.

Even when using the product within the guaranteed range, you must consider the predicted failure rate and failure mode of the product. You can then implement system measures such as making the system failsafe so that operation of the Hitachi product will not cause personal injury, fire, and other consequential damage.

The Programmable Controllers ( ((PCs^{#})) ) in which the CPU unit and PI/O units are installed are neither fireproof, dustproof, nor waterproof. Install the PCs in steel cabinets that are fireproof, dustproof, and waterproof (see Figure 1-1).

#: PCs means the programmable controllers in their entirety including the CPU unit and PI/O units.

● Use the S10VE in an environment that is within the specifications explained in Chapter 3. To ensure long-term stable operation, we recommend that you use the product at room temperature and normal relative humidity (15 to 35°C and 45 to 85% RH). Using the product in a high-temperature or high-humidity environment or an environment where the temperature varies widely over the course of a day leads to a reduced service life.

image.png

■ Output module

You must provide a short-circuit protection fuse in the load power supply circuit of the output module. Use fuses with the correct load rating. Using the wrong fuse might result in damage to the PCB or housing if the load shortcircuits.

image.png

■ Grounding

● Panel grounding specifications

The PCs panel that incorporates the S10VE must be welded to the steel frame of a building that provides at least class D grounding with the ground resistance of 100Ω or less.

Conditions for grounding to the steel frame of a building

- The steel frame is welded together

- The grounding between the earth and the steel frame meets the criteria for class D

If this is not achievable, ground the PCs panel by connecting it to a grounding rod driven into the earth. This provides a low grounding resistance that prevents surrounding noise from entering the PCs.

image.png

■ Noise

Do not install the S10VE in or near a panel to which a high-voltage device (such as an inverter) is mounted. If this is unavoidable, use a shielding plate to shield the CPU unit, PI/O units, and cabling from electromagnetic and electrostatic induction.

■ Emergency stop circuit

A partial failure can affect the entire system. Provide an emergency stop circuit as an external circuit. Do not incorporate the emergency stop circuit into programs run on the programmable controller.

■ Disassembling modules

Do not disassemble the modules.

■ Removing/inserting modules

You must turn off the power before removing or inserting a module. To prevent module damage due to static electricity, discharge any static electricity from your body before touching the equipment.

■ Installation of new equipment

When peripheral equipment is added or replaced, check the following aspects of the power supply and grounding:

Power supply

Inspect the power supply voltage and waveform.

- Has the voltage dropped?

- Is there any noise in the power cable?

image.png

1. Usage Notes

● Grounding

- Make sure that the S10VE does not share its ground cable with other equipment.

- Make sure that no power or lead cables are positioned too closely to a signal cable (such as a remote I/O cable).

image.png

2. Overview

2.1 Overview of the system

The S10VE is a programmable controller suited for a wide range of applications from simple condition control to complex arithmetic control. It is capable of simultaneously executing ladder logic, HI-FLOW, and C languages.

2.2 System configuration

2.2.1 Example system configuration

Figure 2-1 shows an example configuration of an S10VE system.

An S10VE system is made up of a CPU unit, PI/O units, and peripherals.

By installing option modules (OD.RING, D.NET, J.NET, FL.NET, ET.NET) in the CPU unit, an S10VE system can connect to an optical communication network and various other optional networks.

By installing a remote I/O interface module (hereafter RI/O-IF module) in the CPU unit, the system can connect to HSC-1000 and HSC-2100 PI/O units using remote I/O lines. A given system can incorporate both HSC-1000 and HSC-2100 PI/O units.

image.png

2.2.2 CPU unit configuration

An S10VE system is made up of a mount base, power supply module, RI/O-IF module, CPU module, and PI/O modules. The mount base incorporates one PS slot (a dedicated slot for the power supply module), one IF slot (a dedicated slot for the RI/O-IF module), one CPU slot (a dedicated slot for the CPU module), and seven I/O slots. The power supply module and CPU module are mandatory components of an S10VE system. Installation of an RI/O-IF module, option modules, and PI/O modules is optional.

image.png


2.2.3 Configuration of remote I/O communication

The S10VE system can use an RI/O-IF module to perform remote I/O communication on a maximum of two lines (see Figure 2-3).

The maximum length of each line is 300 m by remote I/O cable alone, extendable to a maximum of 3.3 km using remote I/O optical adapters. This length of 3.3 km is three optical cables of 1 km each, plus the 300 m achievable by remote I/O cable.

You can use HSC-1000 and HSC-2100 PI/O units in the same system.

image.png


2.3 System components

2.3.1 Components of CPU unit

Table 2-1 shows the components that make up the CPU unit.

The specifications and functions of the mount base, power supply module, CPU module, and RI/O-IF module are explained in the following chapters:

- Chapter 3: Specifications

- Chapter 5: Part Names and Functions

For details about the specifications and functions of the option modules, see the following manuals:

- S10VE User's Manual Option OD.RING (LQE510-E) (manual number SEE-1-101)

- S10VE User's Manual Option J.NET (LQE540-E) (manual number SEE-1-102)

- S10VE User's Manual Option D.NET (LQE770-E) (manual number SEE-1-103)

- S10VE User's Manual Option FL.NET (LQE702-E) (manual number SEE-1-104)

- S10VE User's Manual Option ET.NET (LQE260-E) (manual number SEE-1-105)

For details about the specifications and functions of the PI/O modules, see the following manual:

- S10mini Hardware Manual I/O Modules (manual number SME-1-114)

image.png

image.png

2.3.2 PI/O units and peripherals

A PI/O unit is made up of an HSC-1000 module and an HSC-2100 module. For details, see the following manuals:

- S10mini Hardware Manual I/O Modules (manual number SME-1-114)

- S10mini Hardware Manual D.Station (manual number SME-1-119)

- HSC-2100 Hardware Manual I/O Modules (manual number SME-1-126)

You can also connect a D.NET optical adapter as a peripheral. For details, see the following manual:

- S10mini Hardware Manual OPT.D-NET (manual number SME-1-120)

2.3.3 PADT

PADT (Programming and Debugging Tools) is a programming tool used to make, test, run, and troubleshoot application programs for the S10VE system. The PADT is a personal computer with the required software such as BASE SYSTEM/S10VE installed.

The required specifications for the personal computer that serves as the PADT are as follows:

- 1 GHz or faster CPU

- At least 2GB RAM

- At least 200 MB free hard disk space

- A display resolution of at least 1,366 × 768 (FWXGA)

- Microsoft® Windows® 7 (64bit) operating system or Microsoft® Windows® 10 (64bit) operating system

image.png

Detailed explanation of core hardware components

1. Core module specifications and functions

Module type, model, key parameters, core functions, installation requirements

CPU module LQP600 has a maximum of 2048 I/O points; Main memory 128MB; PI/O memory (bit area 2MB/word area 1MB); Processing speed: bit operation 9.4ns/step system control core, supports ladder diagram/HI-FLOW/C language parallel execution; Built in Ethernet ports (ET1/ET2); Install resources such as event registers and data registers in dedicated CPU slots; Need to connect the main battery (HDC5200) in advance; Avoid direct proximity to high-voltage modules

Power module LQ410 input: 100-120VAC/100-110VDC; Output: 5VDC/10A; The power of 144VA (AC)/132W (DC) provides stable DC power supply for the system; Equipped with overcurrent (OC) and overvoltage (OV) protection; Support the installation of power status LED indicators in PS dedicated slots; Reliable grounding is required; Power switch start stop interval ≥ 5 seconds

RI/O-IF module LQE950 2-channel remote I/O cable; Communication speed 768kbps; Maximum of 12 PI/O units per channel; Implement remote I/O expansion with a transmission distance of ≤ 300m; Support 100 Ω/150 Ω terminal resistor configuration; Provide PCsOK signal output installed in IF dedicated slot; Remote I/O cables require shielded twisted pair cables; Unused ports require a 150 Ω resistor to be connected

Option module - OD.RING LQE510-E duplex ring network; Maximum 64 nodes; Shared data: I/O 4096 points/word data 4096 words cross CPU unit memory data sharing; Simplified line fault analysis installation in I/O slots; Optical connectors require insulation materials for protection

Option module - ET.net LQE260-E supports TCP/IP/UDP/IP; Compatible with 10BASE-T/100BASE-TX; Maximum 1024 node Ethernet communication extension; Adapting to industrial network integration requires configuring IP addresses and routing information; Prioritize using the ET2 port for communication with PADT

2. Classification and specifications of PI/O modules

The PI/O module is divided into three categories: digital I/O, analog I/O, and pulse counter, which are suitable for different signal acquisition and execution requirements:

Digital input modules: such as LQX200 (12-24VDC/16 points), LQX350 (12-24VDC/64 points), support contact input, current consumption 80-170mA/module;

Digital output module: such as LQY200 (transistor output/16 points), LQY100 (relay output/16 points), supporting a maximum output current of 2A and a relay life of 70000 times;

Simulation module: such as LQA000 (voltage input/4 points), LQA500 (voltage output/4 points), supporting ± 5V/± 10V/1-5V voltage range;

Pulse counter module: LQC000 (1-phase/2-phase pulse input), supports 1-point pulse counting, with a current consumption of 150mA per module.

3. Key physical and environmental parameters

Physical specifications: 7-slot mounting base (HSC-1770) with dimensions of 437 × 138.6 × 100mm and weight ≤ 1300g; the thickness of each module is uniformly 34mm (excluding some), and the tightening torque of the mounting screws is 1.0N · m (M4);

Environmental adaptability: operating temperature 0-55 ° C (temperature variation ≤ 10 ° C/hour), storage temperature -20-75 ° C; relative humidity 10-90% RH (no condensation); Seismic resistance: 10-150Hz, 10m/s ² acceleration, 8 minutes/cycle; Impact resistance: 147m/s ² peak acceleration, 11ms half sine wave;

Grounding requirements: Class D grounding (grounding resistance ≤ 100 Ω), separated from the AC panel grounding main line, with a spacing of ≥ 15m.

image.png

 Installation and commissioning process

1. Key steps and requirements for installation

(1) Preliminary preparation

Confirm installation environment: temperature 0-55 ° C, humidity 10-90% RH, no corrosive gases, dust concentration ≤ 0.1mg/m ³;

Grounding preparation: Construction shall be carried out in accordance with Class D grounding standards, with a grounding resistance of ≤ 100 Ω, and multiple cabinets shall be connected to the ground using a daisy chain connection;

Tool preparation: Use calibrated measuring instruments and compatible screwdrivers (tightening torque 1.0-1.5N · m).

(2) Installation process

Installation base: fixed on the vertical surface of the cabinet, using M5 screws (tightening torque 1.5N · m) to ensure that the insulation lining does not fall off and the metal part of the base does not touch the control cabinet;

Module assembly: Install in the order of "power module → RI/O-IF module → CPU module → option module → PI/O module", align the module with the guide rail, insert it vertically, and tighten the screws;

Battery connection: Before installing the CPU module, insert the main battery cable into the connector according to the corresponding color, and cover the battery cover tightly (hear a snap sound);

Wiring specifications:

Power cable: ≥ 2mm ² shielded twisted pair, with a distance of ≥ 100mm from the network cable;

Remote I/O cable: Select according to the transmission distance (0.75mm ² cable for long distances, ≤ 300m), with single ended grounding of the shielding layer (RI/O-IF side);

Grounding wiring: The FG terminal is connected in a daisy chain and ultimately connected to the power module FG terminal. The cable cross-section is ≥ 2mm ² (inside the cabinet)/≥ 5.5mm ² (outside the cabinet).

(3) Installation gap requirements

The distance between the cabinet and the unit is ≥ 100mm, and the distance between the sides is ≥ 50mm;

There is a requirement for no distance between modules, but one empty slot needs to be left between the high-voltage PI/O module (≥ 100VAC/48VDC) and the CPU/option/simulation module;

Cooling measures: The cabinet needs to have air vents or install fans to ensure that the intake temperature is ≤ 55 ° C.

2. Debugging core processes and tools

(1) Debugging Tools and Environment

Tool: BASE SYSTEM/S10VE (requires administrator privileges to install), supports Windows 7/10 (64 bit), PADT needs to meet 1GHz CPU, 2GB memory, 200MB free hard disk;

Connection: Connect PADT to CPU module ET1/ET2 ports via Ethernet cable, with default IP address 192.192.192.1 (ET1)/192.192.193.1 (ET2).

(2) Debugging key steps

Project creation: Start BASE SYSTEM, create a new project and configure PC numbers and comments, enable C mode requires installation of RPDP;

Network configuration: Set the IP address, subnet mask, and routing information of the CPU's built-in Ethernet or ET.net module, write them, and restart the system;

Program download: Write the program using LADDER DIAGRAM SYSTEM/HI-FLOW SYSTEM, download it to the CPU module, and confirm that there are no syntax errors;

Parameter configuration: Set PI/O installation status, partition (FIX/FREE), I/O point count, remote I/O synchronization mode, etc;

System startup: Turn the CPU RUN/STOP switch to RUN, observe that the RUN LED is constantly on, and confirm that there are no error codes through the indicator;

Function verification: Monitor memory data through MCS function, view module status and error logs through RAS menu, and verify that I/O signal acquisition and execution are normal.

3. Operations and troubleshooting

(1) Key points of daily operation and maintenance

Regular inspection: monthly check the tightness of module screws, LED status, and cable connections; Clean ventilation ducts and verify grounding resistance annually;

Backup strategy: Regularly backup CPU data, including main memory and MRAM data, through the BACKUP STORE SYSTEM, and backup files need to be stored remotely;

Module replacement: It is recommended to replace the power module within 10 years (the lifespan of the aluminum electrolytic capacitor), and replace the main battery within 5 years. When replacing, the power should be turned off;

(2) Common troubleshooting

LED fault indication:

ERR LED constantly on: CPU module has a serious error. Check the error code through the indicator (such as ECF=xxxxx) and refer to the manual for troubleshooting;

OV/OC LED on: Power module overvoltage/overcurrent, check input voltage and load current;

LINK LED not lit: Ethernet physical connection abnormality, check cable and switch ports;

Remote I/O communication failure: Confirm terminal resistance configuration (unused port connected to 150 Ω), cable shielding grounding, station number setting, and check timeout status through system registers;

Program execution exception: Check for ladder mode (RUN/STOP), PI/O module installation restrictions, and locate syntax or logic errors through error logs.

image.png


  • Vibro-meter CMC16 16-Slot Machinery Protection Rack
  • Vibro-meter MPC4 4-Channel Protection Card
  • Vibro-meter VM600 IOC4T 4-Channel I/O Module
  • Vibro-meter VM600 204-040-100-012 System Controller
  • Vibro-meter VM600 PNR200-570-000-111 Relay Module
  • Vibro-Meter VM600 IOCN 200-566-000-112 Network Interface
  • Vibro-Meter VM600 IOC16T 200-565-000-013 I/O Card
  • Vibro-Meter VM600 RPS6U 200-582-500-013 Power Supply
  • Vibro-Meter VM600 CMC16 200-530-022-014 Monitoring Card
  • Vibro-Meter VM600 MPC4 200-510-070-113 Protection Card
  • Vibro-meter VM600 204-040-100-012 System Controller
  • Vibro-meter VMF IOCN Network I/O Module
  • Vibro-meter VMF RLC16 Relay Output Module
  • Vibro-meter VMF IOC4T 4-Channel I/O Module
  • Vibro-meter VMF IOC16T 16-Channel I/O Module
  • Vibro-Meter CMC16 200-530-111-013 Condition Monitoring Card
  • Vibro-Meter CPUM 200-595-046-114 Advanced Rack Controller
  • Vibro-Meter MPC4 200-510-111-034 Machinery Protection Card
  • Vibro-Meter CPUM 200-595-045-114 Rack Controller
  • Vibro-Meter SIM-275A 200-582-500-013 Signal Interface
  • Vibro-Meter VM600-CSA 204-040-100-211 Redundancy Module
  • Vibro-meter VM600 204-040-100-012 System Controller
  • Vibro-meter VM600 RLC16 Relay Module
  • Vibro-meter VM600 RPS6U Redundant Power Supply
  • Vibro-meter VM600 CMC16 Machinery Protection Rack
  • Vibro-meter VM600 ABE042 System Controller Card
  • Vibro-Meter VM600 RPS6U 200-582-200-011 Power Supply
  • Vibro-Meter VM600 RLC16 Relay Card
  • Vibro-Meter VM600 IOC4T 200-560-000-018 Input Output Card
  • Vibro-Meter VM600 XIO16T 620-003-111-112 Input Output Module
  • Vibro-meter VM600 XMV16 Vibration Measurement Card
  • Vibro-meter VM600 ABE040 System Controller Card
  • Vibro-Meter 444-680-000-511 Signal Conditioning Module
  • Vibro-meter VM600 CMC16 Machinery Protection System
  • VIPA 62K-NHC0-DH Touch Panel HMI
  • VIPA 972-0DP10 PROFIBUS DP Interface Module
  • VMIC Assy 11993R2 Circuit Board Assembly
  • VMIC 11-1001245-01 Industrial Module
  • VMIC ZT5524A1A CompactPCI Intelligent Controller
  • VMIC VMIVME-2533 32-Channel Digital I/O Module
  • Vortran LST200 Laser Diode Control System
  • Vortran Stradus 405nm Laser Module
  • Vishay 120NQ045R Schottky Rectifier Diode
  • VMIC VMIVME-7740-840 Pentium III VME SBC
  • VMIC VMIVME-7740-855 PowerPC VME Single Board Computer
  • VMIC VMIVME-1128 128-Bit High Voltage Digital Input Board
  • VMIC ASSY 12149 VMEbus Single Board Computer
  • VMIC ASSY 11994R13 VMEbus Industrial I/O Module
  • Wavecrest DTS-2079 High-Performance Controller Module
  • Wurth Elektronik 74271132 WE-STAR-TEC Snap Ferrite
  • Woodward 9907-165 Digital Turbine Control Module
  • DS1230Y-150+ 256Kb Non-Volatile SRAM Maxim Integrated
  • ZIPPE MWS10/A Industrial Weighing Transmitter Module
  • ZNYX ZX370 Series Fast Ethernet PCI Adapter
  • Vortran KDL-1230 Precision Medical Control
  • VWR Scientific Model 3000 Lab Equipment
  • Wagner+Grimm CH-6102 ETUI1500 Transformer Technical Specs
  • Wago MCS 231-302/037-000 Male Connector
  • Wago VDE0611 Series Rail-Mounted Terminal Blocks
  • Warner Electric ERS-198 1005-05-001 Electrically Released Brake
  • Yaskawa SGDH-01AE Sigma II Servo Driver
  • Omron 3G3HV-A4022-CE Inverter
  • Omron NT625C-ST152 Color Touch HMI
  • Parker Parvex NX310EAKR7001 NX Series Servo Motor
  • UniOp TCP10G-04-0245 Industrial HMI
  • Yaskawa SGDH-04AE Servo Driver 200V 400W
  • Presstech 7612-099Z-01 PLC Control Board
  • Yaskawa SGDH-10DE Servo Driver 400V 1kW
  • Landis Gyr PCA1 M35M4 CPU Controller
  • MICREX-F FLT-ASFKA PLC Loader with RS232 Cable
  • ABB Bailey INNIS21 Network Interface Module
  • Omron Sysmac CV500-SNT31 SYSMAC LINK Unit
  • Parker Hannifin HID2CS/S4 HiDrive Servo Driver
  • Pogliano Busmar PPeF 224541Z0HAC 250A Switch
  • GE Fanuc A16B-3300-003 Series 16-i Main Board
  • BLQ63M30 Brushless Servo Motor High Precision Motion Control
  • YASKAWA SGDH-08AE-S-OY Servopack Servo Drive Motion Control
  • OMRON C200H-RT201 Remote I/O Unit PLC Communication Module
  • PARKER HPD2S2N Servo Driver Industrial Motion Controller
  • SIEMENS 6AV3617-1JC00-0AX1 HMI Operator Panel Interface
  • KEB E3.SM.001.4400 Servomotor
  • Omron SCY-M1-PRO-51C SYSMAC Programming Console
  • ABB SACE TMAX T4 S 160 4 Pole Circuit Breaker
  • Omron CS1G-CPU44-EV1 PLC CPU Unit
  • ABB SACE PR212/P Electronic Trip Unit
  • Mitsubishi HC-SFS524K AC Servo Motor
  • Parker S.B.C. HPD2S1N Electronics Servo Driver
  • Yaskawa SGMPH-08A1A41 Sigma II Servo Motor
  • Omron FQ2-S25050F Smart Camera Vision System
  • Omron C120-LK202-EV1 Host Link Unit RS-422C Interface
  • 23.SM.000.3400 PLC KEB Servo Motor Industrial Control System
  • Biesse Rover CNI PLC 2153 030 7146.30 Industrial Control Unit
  • OMRON ME5614C Industrial Modem 56000bps V.90 Communication
  • SCHNEIDER BCH16HF07332A5C2 Servo Motor High Precision Control
  • ANFX-P130F-1GL3-33 Precision Gearbox Industrial Transmission
  • Beckhoff CX5020-0110 Embedded PC PLC
  • Schneider PowerLogic P5U20 Protection Relay Easergy
  • Siemens 6ES5 466-3LA11 Simatic Analog Input Module
  • Tex Computer TEB0055 77037 Industrial Terminal
  • Audiotel Engineering 0802P1I8000E Industrial Interface Module
  • ELAU DB-5 Distribution HW 5104 Servo System
  • Touchstar 10K TS10KCC0CEMP Industrial Touch Panel
  • Beckhoff CX2030-0125 Embedded PC PLC
  • Parker Hannifin HID5CS/S4 HIDRIVE 5A Servo Drive
  • Yaskawa ACE-P300-TH5 Servo Drive with Profibus
  • Omron Sysmac SCY-P0 13E Sequencer Controller
  • Saia Burgess PCD4.M120 PCD4.M12 Central Controller
  • Schneider Electric TSX3722101 Modicon Micro PLC
  • Siemens Micromaster 440 6SE6440-2AD25-5CA1 Inverter
  • SICK DL50-P1123 Distance Sensor
  • Yaskawa SGDH-04AE-OY Servo Driver 200V 400W
  • Cincinnati Milacron 3-542-1203A Circuit Board Module
  • Allen-Bradley 1756-EN2T EtherNet/IP Communication Module
  • OMRON CS1H-CPU66-V1 Programmable Logic Controller
  • ABB SACE TMAX S6N 630 Molded Case Circuit Breaker
  • Weidmuller IE-SW-VL16-16TX 16-Port Ethernet Switch
  • Schneider PowerLogic CM4250 Circuit Monitor
  • Sacmi IDPM IDMP1.A SMC 085.16.982 Control
  • Omron C120-LK202-EV1 Host Link Unit
  • Omron FQ2-S15050F Smart Camera Vision System
  • OMRON CJ1G-CPU44H Programmable Logic Controller
  • SIEMENS KTP600 HMI 6AV6 647-0AD11-3AX0 Touch Panel
  • OMRON CS1G-CPU45H EV1 Programmable Logic Controller
  • Omron C200HG PLC System C200H-ID212 C200H-OC226
  • ROBOSYSTEM IOG4AX-HD-100 IOG-HD Motion Controller
  • Datalogic SG4-S3-080-PP-W Safety Light Curtain
  • Omron NS12-TS01B-V2 Interactive Display
  • Esto Electronic E.CGT-405-42TE PLC Rack