Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

HITACHI S10VE Programmable Controller

F: | Au:FAN | DA:2025-12-30 | 615 Br: | 🔊 点击朗读正文 ❚❚ | Share:

HITACHI S10VE Programmable Controller

Usage Notes

■ Installation

The programmable controller employs electronic circuit and processor technologies. Note the following in particular:

● When constructing a system, make sure that conditions including the maximum rating, operating power supply voltage range, heat dissipation characteristics, and installation conditions are within the guaranteed operating range described in this manual. Hitachi bears no responsibility for failures or accidents that arise from use of the product outside the guaranteed range.

Even when using the product within the guaranteed range, you must consider the predicted failure rate and failure mode of the product. You can then implement system measures such as making the system failsafe so that operation of the Hitachi product will not cause personal injury, fire, and other consequential damage.

The Programmable Controllers ( ((PCs^{#})) ) in which the CPU unit and PI/O units are installed are neither fireproof, dustproof, nor waterproof. Install the PCs in steel cabinets that are fireproof, dustproof, and waterproof (see Figure 1-1).

#: PCs means the programmable controllers in their entirety including the CPU unit and PI/O units.

● Use the S10VE in an environment that is within the specifications explained in Chapter 3. To ensure long-term stable operation, we recommend that you use the product at room temperature and normal relative humidity (15 to 35°C and 45 to 85% RH). Using the product in a high-temperature or high-humidity environment or an environment where the temperature varies widely over the course of a day leads to a reduced service life.

image.png

■ Output module

You must provide a short-circuit protection fuse in the load power supply circuit of the output module. Use fuses with the correct load rating. Using the wrong fuse might result in damage to the PCB or housing if the load shortcircuits.

image.png

■ Grounding

● Panel grounding specifications

The PCs panel that incorporates the S10VE must be welded to the steel frame of a building that provides at least class D grounding with the ground resistance of 100Ω or less.

Conditions for grounding to the steel frame of a building

- The steel frame is welded together

- The grounding between the earth and the steel frame meets the criteria for class D

If this is not achievable, ground the PCs panel by connecting it to a grounding rod driven into the earth. This provides a low grounding resistance that prevents surrounding noise from entering the PCs.

image.png

■ Noise

Do not install the S10VE in or near a panel to which a high-voltage device (such as an inverter) is mounted. If this is unavoidable, use a shielding plate to shield the CPU unit, PI/O units, and cabling from electromagnetic and electrostatic induction.

■ Emergency stop circuit

A partial failure can affect the entire system. Provide an emergency stop circuit as an external circuit. Do not incorporate the emergency stop circuit into programs run on the programmable controller.

■ Disassembling modules

Do not disassemble the modules.

■ Removing/inserting modules

You must turn off the power before removing or inserting a module. To prevent module damage due to static electricity, discharge any static electricity from your body before touching the equipment.

■ Installation of new equipment

When peripheral equipment is added or replaced, check the following aspects of the power supply and grounding:

Power supply

Inspect the power supply voltage and waveform.

- Has the voltage dropped?

- Is there any noise in the power cable?

image.png

1. Usage Notes

● Grounding

- Make sure that the S10VE does not share its ground cable with other equipment.

- Make sure that no power or lead cables are positioned too closely to a signal cable (such as a remote I/O cable).

image.png

2. Overview

2.1 Overview of the system

The S10VE is a programmable controller suited for a wide range of applications from simple condition control to complex arithmetic control. It is capable of simultaneously executing ladder logic, HI-FLOW, and C languages.

2.2 System configuration

2.2.1 Example system configuration

Figure 2-1 shows an example configuration of an S10VE system.

An S10VE system is made up of a CPU unit, PI/O units, and peripherals.

By installing option modules (OD.RING, D.NET, J.NET, FL.NET, ET.NET) in the CPU unit, an S10VE system can connect to an optical communication network and various other optional networks.

By installing a remote I/O interface module (hereafter RI/O-IF module) in the CPU unit, the system can connect to HSC-1000 and HSC-2100 PI/O units using remote I/O lines. A given system can incorporate both HSC-1000 and HSC-2100 PI/O units.

image.png

2.2.2 CPU unit configuration

An S10VE system is made up of a mount base, power supply module, RI/O-IF module, CPU module, and PI/O modules. The mount base incorporates one PS slot (a dedicated slot for the power supply module), one IF slot (a dedicated slot for the RI/O-IF module), one CPU slot (a dedicated slot for the CPU module), and seven I/O slots. The power supply module and CPU module are mandatory components of an S10VE system. Installation of an RI/O-IF module, option modules, and PI/O modules is optional.

image.png


2.2.3 Configuration of remote I/O communication

The S10VE system can use an RI/O-IF module to perform remote I/O communication on a maximum of two lines (see Figure 2-3).

The maximum length of each line is 300 m by remote I/O cable alone, extendable to a maximum of 3.3 km using remote I/O optical adapters. This length of 3.3 km is three optical cables of 1 km each, plus the 300 m achievable by remote I/O cable.

You can use HSC-1000 and HSC-2100 PI/O units in the same system.

image.png


2.3 System components

2.3.1 Components of CPU unit

Table 2-1 shows the components that make up the CPU unit.

The specifications and functions of the mount base, power supply module, CPU module, and RI/O-IF module are explained in the following chapters:

- Chapter 3: Specifications

- Chapter 5: Part Names and Functions

For details about the specifications and functions of the option modules, see the following manuals:

- S10VE User's Manual Option OD.RING (LQE510-E) (manual number SEE-1-101)

- S10VE User's Manual Option J.NET (LQE540-E) (manual number SEE-1-102)

- S10VE User's Manual Option D.NET (LQE770-E) (manual number SEE-1-103)

- S10VE User's Manual Option FL.NET (LQE702-E) (manual number SEE-1-104)

- S10VE User's Manual Option ET.NET (LQE260-E) (manual number SEE-1-105)

For details about the specifications and functions of the PI/O modules, see the following manual:

- S10mini Hardware Manual I/O Modules (manual number SME-1-114)

image.png

image.png

2.3.2 PI/O units and peripherals

A PI/O unit is made up of an HSC-1000 module and an HSC-2100 module. For details, see the following manuals:

- S10mini Hardware Manual I/O Modules (manual number SME-1-114)

- S10mini Hardware Manual D.Station (manual number SME-1-119)

- HSC-2100 Hardware Manual I/O Modules (manual number SME-1-126)

You can also connect a D.NET optical adapter as a peripheral. For details, see the following manual:

- S10mini Hardware Manual OPT.D-NET (manual number SME-1-120)

2.3.3 PADT

PADT (Programming and Debugging Tools) is a programming tool used to make, test, run, and troubleshoot application programs for the S10VE system. The PADT is a personal computer with the required software such as BASE SYSTEM/S10VE installed.

The required specifications for the personal computer that serves as the PADT are as follows:

- 1 GHz or faster CPU

- At least 2GB RAM

- At least 200 MB free hard disk space

- A display resolution of at least 1,366 × 768 (FWXGA)

- Microsoft® Windows® 7 (64bit) operating system or Microsoft® Windows® 10 (64bit) operating system

image.png

Detailed explanation of core hardware components

1. Core module specifications and functions

Module type, model, key parameters, core functions, installation requirements

CPU module LQP600 has a maximum of 2048 I/O points; Main memory 128MB; PI/O memory (bit area 2MB/word area 1MB); Processing speed: bit operation 9.4ns/step system control core, supports ladder diagram/HI-FLOW/C language parallel execution; Built in Ethernet ports (ET1/ET2); Install resources such as event registers and data registers in dedicated CPU slots; Need to connect the main battery (HDC5200) in advance; Avoid direct proximity to high-voltage modules

Power module LQ410 input: 100-120VAC/100-110VDC; Output: 5VDC/10A; The power of 144VA (AC)/132W (DC) provides stable DC power supply for the system; Equipped with overcurrent (OC) and overvoltage (OV) protection; Support the installation of power status LED indicators in PS dedicated slots; Reliable grounding is required; Power switch start stop interval ≥ 5 seconds

RI/O-IF module LQE950 2-channel remote I/O cable; Communication speed 768kbps; Maximum of 12 PI/O units per channel; Implement remote I/O expansion with a transmission distance of ≤ 300m; Support 100 Ω/150 Ω terminal resistor configuration; Provide PCsOK signal output installed in IF dedicated slot; Remote I/O cables require shielded twisted pair cables; Unused ports require a 150 Ω resistor to be connected

Option module - OD.RING LQE510-E duplex ring network; Maximum 64 nodes; Shared data: I/O 4096 points/word data 4096 words cross CPU unit memory data sharing; Simplified line fault analysis installation in I/O slots; Optical connectors require insulation materials for protection

Option module - ET.net LQE260-E supports TCP/IP/UDP/IP; Compatible with 10BASE-T/100BASE-TX; Maximum 1024 node Ethernet communication extension; Adapting to industrial network integration requires configuring IP addresses and routing information; Prioritize using the ET2 port for communication with PADT

2. Classification and specifications of PI/O modules

The PI/O module is divided into three categories: digital I/O, analog I/O, and pulse counter, which are suitable for different signal acquisition and execution requirements:

Digital input modules: such as LQX200 (12-24VDC/16 points), LQX350 (12-24VDC/64 points), support contact input, current consumption 80-170mA/module;

Digital output module: such as LQY200 (transistor output/16 points), LQY100 (relay output/16 points), supporting a maximum output current of 2A and a relay life of 70000 times;

Simulation module: such as LQA000 (voltage input/4 points), LQA500 (voltage output/4 points), supporting ± 5V/± 10V/1-5V voltage range;

Pulse counter module: LQC000 (1-phase/2-phase pulse input), supports 1-point pulse counting, with a current consumption of 150mA per module.

3. Key physical and environmental parameters

Physical specifications: 7-slot mounting base (HSC-1770) with dimensions of 437 × 138.6 × 100mm and weight ≤ 1300g; the thickness of each module is uniformly 34mm (excluding some), and the tightening torque of the mounting screws is 1.0N · m (M4);

Environmental adaptability: operating temperature 0-55 ° C (temperature variation ≤ 10 ° C/hour), storage temperature -20-75 ° C; relative humidity 10-90% RH (no condensation); Seismic resistance: 10-150Hz, 10m/s ² acceleration, 8 minutes/cycle; Impact resistance: 147m/s ² peak acceleration, 11ms half sine wave;

Grounding requirements: Class D grounding (grounding resistance ≤ 100 Ω), separated from the AC panel grounding main line, with a spacing of ≥ 15m.

image.png

 Installation and commissioning process

1. Key steps and requirements for installation

(1) Preliminary preparation

Confirm installation environment: temperature 0-55 ° C, humidity 10-90% RH, no corrosive gases, dust concentration ≤ 0.1mg/m ³;

Grounding preparation: Construction shall be carried out in accordance with Class D grounding standards, with a grounding resistance of ≤ 100 Ω, and multiple cabinets shall be connected to the ground using a daisy chain connection;

Tool preparation: Use calibrated measuring instruments and compatible screwdrivers (tightening torque 1.0-1.5N · m).

(2) Installation process

Installation base: fixed on the vertical surface of the cabinet, using M5 screws (tightening torque 1.5N · m) to ensure that the insulation lining does not fall off and the metal part of the base does not touch the control cabinet;

Module assembly: Install in the order of "power module → RI/O-IF module → CPU module → option module → PI/O module", align the module with the guide rail, insert it vertically, and tighten the screws;

Battery connection: Before installing the CPU module, insert the main battery cable into the connector according to the corresponding color, and cover the battery cover tightly (hear a snap sound);

Wiring specifications:

Power cable: ≥ 2mm ² shielded twisted pair, with a distance of ≥ 100mm from the network cable;

Remote I/O cable: Select according to the transmission distance (0.75mm ² cable for long distances, ≤ 300m), with single ended grounding of the shielding layer (RI/O-IF side);

Grounding wiring: The FG terminal is connected in a daisy chain and ultimately connected to the power module FG terminal. The cable cross-section is ≥ 2mm ² (inside the cabinet)/≥ 5.5mm ² (outside the cabinet).

(3) Installation gap requirements

The distance between the cabinet and the unit is ≥ 100mm, and the distance between the sides is ≥ 50mm;

There is a requirement for no distance between modules, but one empty slot needs to be left between the high-voltage PI/O module (≥ 100VAC/48VDC) and the CPU/option/simulation module;

Cooling measures: The cabinet needs to have air vents or install fans to ensure that the intake temperature is ≤ 55 ° C.

2. Debugging core processes and tools

(1) Debugging Tools and Environment

Tool: BASE SYSTEM/S10VE (requires administrator privileges to install), supports Windows 7/10 (64 bit), PADT needs to meet 1GHz CPU, 2GB memory, 200MB free hard disk;

Connection: Connect PADT to CPU module ET1/ET2 ports via Ethernet cable, with default IP address 192.192.192.1 (ET1)/192.192.193.1 (ET2).

(2) Debugging key steps

Project creation: Start BASE SYSTEM, create a new project and configure PC numbers and comments, enable C mode requires installation of RPDP;

Network configuration: Set the IP address, subnet mask, and routing information of the CPU's built-in Ethernet or ET.net module, write them, and restart the system;

Program download: Write the program using LADDER DIAGRAM SYSTEM/HI-FLOW SYSTEM, download it to the CPU module, and confirm that there are no syntax errors;

Parameter configuration: Set PI/O installation status, partition (FIX/FREE), I/O point count, remote I/O synchronization mode, etc;

System startup: Turn the CPU RUN/STOP switch to RUN, observe that the RUN LED is constantly on, and confirm that there are no error codes through the indicator;

Function verification: Monitor memory data through MCS function, view module status and error logs through RAS menu, and verify that I/O signal acquisition and execution are normal.

3. Operations and troubleshooting

(1) Key points of daily operation and maintenance

Regular inspection: monthly check the tightness of module screws, LED status, and cable connections; Clean ventilation ducts and verify grounding resistance annually;

Backup strategy: Regularly backup CPU data, including main memory and MRAM data, through the BACKUP STORE SYSTEM, and backup files need to be stored remotely;

Module replacement: It is recommended to replace the power module within 10 years (the lifespan of the aluminum electrolytic capacitor), and replace the main battery within 5 years. When replacing, the power should be turned off;

(2) Common troubleshooting

LED fault indication:

ERR LED constantly on: CPU module has a serious error. Check the error code through the indicator (such as ECF=xxxxx) and refer to the manual for troubleshooting;

OV/OC LED on: Power module overvoltage/overcurrent, check input voltage and load current;

LINK LED not lit: Ethernet physical connection abnormality, check cable and switch ports;

Remote I/O communication failure: Confirm terminal resistance configuration (unused port connected to 150 Ω), cable shielding grounding, station number setting, and check timeout status through system registers;

Program execution exception: Check for ladder mode (RUN/STOP), PI/O module installation restrictions, and locate syntax or logic errors through error logs.

image.png


  • Basler DECS-200-2L Digital Excitation Control
  • Basler BE1-47N Voltage Phase Sequence Relay
  • Basler AEC63-7 Analog Excitation Controller 220-277V
  • Basler BE1-50/51B-107 Overcurrent Relay
  • Basler Electric BE1‑32R BE1‑E1P‑BON0F Protective Relay
  • Basler BE1-25 Solid State Time Overcurrent Relay M1EA6PA5S1F
  • Basler MVC 232 Manual Voltage Control Module 90 37000 103 60VAC 55VDC
  • Basler RAL6144-16GM Racer GigE Line Scan Camera
  • Basler SSR 63-12 Static Voltage Regulator
  • Basler BE1-51A Overcurrent Relay
  • Basler BE1-87T Solid State Protective Relay
  • Basler SR4A2B01B3A Static Voltage Regulator
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler TRR00696 Transformer 1KVA 115V
  • Basler DECS-100-B15 AVR Replacement
  • Basler BE1-27 Under-Voltage Relay
  • Basler ACA2000-50GM Interface Module
  • Basler AEC63-7 Analog Excitation Controller
  • Basler PRS 250 Veri-Sync Relay
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE1-32R Power Relay
  • Basler SR8A-2B06B3E Static Voltage Regulator
  • Basler BE1-81 O/U Frequency Relay
  • Basler BE1-51A-K2E-W6M-B1N0F Overcurrent Relay
  • Basler BE1-851 Overcurrent Relay G3A1S1 – 48-125V AC/DC
  • Basler BEI-51 Overcurrent Relay – NSN 5945-01-293-2363
  • Basler Electric L301KC Protective Relay – L301KC
  • Basler DECS-100-B15 Automatic Voltage Regulator – Generator AVR
  • Basler SR4A-2B15B3A Static Voltage Regulator – SR4A2B15B3A
  • Basler UF 312 Under Frequency Protective Module – 9094700100
  • Basler Electric MVC 232 Manual Control Module – 60VAC 55VDC 20A
  • Basler PRS 250 Veri-Sync Relay – Generator Synchronizing Relay
  • Basler DECS-100-A05 Digital Regulator Review
  • Basler AEM-2020 Analog Expansion Module Specs
  • Basler DECS-100-B15 Digital Excitation Specs
  • Basler Electric 9125600106 Regulator Component
  • Basler BE1-51A-K1E-W6M-B1N0F Overcurrent Relay
  • Basler MVC-301 MVC 300 Excitation Controller
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler 9-2849-00-101 Control Module
  • Basler BE1-51A Overcurrent Relay
  • Basler BE1-51/27R Overcurrent Relay
  • Basler BE1-51 Overcurrent Relay
  • Basler SR8A-2B15B3A Static Voltage Regulator
  • Basler BE32965001 Transformer and Timer Board
  • Basler 9174700100 EL200-7 Excitation Limiter
  • Basler BE2000E AVR Voltage Regulator
  • Basler BE1-87G Differential Relay
  • Basler BE21834001 Generator Control Module
  • Basler DECS-100-B15 AVR
  • Basler D90 96801 100 PCB Card
  • Basler XR2002F Voltage Regulator (110 VAC, 48-480 Hz)
  • Basler SR8A-2B14B3A Regulator
  • Basler 9561500100 Module
  • Basler DECS-400 BE1-11 System
  • Basler DECS-100-B15 Excitation Control
  • Basler SCP 210 Frequency Controller
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE1-32R Power Relay
  • Basler PIA2400-17GM Power Interface Adapter
  • Basler MVC 232 Manual Voltage Control Module
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler 5MW AVR Generator Voltage Regulator
  • Basler VR63-4B Voltage Regulator
  • Basler DECS-100-A05 AVR for Engine Generator
  • Basler DECS-100-B15 Automatic Voltage Regulator
  • Basler BE1-32R Directional Power Relay
  • Basler BE1-87B Differential Relay
  • Basler UFOV 260A Protective Module
  • Basler 9-2614-02-100 PCB Rev M
  • Basler DECS-100-B15 Digital AVR
  • Basler 9284900103 PS DECS-400N
  • Basler D4N3H1U Intertie Protection
  • Basler DECS-100-B15 A15 AVR
  • Basler KR4F Voltage Regulator
  • Basler BE26434 T14 Transformer
  • Basler SR8A-2B15B3A Regulator
  • Westinghouse 774B472A12 AR Relay
  • Basler DECS-100-B15 AVR
  • Basler XR2002F Regulator 110V
  • Basler SR125-E Static Regulator
  • Basler SSR 125-12 Regulator
  • Basler MOC2599 Motor Pot
  • Basler BE1-DFPR Feeder Relay
  • Basler CBS 305 Current Boost
  • Basler BE1-25 AutoSync
  • Basler MVC 300 Voltage Control
  • Basler BE3-25A AutoSync
  • Basler KR7FF Static Regulator
  • Basler 90-49000-100 Regulator
  • Basler 880 kVA Dry Type Transformer Specs
  • Basler Electric BE1-25 Sync-Check Relay Specs
  • Basler SSR 125-12 Voltage Regulator Specs
  • Basler Electric BE1-851 Overcurrent Relay Review
  • Basler Electric 149D930G02 Control Sub-Assembly
  • Basler Electric BE1-81O/UT Frequency Relay Specs
  • Basler Electric BE1-51/27C Overcurrent Relay
  • Basler Electric 149D956G02 Industrial Component
  • Basler Electric BE1-51A Overcurrent Relay Specs
  • Basler Electric BE1-40Q Loss of Excitation Relay
  • Basler DECS-200 Excitation Control System
  • Basler DECS-200 Voltage Regulator 56-277V AC / 125V DC
  • Basler BE1-87T Transformer Differential Relay
  • Basler RDP-110-S1 Protection Relay
  • Basler BE1-700V Digital Protective Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler DECS-300 Digital Excitation Control
  • Basler DECS-200 Digital Excitation Control
  • Basler DECS-200-1C Excitation Control System
  • Basler DECS-200-1L Digital Excitation Control
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-200-1C Digital Excitation Controller
  • Basler Electric DECS125-15 Excitation Control with Power Module
  • Basler Electric BE1-87G Differential Relay
  • Basler Electric BE1-11 Protection System I5A3M2P2N0EA00
  • Basler Electric DECS-200-1C Excitation Control System
  • Basler Electric BE1-11g Generator Protection Relay
  • Basler Electric DECS 125-15-B2C1 V2.0.9 Excitation Control
  • Basler Electric BE1-81O/UT3ED1JA7N2F Frequency Relay
  • Basler Electric BE1-81O/UT3EE1YB7N1F Frequency Relay
  • Basler Electric DECS-200-1L Digital Excitation Control System
  • Basler DECS125-15-B2C1 Excitation Control
  • Basler 9507900205 SSR Retrofit Voltage Regulator
  • Basler BE2000E Digital Voltage Regulator
  • Basler BE1-GPS Generator Protection System
  • Basler DECS-250-CN1CN1N Digital Excitation Control
  • Basler DGC-2020 Genset Controller
  • Basler BE1-81O UT3ED1LA7N0F Frequency Relay (Variant)