Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

HITACHI S10VE Programmable Controller

来源: | 作者:FAN | 发布时间 :2025-12-30 | 481 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

HITACHI S10VE Programmable Controller

Usage Notes

■ Installation

The programmable controller employs electronic circuit and processor technologies. Note the following in particular:

● When constructing a system, make sure that conditions including the maximum rating, operating power supply voltage range, heat dissipation characteristics, and installation conditions are within the guaranteed operating range described in this manual. Hitachi bears no responsibility for failures or accidents that arise from use of the product outside the guaranteed range.

Even when using the product within the guaranteed range, you must consider the predicted failure rate and failure mode of the product. You can then implement system measures such as making the system failsafe so that operation of the Hitachi product will not cause personal injury, fire, and other consequential damage.

The Programmable Controllers ( ((PCs^{#})) ) in which the CPU unit and PI/O units are installed are neither fireproof, dustproof, nor waterproof. Install the PCs in steel cabinets that are fireproof, dustproof, and waterproof (see Figure 1-1).

#: PCs means the programmable controllers in their entirety including the CPU unit and PI/O units.

● Use the S10VE in an environment that is within the specifications explained in Chapter 3. To ensure long-term stable operation, we recommend that you use the product at room temperature and normal relative humidity (15 to 35°C and 45 to 85% RH). Using the product in a high-temperature or high-humidity environment or an environment where the temperature varies widely over the course of a day leads to a reduced service life.

image.png

■ Output module

You must provide a short-circuit protection fuse in the load power supply circuit of the output module. Use fuses with the correct load rating. Using the wrong fuse might result in damage to the PCB or housing if the load shortcircuits.

image.png

■ Grounding

● Panel grounding specifications

The PCs panel that incorporates the S10VE must be welded to the steel frame of a building that provides at least class D grounding with the ground resistance of 100Ω or less.

Conditions for grounding to the steel frame of a building

- The steel frame is welded together

- The grounding between the earth and the steel frame meets the criteria for class D

If this is not achievable, ground the PCs panel by connecting it to a grounding rod driven into the earth. This provides a low grounding resistance that prevents surrounding noise from entering the PCs.

image.png

■ Noise

Do not install the S10VE in or near a panel to which a high-voltage device (such as an inverter) is mounted. If this is unavoidable, use a shielding plate to shield the CPU unit, PI/O units, and cabling from electromagnetic and electrostatic induction.

■ Emergency stop circuit

A partial failure can affect the entire system. Provide an emergency stop circuit as an external circuit. Do not incorporate the emergency stop circuit into programs run on the programmable controller.

■ Disassembling modules

Do not disassemble the modules.

■ Removing/inserting modules

You must turn off the power before removing or inserting a module. To prevent module damage due to static electricity, discharge any static electricity from your body before touching the equipment.

■ Installation of new equipment

When peripheral equipment is added or replaced, check the following aspects of the power supply and grounding:

Power supply

Inspect the power supply voltage and waveform.

- Has the voltage dropped?

- Is there any noise in the power cable?

image.png

1. Usage Notes

● Grounding

- Make sure that the S10VE does not share its ground cable with other equipment.

- Make sure that no power or lead cables are positioned too closely to a signal cable (such as a remote I/O cable).

image.png

2. Overview

2.1 Overview of the system

The S10VE is a programmable controller suited for a wide range of applications from simple condition control to complex arithmetic control. It is capable of simultaneously executing ladder logic, HI-FLOW, and C languages.

2.2 System configuration

2.2.1 Example system configuration

Figure 2-1 shows an example configuration of an S10VE system.

An S10VE system is made up of a CPU unit, PI/O units, and peripherals.

By installing option modules (OD.RING, D.NET, J.NET, FL.NET, ET.NET) in the CPU unit, an S10VE system can connect to an optical communication network and various other optional networks.

By installing a remote I/O interface module (hereafter RI/O-IF module) in the CPU unit, the system can connect to HSC-1000 and HSC-2100 PI/O units using remote I/O lines. A given system can incorporate both HSC-1000 and HSC-2100 PI/O units.

image.png

2.2.2 CPU unit configuration

An S10VE system is made up of a mount base, power supply module, RI/O-IF module, CPU module, and PI/O modules. The mount base incorporates one PS slot (a dedicated slot for the power supply module), one IF slot (a dedicated slot for the RI/O-IF module), one CPU slot (a dedicated slot for the CPU module), and seven I/O slots. The power supply module and CPU module are mandatory components of an S10VE system. Installation of an RI/O-IF module, option modules, and PI/O modules is optional.

image.png


2.2.3 Configuration of remote I/O communication

The S10VE system can use an RI/O-IF module to perform remote I/O communication on a maximum of two lines (see Figure 2-3).

The maximum length of each line is 300 m by remote I/O cable alone, extendable to a maximum of 3.3 km using remote I/O optical adapters. This length of 3.3 km is three optical cables of 1 km each, plus the 300 m achievable by remote I/O cable.

You can use HSC-1000 and HSC-2100 PI/O units in the same system.

image.png


2.3 System components

2.3.1 Components of CPU unit

Table 2-1 shows the components that make up the CPU unit.

The specifications and functions of the mount base, power supply module, CPU module, and RI/O-IF module are explained in the following chapters:

- Chapter 3: Specifications

- Chapter 5: Part Names and Functions

For details about the specifications and functions of the option modules, see the following manuals:

- S10VE User's Manual Option OD.RING (LQE510-E) (manual number SEE-1-101)

- S10VE User's Manual Option J.NET (LQE540-E) (manual number SEE-1-102)

- S10VE User's Manual Option D.NET (LQE770-E) (manual number SEE-1-103)

- S10VE User's Manual Option FL.NET (LQE702-E) (manual number SEE-1-104)

- S10VE User's Manual Option ET.NET (LQE260-E) (manual number SEE-1-105)

For details about the specifications and functions of the PI/O modules, see the following manual:

- S10mini Hardware Manual I/O Modules (manual number SME-1-114)

image.png

image.png

2.3.2 PI/O units and peripherals

A PI/O unit is made up of an HSC-1000 module and an HSC-2100 module. For details, see the following manuals:

- S10mini Hardware Manual I/O Modules (manual number SME-1-114)

- S10mini Hardware Manual D.Station (manual number SME-1-119)

- HSC-2100 Hardware Manual I/O Modules (manual number SME-1-126)

You can also connect a D.NET optical adapter as a peripheral. For details, see the following manual:

- S10mini Hardware Manual OPT.D-NET (manual number SME-1-120)

2.3.3 PADT

PADT (Programming and Debugging Tools) is a programming tool used to make, test, run, and troubleshoot application programs for the S10VE system. The PADT is a personal computer with the required software such as BASE SYSTEM/S10VE installed.

The required specifications for the personal computer that serves as the PADT are as follows:

- 1 GHz or faster CPU

- At least 2GB RAM

- At least 200 MB free hard disk space

- A display resolution of at least 1,366 × 768 (FWXGA)

- Microsoft® Windows® 7 (64bit) operating system or Microsoft® Windows® 10 (64bit) operating system

image.png

Detailed explanation of core hardware components

1. Core module specifications and functions

Module type, model, key parameters, core functions, installation requirements

CPU module LQP600 has a maximum of 2048 I/O points; Main memory 128MB; PI/O memory (bit area 2MB/word area 1MB); Processing speed: bit operation 9.4ns/step system control core, supports ladder diagram/HI-FLOW/C language parallel execution; Built in Ethernet ports (ET1/ET2); Install resources such as event registers and data registers in dedicated CPU slots; Need to connect the main battery (HDC5200) in advance; Avoid direct proximity to high-voltage modules

Power module LQ410 input: 100-120VAC/100-110VDC; Output: 5VDC/10A; The power of 144VA (AC)/132W (DC) provides stable DC power supply for the system; Equipped with overcurrent (OC) and overvoltage (OV) protection; Support the installation of power status LED indicators in PS dedicated slots; Reliable grounding is required; Power switch start stop interval ≥ 5 seconds

RI/O-IF module LQE950 2-channel remote I/O cable; Communication speed 768kbps; Maximum of 12 PI/O units per channel; Implement remote I/O expansion with a transmission distance of ≤ 300m; Support 100 Ω/150 Ω terminal resistor configuration; Provide PCsOK signal output installed in IF dedicated slot; Remote I/O cables require shielded twisted pair cables; Unused ports require a 150 Ω resistor to be connected

Option module - OD.RING LQE510-E duplex ring network; Maximum 64 nodes; Shared data: I/O 4096 points/word data 4096 words cross CPU unit memory data sharing; Simplified line fault analysis installation in I/O slots; Optical connectors require insulation materials for protection

Option module - ET.net LQE260-E supports TCP/IP/UDP/IP; Compatible with 10BASE-T/100BASE-TX; Maximum 1024 node Ethernet communication extension; Adapting to industrial network integration requires configuring IP addresses and routing information; Prioritize using the ET2 port for communication with PADT

2. Classification and specifications of PI/O modules

The PI/O module is divided into three categories: digital I/O, analog I/O, and pulse counter, which are suitable for different signal acquisition and execution requirements:

Digital input modules: such as LQX200 (12-24VDC/16 points), LQX350 (12-24VDC/64 points), support contact input, current consumption 80-170mA/module;

Digital output module: such as LQY200 (transistor output/16 points), LQY100 (relay output/16 points), supporting a maximum output current of 2A and a relay life of 70000 times;

Simulation module: such as LQA000 (voltage input/4 points), LQA500 (voltage output/4 points), supporting ± 5V/± 10V/1-5V voltage range;

Pulse counter module: LQC000 (1-phase/2-phase pulse input), supports 1-point pulse counting, with a current consumption of 150mA per module.

3. Key physical and environmental parameters

Physical specifications: 7-slot mounting base (HSC-1770) with dimensions of 437 × 138.6 × 100mm and weight ≤ 1300g; the thickness of each module is uniformly 34mm (excluding some), and the tightening torque of the mounting screws is 1.0N · m (M4);

Environmental adaptability: operating temperature 0-55 ° C (temperature variation ≤ 10 ° C/hour), storage temperature -20-75 ° C; relative humidity 10-90% RH (no condensation); Seismic resistance: 10-150Hz, 10m/s ² acceleration, 8 minutes/cycle; Impact resistance: 147m/s ² peak acceleration, 11ms half sine wave;

Grounding requirements: Class D grounding (grounding resistance ≤ 100 Ω), separated from the AC panel grounding main line, with a spacing of ≥ 15m.

image.png

 Installation and commissioning process

1. Key steps and requirements for installation

(1) Preliminary preparation

Confirm installation environment: temperature 0-55 ° C, humidity 10-90% RH, no corrosive gases, dust concentration ≤ 0.1mg/m ³;

Grounding preparation: Construction shall be carried out in accordance with Class D grounding standards, with a grounding resistance of ≤ 100 Ω, and multiple cabinets shall be connected to the ground using a daisy chain connection;

Tool preparation: Use calibrated measuring instruments and compatible screwdrivers (tightening torque 1.0-1.5N · m).

(2) Installation process

Installation base: fixed on the vertical surface of the cabinet, using M5 screws (tightening torque 1.5N · m) to ensure that the insulation lining does not fall off and the metal part of the base does not touch the control cabinet;

Module assembly: Install in the order of "power module → RI/O-IF module → CPU module → option module → PI/O module", align the module with the guide rail, insert it vertically, and tighten the screws;

Battery connection: Before installing the CPU module, insert the main battery cable into the connector according to the corresponding color, and cover the battery cover tightly (hear a snap sound);

Wiring specifications:

Power cable: ≥ 2mm ² shielded twisted pair, with a distance of ≥ 100mm from the network cable;

Remote I/O cable: Select according to the transmission distance (0.75mm ² cable for long distances, ≤ 300m), with single ended grounding of the shielding layer (RI/O-IF side);

Grounding wiring: The FG terminal is connected in a daisy chain and ultimately connected to the power module FG terminal. The cable cross-section is ≥ 2mm ² (inside the cabinet)/≥ 5.5mm ² (outside the cabinet).

(3) Installation gap requirements

The distance between the cabinet and the unit is ≥ 100mm, and the distance between the sides is ≥ 50mm;

There is a requirement for no distance between modules, but one empty slot needs to be left between the high-voltage PI/O module (≥ 100VAC/48VDC) and the CPU/option/simulation module;

Cooling measures: The cabinet needs to have air vents or install fans to ensure that the intake temperature is ≤ 55 ° C.

2. Debugging core processes and tools

(1) Debugging Tools and Environment

Tool: BASE SYSTEM/S10VE (requires administrator privileges to install), supports Windows 7/10 (64 bit), PADT needs to meet 1GHz CPU, 2GB memory, 200MB free hard disk;

Connection: Connect PADT to CPU module ET1/ET2 ports via Ethernet cable, with default IP address 192.192.192.1 (ET1)/192.192.193.1 (ET2).

(2) Debugging key steps

Project creation: Start BASE SYSTEM, create a new project and configure PC numbers and comments, enable C mode requires installation of RPDP;

Network configuration: Set the IP address, subnet mask, and routing information of the CPU's built-in Ethernet or ET.net module, write them, and restart the system;

Program download: Write the program using LADDER DIAGRAM SYSTEM/HI-FLOW SYSTEM, download it to the CPU module, and confirm that there are no syntax errors;

Parameter configuration: Set PI/O installation status, partition (FIX/FREE), I/O point count, remote I/O synchronization mode, etc;

System startup: Turn the CPU RUN/STOP switch to RUN, observe that the RUN LED is constantly on, and confirm that there are no error codes through the indicator;

Function verification: Monitor memory data through MCS function, view module status and error logs through RAS menu, and verify that I/O signal acquisition and execution are normal.

3. Operations and troubleshooting

(1) Key points of daily operation and maintenance

Regular inspection: monthly check the tightness of module screws, LED status, and cable connections; Clean ventilation ducts and verify grounding resistance annually;

Backup strategy: Regularly backup CPU data, including main memory and MRAM data, through the BACKUP STORE SYSTEM, and backup files need to be stored remotely;

Module replacement: It is recommended to replace the power module within 10 years (the lifespan of the aluminum electrolytic capacitor), and replace the main battery within 5 years. When replacing, the power should be turned off;

(2) Common troubleshooting

LED fault indication:

ERR LED constantly on: CPU module has a serious error. Check the error code through the indicator (such as ECF=xxxxx) and refer to the manual for troubleshooting;

OV/OC LED on: Power module overvoltage/overcurrent, check input voltage and load current;

LINK LED not lit: Ethernet physical connection abnormality, check cable and switch ports;

Remote I/O communication failure: Confirm terminal resistance configuration (unused port connected to 150 Ω), cable shielding grounding, station number setting, and check timeout status through system registers;

Program execution exception: Check for ladder mode (RUN/STOP), PI/O module installation restrictions, and locate syntax or logic errors through error logs.

image.png


  • B&R X20IF1072 CAN Bus Interface Module
  • Mitsubishi OSE253S2 Rotary Encoder
  • Mitsubishi NV630-SW 4P 500A Earth Leakage Breaker
  • Euchner MGB-L1B-PNA-R-121857 Safety Switch
  • Honeywell 900A01-0102 Analog Input Module
  • OMRON C500-ID219 Input Unit
  • Westinghouse EL3030R Current Limiter
  • CLA-2 3L Electric Lubrication Pump
  • Proface GP2501-TC41-24V HMI
  • Omron KM-N1-FLK Small Power Monitor
  • HPM 1D703-0040 Command 9000 Console Card
  • Siemens 3RW5074-6AB14 SIRIUS Soft Starter
  • Genie 75032 Limit Switch
  • OMRON C200H-SP001 Space Module
  • OMRON C200H-PS211 Power Supply Unit
  • OMRON C200H-OC222 Relay Output Unit
  • Keyence KV-8000SO 4221 CPU Module
  • Cincinnati Milacron 3-542-1079A Circuit Board
  • Beckhoff EL3124 Analog Input EtherCAT Terminal
  • KRONES BWU1703 0900853537 ASi PROFIBUS Gateway
  • Radio Energie RE0444 R1S 0.06 CA Tachogenerator
  • Mitsubishi GT1685M-STBA GOT1000 HMI
  • Siemens 6GK7342-5DA03-0XE0 CP 342-5 PROFIBUS
  • Allen Bradley 8520-PX-ASM3-EXEC2-63M Servo Module
  • Delta AH10PM-5A Programmable Controller
  • Siemens 3TK2805-0BB4 Safety Contactor Combination
  • EUCHNER HBA-079827 Pendant Station
  • CLC-2 4L PLC Lubrication Pump
  • KEYENCE GS-51P5 Safety Switch
  • AB 442G-MABH-R Safety Switch
  • GE Fanuc VersaMax PLC Module Set
  • Siemens 6ES7214-1HF40-0XB0 CPU 1214FC
  • Microchip DSPIC30F4011-30I/P DSC
  • FANUC A20B-2102-0081 I/O Link Module
  • Endress Hauser CLS15-B1M2A Conductivity Sensor
  • B&R 3AM050.6 Analog I/O Module
  • Fanuc A16B-2201-0320 MAIN-B CPU Board
  • Pilz 475650 PNOZ 1 Safety Gate Relay
  • Omron NSH5-AL001 Handheld HMI Terminal
  • Allen-Bradley 1756-OF8 Analog Output 8 Ch
  • Siemens 6SL3210-1SE31-0AA0 45kW Power Module
  • PMA TB45-110-00000-000 Temperature Limiter
  • PSR-SCP-24DC-ESD-5x1-1x2-300 Safety Relay
  • Pilz 774140 PZE 9 24V AC Safety Relay
  • Telemecanique TSXRKN82F 8 Slot Rack
  • Mitsubishi R16CPU iQ-R PLC CPU
  • Mitsubishi A2ACPU-R21-S1 PLC CPU
  • Omron NX-AD4208 Analog Input Unit
  • Schneider LMC802CAA10000 PacDrive 3 Controller
  • Reliance Electric 0-51874 Static Sequence Card
  • Pilz 787310 PNOZ X3P C Safety Relay
  • B&R X20CP1684 CPU Module
  • Siemens 6SN1145-1BB00-0FA1 Power Module
  • Beckhoff EL3174 Analog Input EtherCAT Terminal
  • CLC-2P 4L PLC Lubrication Pump System
  • Omron CJ1W-DA08C Analog Output Unit
  • Metso Automation D201776 ACN PO DC PLC Control Server Computer
  • GE AT868 AquaTrans Ultrasonic Flow Transmitter
  • ABB PFSA107-Z42 DTU Stressometer Digital Transmission Unit
  • ABB PFSA240 3BSE073476R1 Roll DC Supply Unit
  • Fanuc A16B-2201-0320 CPU MAIN Board
  • Pilz 475650 PNOZ 1 Safety Gate Relay
  • Omron NSH5-AL001 HMI Interface Unit
  • Allen-Bradley 1756-OF8 Analog Output Module
  • Siemens 6SL3210-1SE31-0AA0 Power Module 45kW
  • PMA TB45-110-00000-000 Temperature Limiter
  • PSR-SCP-24DC-ESD-5x1-1x2-300 Safety Relay
  • Pilz 774140 PZE 9 Safety Relay
  • Telemecanique TSXRKN82F PLC Rack Chassis
  • Mitsubishi R16CPU PLC CPU Module
  • OMRON C500-PS223-E Power Supply Module
  • Siemens 3VL4731-1DC36-0AA0 Circuit Breaker
  • Siemens 7ML5201-0EA0 Ultrasonic Level Transmitter
  • OMRON NQ3 NQ5 Touch Panel HMI
  • OMRON CJ1W-AD081-V1 Analog Input Module
  • OMRON NJ301-1100 Machine Automation Controller
  • B&R X20BC00G3 EtherCAT Bus Controller
  • Schneider ATV212HD22N4S Variable Speed Drive
  • B&R 8B0C0320HW00.002-1 Power Supply Module
  • Mitsubishi OSA105S2A Incremental Rotary Encoder
  • Pilz 777514 PNOZ XV3P Safety Relay
  • Gould AS-884A-111 Modicon 884 Controller
  • Siemens 6SC6130-0FE00 SIMODRIVE Control Card
  • Omron CV500-PS221 PLC Power Supply Module
  • ABB CM577-ETH AC500 PLC Ethernet Module
  • Omron NX-SIH400 Safety Input Unit NX Series
  • Omron NJ501-1300 Machine Automation Controller
  • Siemens 3VT8563-2AA03-2KA2 Molded Case Breaker
  • Pilz PNOZ m1p ETH 773103 Safety Controller
  • Omron CJ1H-CPU66H-R CJ1 Series CPU Module
  • ASI ASI533-S00 PLC Module S1
  • Mitsubishi AJ71C21-S1 Serial Module
  • Keyence IX-1000 Laser Sensor Amplifier
  • Siemens 6SN1145-1AA01-0AA1 Power Module
  • Siemens 3VA2340-5HL32-0AA0 MCCB 400A
  • Mitsubishi OSA104S Absolute Encoder
  • Siemens 6ES7350-1AH03-0AE0 FM 350-1 Counter
  • Siemens 6SE7038-6EK84-1JC2 IGD8 Gate Driver
  • Eaton EASY819-AC-RC Programmable Relay
  • Omron CPM1A-40CDT-D PLC 24V DC
  • Omron NA5-12W101B-V1 12-inch Programmable Terminal
  • Siemens 6ES7331-7KF02-0AB0 Analog Input SM 331
  • Moxa PTC-101-S-SC-HV Photoelectric Converter
  • Fanuc A20B-3300-0031 CNC Control Circuit Board
  • OMRON NA5-7W001B-V1 Programmable Terminal HMI
  • Parker AH385851U002 590C DC Drive Power Board
  • ABB 3BSE040662R1 AI830A Analog Input Module
  • DOLD BF9250.01/001 Solid State Relay
  • Siemens 6ES7331-7KF02-0AB0 SIMATIC S7-300 SM 331
  • ABB 07AC91 I6 GJR5252300R3101 Advant Controller 31
  • Schneider HMIST6500 Touch Screen HMI
  • Phoenix IL PN BK DI8 DO4 2TX-PAC Bus Coupler
  • NLTECH NL8060AC21-21D 8.4 inch LCD Display
  • Mitsubishi A2NCPU-P21 CPU Module A2NCPUP21
  • 1841-PL1-B-LH-ES Pressure Controller
  • Mitsubishi GT2512-STBA GT2512-STBD HMI
  • Cosel PJA600F-24 24V 600W Power Supply
  • B&R X67DM1321 Digital Mixed Module
  • Fanuc A16B-1310-0010 Power Supply Unit
  • Festo VABF-S4-1-V2B1-C-VH-20 Vacuum Generator
  • Mitsubishi A3ACPUP21 A3ACPU-P21 CPU
  • Mitsubishi Mazak PD14B-1 Power Supply
  • Siemens 6SY7000-0AC80 Module
  • PILZ 774400 PDZ Safety Relay
  • Mitsubishi A1SX81 Digital Input Module
  • Asyst Gasonics R94-1163 Controller 112671
  • Cincinnati Milacron 3 545 1000A Card
  • Siemens 6DD1607-0AA2 UPS Module