SINAMICS SIRIUS series switchgear

来源: | 作者:FAN | 发布时间 :2025-11-26 | 347 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

SINAMICS SIRIUS series switchgear

Contactor Relay

Contactor relay is a key component for achieving "signal amplification and circuit switching" in industrial control. The document focuses on the 3RH2 and 3TH4 series, which complement each other in positioning and adapt to different scene requirements.

3RH2 series (size S00, compact)

(1) Product positioning and core features

Specially designed for compact control cabinets, with a size of only S00 (45mm wide), supporting 4-pole, 8-pole, and 4-pole latch types, it is the "basic contactor relay" of Siemens SIRIUS series, with core advantages including:

Multiple terminal selection: screw terminals (traditional wiring) and spring terminals (push in, tool free quick wiring) are optional;

Climate adaptation: operating temperature -25~+60 ℃, storage temperature -55~+80 ℃, suitable for use in high/low temperature industrial environments (such as cold chain workshops and metallurgical plants);

Safety compliance: Compliant with the IEC 60529 finger protection standard, both the basic unit and auxiliary switch have "forced guide contacts" (Appendix L of IEC 60947-5-1), which can be used for safety related applications (such as emergency stop circuits).

(2) Detailed product classification and model analysis

According to their functions and application scenarios, the 3RH2 series can be divided into four categories, with model codes following a fixed logic ("3RH2 @ @ - @ @ @ @ 0- @ @ @ @"). The meanings and examples of each field are as follows:

Product type Pole number Terminal type Coil voltage Model example Key characteristics Corresponding page numbers

Standard contactor relay 4-pole screw terminal 24V AC (50/60Hz) 3RH2140-1AB00 basic model, 4NO contact, terminal identification in accordance with EN 50011 5/12, 5/13

Standard contactor relay 8-pole spring terminal 230V AC (50/60Hz) 3RH2244-2AP00 8-pole (4NO+4NC) with permanently installed auxiliary switches 5/12, 5/13

Lock type contactor relay 4-pole screw terminal 24V DC 3RH2440-1BB40 requires external signal unlocking, suitable for "hold type circuit" (such as gate control) 5/12, 5/13

Coupling contactor relay (PLC compatible) 4-pole screw terminal 24V DC 3RH2140-1HB40 low power consumption (2.8W), wide coil working range (0.7~1.25 × Us), compatible with PLC solid-state output 5/14, 5/15

Railway application type contactor relay 4-pole screw terminal wide voltage coil 3RH2122-2K.40 coil voltage range extension, anti vibration (AC operation 11.4g/5ms) 4/64

(3) Key technical parameters (detailed explanation by dimension)

Technical parameters are the core basis for selection, and the document specifies the electrical, mechanical, and environmental performance of the 3RH2 series through tables and charts. The core data is as follows:

Size and Installation:

Component type Terminal type Width x Height x Depth (mm) Installation method

Basic unit screw terminal 45 × 58 × 73 fixed with screws/TH 35 rail clamp

Basic unit spring terminal 45 × 70 × 73 fixed with screws/TH 35 rail clamp

Basic unit+front auxiliary switch screw terminal 45 × 58 × 117 TH 35 rail card installation

Basic unit+functional module spring terminal 45 × 70 × 147 TH 35 rail card installation

Electrical performance:

Insulation voltage (Ui, pollution level 3): 690V, suitable for medium and high voltage industrial circuits;

Surge withstand voltage (Uimp): 6kV, strong resistance to grid surges;

Coil power consumption (cold state, 1.0 × Us):

AC 50Hz: Close at 37VA/power factor 0.8, maintain at 5.7VA/power factor 0.25;

AC 60Hz: closed 33VA/power factor 0.75, maintained 4.4VA/power factor 0.25;

DC: closed=hold, 4.0W (low power consumption suitable for battery powered scenarios);

Contact reliability: Contact stability at 17V/1mA (IEC 60947-5-4), fault frequency<10 ⁻⁸ (<1 fault per 100 million operations).

Lifespan and Durability:

Component type Mechanical life (10000 cycles) Electrical life (AC-15/230V, 10000 cycles) Remarks

Basic unit 3000 100 without auxiliary accessories, randomly switched (asynchronous phase)

Basic unit+auxiliary switch 1000 50 Auxiliary switch is front mounted, 4-pole maximum expansion

Solid state compatible auxiliary switch 500 30 compatible with solid-state circuits, without forced guiding contacts

(4) Accessory System and Application Expansion

The 3RH2 series supports a variety of accessories, which can achieve functional upgrades and convenient maintenance. The core accessories are as follows:

Accessory type, model, example, function description, installation method, corresponding page number

Auxiliary switch 3RH2911-. NF. 1-pole/2-pole, front/side mounted, expansion contact quantity (maximum 4-pole) snap fit installation 3/89, 3/99

Functional modules 3RA281., 3RA283. Direct start, star delta start module, integrated control logic front mounted 3/107

Surge suppressor 3RT2916-4MA10 RC component/varistor/diode, suppression coil disconnect surge front mounted, with LED indication 3/104, 3/105

Additional load module 3RT2916 increases allowable residual current (compatible with high residual current PLC output) Front mounted 3/121

Anti misoperation cover plate 3RT2916-4MA10 sealed terminal, preventing accidental contact or tampering with snap on cover 3/119

(5) Selection and ordering precautions

Model coding logic: It is necessary to clarify "number of poles → contact type (NO/NC) → terminal type → coil voltage → special version", for example, in "3RH2122-1AB00", "22" represents 2NO+2NC, "1" represents screw terminal, and "AB00" represents 24V AC coil;

Minimum order unit (PU): 1 unit (single unit), discounts are available for partial bulk orders (please consult Siemens sales);

Special requirements: Railway application type (wide voltage coil) and latch type require separate confirmation of delivery time, non-standard voltage (such as 48V DC) can be customized according to the "3/75 page" requirements.


2. 3TH4 series (8-pole/10 pole, multi circuit type)

(1) Product positioning and core differences

Unlike the "compact" positioning of the 3RH2 series, the 3TH4 series focuses on multi pole numbers and high reliability, designed specifically for "multi loop centralized control" scenarios (such as complex motor control and machine tool hydraulic systems). The core differences are reflected in:

More poles: Only 8 poles (3TH42) and 10 poles (3TH43), supporting more independent circuit switching;

More stable structure: greater depth (AC type 97mm, DC type 130mm), stronger impact resistance (AC operation 12g/5ms);

Single terminal type: only screw terminals (M3.5), suitable for connecting large cross-sectional wires (up to 4mm ²);

Narrow environmental adaptability: operating temperature -25~+55 ℃ (5 ℃ lower than 3RH2), more suitable for industrial environments at room temperature.

(2) Product classification and key parameters

Product classification: Divided by pole number into 3TH42 (8 poles) and 3TH43 (10 poles), both support AC/DC coils. The model examples are as follows:

Series pole control voltage terminal type model example corresponding page number

3TH42 8-pole 230V AC (50Hz) screw terminal 3TH4280-0AP0 5/20

3TH42 8-pole 24V DC screw terminal 3TH4280-0BB4 5/20

3TH43 10 pole 230V AC (50Hz) screw terminal 3TH4310-0AP0 5/21

3TH43 10 pole 24V DC screw terminal 3TH4310-0BB4 5/21

Core technical parameters:

Insulation voltage (Ui): 690V, impulse withstand voltage (Uimp): 8kV (2kV higher than 3RH2);

Coil power consumption (AC 50Hz, cold state): closed 68VA/power factor 0.82, maintaining 10VA/power factor 0.29;

Contact current capacity (AC-15): 10A at 230V, 6A at 400V, 4A at 500V, 2A at 690V;

Mechanical lifespan: 30 million cycles (basic unit), electrical lifespan (AC-15/230V): 3.6 million cycles (3 times higher than 3RH2).

(3) Accessories and Special Features

Surge Suppressor: 3TX7402 series, including diodes (24~250V DC, 3TX7402-3A), varistors (24~600V AC, 3TX7402-3G), RC components (24~600V AC, 3TX7402-3R), directly installed on coil terminals to suppress disconnection surges;

Delay device: 3TX4180-0A (ON delay, 0.1~5s), suitable for circuits that require delayed start (such as fan soft start);

Railway application type: coil voltage range extension (0.85~1.1 × Us), model such as 3TH42. -0B., needs to be ordered according to the requirements on page 4/66.

image.png

Coupling relay

Coupling relays mainly achieve electrical isolation and signal level matching between control circuits and load circuits. The document covers three major series: 3RQ2, 3RQ3, and LZS/LZX, corresponding to "industrial shell type, narrow design type, and plug-in customized type", meeting different installation spaces and customization requirements.

3RQ2 series (industrial shell type, 22.5mm)

(1) Product positioning and core advantages

Replacing the traditional 3RS18 series, designed specifically for industrial grade signal coupling, with a 22.5mm wide industrial casing (titanium gray) that is visually consistent with the SIRIUS series. The core advantages include:

Wide voltage compatibility: 24~240V AC/DC coils, no need to distinguish between AC and DC, reducing inventory types;

High contact reliability: Some models use "hard gold-plated contacts" (AgNi+Au), which provide stable contact in low current (≥ 1mA) and low voltage (≥ 17V) scenarios;

Easy to maintain design: detachable terminals (screw/spring type), no need to disconnect wires to replace terminals; TOP wiring (front wire entry) increases wiring efficiency by 30%.

(2) Product Classification and Technical Parameters

Product classification: Divided by the number of contacts into 1 conversion (CO), 2 conversion, and 3 conversion. Model examples and parameters are as follows:

Number of contacts, terminal type, contact material, coil voltage range, model example, working temperature, insulation voltage, corresponding page number

1. Conversion screw terminal AgSnO2 24~240V AC/DC 3RQ2000-1AW00-40~+60 ℃ 300V 5/26

2 Conversion Spring Terminal AgSnO2 24~240V AC/DC 3RQ2000-2BW00-40~+60 ℃ 300V 5/26

3 conversion screw terminals AgNi+Au 24~240V AC/DC 3RQ2000-1CW01-40~+60 ℃ 300V 5/26

Electrical performance:

Load current (AC-15/250V): 3A;

Load current (DC-13/24V): 1A;

Mechanical lifespan: 10 million cycles, electrical lifespan (AC-15/230V): 100000 cycles;

Protection level: IP20 (front), preventing solid foreign objects from entering.

(3) Accessories and Selection

Core accessories:

Accessory type, model, example, function description, ordering unit, corresponding page number

Detachable terminal 3ZY1122-1BA00 2-pole, screw terminal, maximum 4mm ² wire 6 units 5/26

Hinge cover 3ZY1450-1AB00 titanium gray, no terminal identification, protective terminal 5 units 5/26

Code pin 3ZY1440-1AA00 mechanical code terminal to prevent accidental insertion of 12 units 5/26

Special screwdriver 3RA2908-1A 3.0 × 0.5mm, designed for dismantling spring type terminals with 1 unit 5/26

Selection precautions: It is necessary to clarify the "number of contacts → terminal type → contact material → coil voltage", for example, "3RQ2000-2CW01" represents "2 conversion contacts, spring terminals, hard gold-plated contacts, 24-240V AC/DC coils".

3RQ3 series (narrow design type, 6.2mm)

(1) Product positioning and core innovation

Specially designed for high-density control cabinets, with a width of only 6.2mm (1/4 of traditional coupling relays), it is a representative of Siemens' "miniaturized coupling relays", with core innovations including:

TOP wiring+spring type terminal: front wire entry, tool free wiring, suitable for batch installation (such as automated production line control cabinets);

Multiple output types: Relay output (non plug/unplug) and semiconductor output are optional, suitable for different switching frequency requirements;

Integrated protection function: reverse polarity protection, EMC arc suppression diode, reducing the use of external protection components.

(2) Product Classification and Technical Parameters

Product classification: Divided into 3 categories based on output type, the core differences and parameters are as follows:

Output Type Model Series Contact/Output Characteristics Coil Voltage Range Operating Temperature Insulation Voltage Corresponding Page Number

Relay output (non plug and play) 3RQ3018/3RQ3038 1 conversion contact, AgSnO2/hard gold-plated 24~230V AC/DC -25~+60 ℃ 300V 5/34

Relay output (plug-in type) 3RQ3118 1 conversion contact, can quickly replace relay 24~230V AC/DC -25~+60 ℃ 300V 5/34

Semiconductor output (non plug and play) 3RQ3050/3RQ3070 contactless, 1mA~5A current capacity 11~30V DC/110~230V AC/DC -25~+60 ℃ 300V 5/34

Key performance differences:

Relay output: with a mechanical lifespan of 10 million cycles, suitable for switching between medium and low frequencies (≤ 1000 cycles/hour);

Semiconductor output: No mechanical wear, suitable for high-frequency switching (≤ 10000 times/hour), no contact bounce and noise.

(3) Accessories and Application Scenarios

Core accessories:

Accessory type, model, example, function description, ordering unit, corresponding page number

Isolation board 3RQ3900-0A electrically isolates different voltage circuits to prevent crosstalk of 10 units 5/35

Connect comb 3RQ3901-0A (2-pole) to the same potential terminal, with a current capacity of 6A 10 units 5/35

Label 3RQ3902-0A (5 × 5mm) Terminal Identification, White Handwritten 2000 units 5/35

Replace relay module 3TX7014-7BM00 with 3RQ3118, AgSnO2 contacts 15 units 5/35

Typical application scenarios:

Relay output: signal coupling between PLC and contactor (such as motor start stop control);

Semiconductor output: sensor signal amplification (such as photoelectric switch → PLC input), high-frequency light control.

3. LZS/LZX series (plug-in customized type)

(1) Product positioning and core features

Specially designed for customized control requirements, supporting free combination of "relay module+base+accessories", with core features including:

Multi type coverage: PT (industrial type, 28mm wide), MT (circular base, 38mm wide), RT (printed type, 15.5mm wide), suitable for different installation scenarios;

High environmental adaptability: Operating temperature -40~+70 ℃, can be used in extreme environments (such as outdoor control cabinets, high-temperature ovens);

Easy to maintain: Plug in relays can be replaced without disconnecting wires, reducing maintenance time by 80%.

(2) Product Classification and Technical Parameters

Product classification: Divided into 3 categories by structure, with the following core parameters:

Type Width (mm) Contact Quantity Terminal Type Coil Voltage Range Operating Temperature Insulation Voltage Corresponding Page Number

PT type (industrial) 28 2/3/4 conversion screw/spring terminal 24~230V AC/DC -40~+70 ℃ 250V 5/40~5/42

MT type (circular base) 38 3 conversion screw terminal 24~230V AC/DC -40~+60 ℃ 250V 5/42

RT type (printing) 15.5 1/2 conversion screw/spring terminal 24~230V AC/DC -40~+70 ℃ 250V 5/43

Special Features:

PT type: equipped with a test button (to forcibly switch relay status), LED module (24V DC version including freewheeling diode);

MT type: 11 pole circular base, suitable for special installation requirements (such as aerospace equipment);

RT type: 5mm pin spacing, suitable for printed circuit board (PCB) installation.

(3) Customized assembly and accessories

Customized assembly logic: Users can select in the order of "relay module → base → LED module → protective component", as shown in the following example:

Select relay module: PT type 3 conversion contact (LZX: PT370024, 24V DC);

Select base: Spring terminal base with logic separation (LZS: PT7874P);

Select LED module: green with freewheeling diode (LZS: PTMG0024);

Select protective component: RC component (LZS: PTMU0524, 24~60V AC).

Core accessories:

Accessory type, model, example, function description, adaptation type, corresponding page number

LED module (red) LZS: PTML0024 24V DC, with freewheeling diode, indicating relay status PT type 5/42

Fixed/pop-up bracket LZS: PT17021 auxiliary disassembly relay, suitable for dense installation of PT type 5/42

RC component LZS: PTMU0524 suppresses coil surge, 24~60V AC PT/MT/RT type 5/42

Connect comb LZS: PT170R6 (6-pole) to the same potential terminal, current capacity 10A PT type 5/42


General Technical Specifications and Safety Standards

At the end of the document, the universal connection methods, security features, and standard certifications for the entire series of products were added to ensure the compliance and security of technical applications.

1. Connection method (universal across the entire series)

Screw terminal: requires tool fastening, wire section 0.5~4mm ² (solid/multi strand with end sleeve), torque 0.8~1.2Nm (3RH2), 0.6~0.8Nm (3RQ2), suitable for large section wires and low vibration scenarios;

Spring terminal (push in):

Advantages: Tool free wiring (hard wire/soft wire with end sleeve), requires a 3.0 × 0.5mm screwdriver for wire removal, earthquake resistant (no risk of loosening), and does not require regular torque checks;

Wire cross-section: 0.5~4mm ² (solid), 0.5~2.5mm ² (multi strand with/without end sleeve);

Plug in terminal: Only supported by LZS series, suitable for scenarios that require frequent replacement of relays, with a wire cross-section of 0.75~1.5mm ².

2. Safety features and standard certification

Core standards:

IEC/EN 60947-1: General Standard for Low Voltage Switchgear;

IEC/EN 60947-4-1: Standard for contactors and motor starters;

IEC/EN 60947-5-1: Electrical standard for control circuits (including requirements for mandatory guide contacts);

IEC 60529: Standard for Degrees of Protection Provided by Enclosures (IP20/IP00/IP50).

Security features:

Finger protection: The front meets IP20 standards to prevent fingers from coming into contact with live parts;

Mandatory guiding contact: 3RH2 and 3TH4 series basic units are equipped to ensure that NO/NC contacts do not close simultaneously (essential for safe applications);

Short circuit protection: Suitable for G-type fuses (such as 3NA, 5SB) or C/B characteristic miniature circuit breakers, with a short-circuit current of 1kA (IEC 60947-5-1).

3. General requirements for installation and maintenance

Installation position: Vertical installation (base facing up), when installing 3TH4 series AC type on the side, a 5mm gap should be left (to prevent overheating);

Wiring specification: Separate the wiring of coils and contact circuits to avoid electromagnetic interference;

Maintenance cycle: Check the terminal fastening status (screw terminals) and contact wear every 6 months (measured by LED indicator or multimeter).


Summary and Core Values

This document serves as the authoritative technical manual for Siemens SIRIUS series switchgear, with core values reflected in:

Technical integrity: covering the entire series of contactor relays and coupling relays, with detailed parameters (including size, current, and lifespan), clear selection logic, and can directly guide engineering design;

Targeted application: classified according to "compact → multipole → industrial → narrow design → customized", suitable for different installation spaces and scene requirements;

Safety compliance: Clarify standard certification and safety features to help users avoid electrical safety risks;

Maintenance convenience: Detailed list of accessory system and maintenance specifications to reduce later operation and maintenance costs.

image.png

  • OEMAX NX-CPU700P PLC Controller
  • OEMAX NX-BASE10 PLC Backplane
  • OEMAX NX-AO4C 4-Channel Analog Output Module
  • OEMAX NX-AI8C 8-Channel Analog Input Module
  • OMACO GF0-57CQD-002 Industrial Control Module Precision Automation
  • OPTIMATE OP-620 Industrial Automation Control Module
  • OPTIMATE OM1510 Industrial Control Module Performance Solution
  • OPTO 22 SNAP-IDC5D Digital Input Module for Automation
  • OPTO 22 SNAP-AITM-2 Thermocouple Module
  • ORIENTAL A4722-9215KM Cooling Fan
  • ORIENTAL MOTOR 2GK180K Gearhead Specifications
  • OSRAM DULUX L 36W 840 865 Lamp Specification
  • OTHER FLASH SERIES 2 Memory Module Data
  • OVATION 1X00458H01 Control Module Specification
  • Emerson Ovation 1C31157G02 Event Sequence Module
  • Emerson Ovation 5X00070G04 Analog Input Module
  • OXIDE 0020-31655 Industrial Controller
  • ABB FAU810 C87-11006 / C10-12010 Flame Analyzer
  • Pilz PSSu E F 4DI Safety Input Module
  • Pepperl+Fuchs KFD2-UFC-1.D Frequency Converter
  • Pacific Scientific VDE0530-S1 Stepper Motor
  • Pacific Scientific 6410-001-N-N-N Stepper Drive
  • PACIFIC LA23GCKC-1Y Servo Motor Reliable Automation Motion Solution
  • PACIFIC LA23GCKX-P500A Servo Motor Advanced Industrial Motion Control
  • PACIFIC LA23GCKC-P500A High Precision Servo Motor for Industrial Automation
  • Pacific Scientific E32NCHA-LNN-NS-00 Hybrid Stepper Motor
  • Pacific Scientific SCE903A3-002-01 Servo Drive
  • Pacific Scientific 6410-024-N-N-N Stepper Motor Drive
  • PALCLEAN JD-BXG Industrial Control Module
  • Panametrics 704-673-20 Ultrasonic Flow Meter
  • Panasonic MSD043A1XX AC Servo Driver
  • Panasonic KX-FT936CN Plain Paper Fax Machine
  • Panasonic DL-1109CWS Electric Bidet Toilet Seat
  • PACIFIC SCIENTIFIC 33VM52-000-29 LDA-196-1000CE Servo Motor Controller
  • PACIFIC LA23GCKC-1G Linear Actuator Specifications
  • PACIFIC PC3406AI-001-E Stepper Controller Manual
  • PACIFIC SCE904AN-002-01 Servo Drive Analysis
  • PACIFIC 6445-001-K-N Digital Servo Drive Details
  • PACIFIC SCIENTIFIC R43HCNA-R2-NS-VS-00 Motor Data
  • Pacific Scientific H32NCHA-LNN-NS-00 Hybrid Motor Performance
  • ABB DSAI130DK01 3BSE020828R1 Analog Input Module
  • Parker 466966-0001-3820 Industrial Component Data
  • PARKER ZETA6104 Microstepping System
  • PARKER COMPAX 2500S/F3 Servo Drive Manual Details
  • PARKER CX-DH Indexer Drive Technical Specifications
  • PARKER 6K8 Motion Controller Features and Specifications
  • PARKER EVM32-BASE I/O Module Base Technical Specification
  • ABB Pb PN-112718 Digital Input Module
  • Pb PN-45734 PN-73899 Industrial Automation Module
  • Control Techniques Pb PN-40856 Industrial Control Module
  • Pb PN-104412 4002910956 Industrial Control Module
  • Siemens Pb PN-41513 Industrial Ethernet Module
  • Pelco PA30-0065-00-A1 PTZ Decoder Module
  • Pentek FILTER 3F11 800000919 Pleated Filter Cartridge
  • Pepperl+Fuchs RSD-TI-EX8 Temperature Input Module
  • PERITEK AC7-00712-1113 Industrial Interface Module
  • PFEIFFER EVR116 Vacuum Control Module
  • Pepperl+Fuchs RSD-CI-EX8 Hazardous Area Interface Module
  • PEPPERL+FUCHS 2108HAT Intrinsic Safety Barrier Module
  • Philips 958481320201 PROC+ Processing Unit
  • Philips 958481321300 PSB Power Supply Board
  • Philips 958481321220 PD208 Power Module
  • PHILIPS 958481321200 PD216 Control Module
  • PHILIPS 958481320201 PROC PLUS Control Module
  • Philips 958481320400 PIF Interface Module
  • Philips 958481320100 LCB Control Board
  • PHILIPS 958481223220 Industrial Control Module
  • PHILIPS 958481223223 Industrial Control Module
  • PHILIPS 958481321300 Industrial Control Module
  • PHILIPS SCM040 Digital Output Synchronization Module
  • PHILIPS DSI020 Data Storage Interface Module
  • PHILIPS OPM010 Optoelectronic Control Module
  • PHILIPS VBM010 Industrial Automation Module
  • PHILIPS VBM030 Turbine Supervisory Instrumentation
  • PHILIPS PR1613 Industrial Control Module
  • PHOENIX PATG1/23 1013847 Ground Terminal Block
  • Phoenix Contact IB ST 24 AI 4/SF Analog Input
  • Phoenix Contact OPC5315-004-AB Industrial PC
  • Phoenix Contact UMK-SE11.25-1 Side Element
  • PHOENIX 2961192 Relay Module
  • PHOENIX IB ST ZF 24 AI 4/SF Analog Input Module
  • Phoenix Contact PLC-BSC-24DC/21 Relay Base
  • Phoenix Contact UK6N Feed-Through Terminal Block
  • Phoenix Contact UK4-T Disconnect Terminal Block
  • Phoenix UK3N Screw Terminal Block
  • Phoenix QUINT-PS-100-240AC/10 Power Supply
  • Phoenix QUINT PS-100-240AC/24DC/10 Power Supply
  • Phoenix UT 6-HE SI Surge Protection Terminal Block
  • Phoenix UT 4-MTD Feed-through Terminal Block
  • Phoenix UT 4-HE SI Surge Protection Terminal Block
  • Phoenix IBS 24BK-I/O-T Bus Coupler
  • Phoenix Contact HDFK4 High-Current Terminal Block
  • PHOENIX ST-SI-UK4 Fuse Terminal Block
  • PHOENIX FLMC10BASE-T/FO G850 Fiber Media Converter
  • PHOENIX CONTACT QUINT-PS-100-240AC/24DC/40 Power Supply
  • PHOENIX CONTACT QUINT-DIODE/40 Redundancy Module
  • Phoenix Contact 2884208 Wireless I/O MUX
  • Photonetics 3646 HE 1540 Tunable Laser Source
  • PI C-663.12 Mercury Multi-Axis Step Motor Controller
  • PI C-663.10 Mercury Step Motor Controller
  • Pillar CB6687-2L Industrial Communication Board
  • Pilz DE-106712 A.F.051.5/01 Safety Module
  • Pilz 680003 Safety Relay Module Set
  • Pilz 301140 PNOZ X3 Safety Relay
  • Pilz P1U-1NB Safety Relay
  • Pioneer PM3398B-6-1-3-E Power Supply
  • Pioneer Magnetics PM3326B-6-1-2-E Power Supply
  • Pioneer Magnetics HYRSP-1500-56 Power Supply
  • Pioneer Magnetics PM3398B-6-1-3-E Power Supply
  • Pioneer Magnetics PM3328BP-6 Power Supply
  • Potter & Brumfield SDAS-01-7Y2S1024 Relay
  • Powec PMP10.48 SIC High-Efficiency Rectifier
  • Powerbox PU200-31C Industrial DC-DC Converter
  • PIONEER MAGNETICS PM3398BP-6-1-3-E Power Supply Module
  • PIONEER MAGNETICS PM1253AL-6-3-Z03 Power Supply Module
  • Powerex PD411811 Rectifier Diode Module
  • Power-One MAP55-1024 AC-DC Power Supply
  • ProSoft MVI56-MDA4 ControlLogix Multi-Protocol
  • POLYSPED PRD2-200 Industrial Drive Module
  • P-OPEN P-OPEN-P4-150 PAC-OP150 Operator Panel
  • ABB Processor 958481321210 350211080320 Rugged CPU
  • ABB Processor 958481320201 350211080460 Safety CPU
  • ABB Processor 958481321200 350211080320 CPU Module
  • ABB Processor 958481321220 350211080320 CPU Module
  • ABB Processor 958481320100 350211080090 CPU Module
  • Pro-Face PL5901-T42-24V HMI Touch Panel
  • PROFIBUS PB3-VME-1-E V1.2.2 Interface Card
  • PROMESS 850040060P Force Displacement Monitor