SynView Software
SynView enables a simple and quick commissioning of Synchrotact 5 equipment. the software runs under Microsoft ® Windows™ 95, 98, 2000, nt or XP and has German, English or French language interfaces. the program can also be used during operation, for example to display the actual values in order to follow the synchronization progress
Main functions of SynView program
Parameters setting, using a simple and user-friendly parameter setting display
display of actual values, like Synchroscope, voltage and frequency with real-time data
Transient recorder displays the recorded data, thus a separate recorder during commissioning is not necessary
Event and error logging in clear text with time stamp for the last 256 events
Product Model Classification and Technical Parameters
SYNCHROTACT ® The 5 series includes 6 core models, each with clear positioning and differentiated parameter design, suitable for different installation scenarios and functional requirements:
(1) Model classification and core positioning
Model core positioning operation mode supports core application scenarios
SYN 5100 Synchrocheck only supports monitoring, in conjunction with manual parallel monitoring of small power stations and simple substations
SYN 5200 advanced function synchronization checker only supports monitoring, with more comprehensive functions for scenarios that require higher monitoring accuracy
SYN 5201 Single Channel Automatic Synchronization Equipment Automatic+Manual (Parallel) Hybrid Operation of Automatic/Manual for Small and Medium sized Power Plants
The SYN 5202 dual channel automatic synchronization system is mainly automatic and supports automatic synchronization of large power stations and hub substations through manual bypass
SYN 5302 redundant dual channel automatic synchronization system is fully automatic, supporting redundant switching between main power stations and core substations (high safety requirements)
SYN 5500 multi parallel point connection auxiliary equipment has no independent operation function, only auxiliary connections need to be connected to multiple parallel points for centralized control scenarios
(2) Key technical parameters
1. Structure and installation parameters
Model, installation method, key dimensions (W × H × D), panel opening size (W × H), weight
SYN 5100 rail buckle installation 205 × 128 × 82 mm -0.3 kg
SYN 5200 panel installation 221 × 163 × 220 mm 222 × 164 mm 4.0 kg
SYN 5201 panel installation 221 × 163 × 220 mm 222 × 164 mm 4.0 kg
SYN 5202 panel installation 221 × 163 × 220 mm 222 × 164 mm 4.0 kg
SYN 5302 panel installation 442 × 154 × 220 mm 443 × 155 mm 8.0 kg
SYN 5500 rail buckle installation 381 × 128 × 50 mm -1.4 kg
2. Electromagnetic compatibility (EMC) and compliance parameters
The equipment strictly follows international standards to ensure stability and compliance in complex electromagnetic environments
Emission standards: Conducted emissions comply with CISPR 22 Class B, radiated emissions comply with CISPR 11 Class A Group 1, and meet the requirements of electromagnetic interference control in industrial environments;
Immunity standard:
electromagnetic fields:IEC 61000-4-3(80-1000 MHz,10 V/m)、IEC 61000-4-6(0.15-80 MHz);
Transient interference: IEC 61000-4-4 (± 4 kV fast transient), IEC 61000-4-5 (± 1 kV/± 2 kV surge voltage);
Voltage sag: IEC 61000-4-11 (30% sag of 10 ms, 60% sag of 100/1000 ms,>95% sag of 5000 ms);
Pulse disturbance: IEC 60255-22-1 (1 MHz common mode/differential mode 2.5 kV);
Compliance Directive: Compliant with the Low Voltage Directive (73/23/ECC, EN 60950), Electromagnetic Compatibility Directive (89/336/ECC, IEC 61000-6-4/6-2), CE certification, and can be used in compliance in the European Union and most parts of the world.

Email:wang@kongjiangauto.com