The GE T60UJ3HKHF8NH6 is a high-performance transformer protection relay from the Multilin T60 series, designed to provide comprehensive protection for power transformers in utility, industrial, and commercial applications. This relay combines advanced differential protection with a full suite of backup protection functions, metering, and communication capabilities. The T60 is engineered to meet the demanding requirements of critical transformer installations where reliability and security are paramount.
Transformer differential protection with harmonic restraint
Phase and ground overcurrent protection (ANSI 50/51)
Thermal overload protection with transformer modeling
Voltage protection functions (ANSI 27, 59, 81)
Sudden pressure and overfluxing protection
Breaker failure protection
The T60UJ3HKHF8NH6 provides advanced transformer differential protection that is essential for detecting internal transformer faults. The relay features harmonic restraint to prevent false tripping during transformer energization and inrush conditions. Second harmonic blocking is configurable to distinguish inrush current from fault currents. Fifth harmonic blocking is available for overexcitation conditions. The differential protection can be configured for two-winding or three-winding transformers, with flexible CT ratio matching and vector group compensation.
Comprehensive backup protection ensures transformer security even in the event of primary protection failure:
Phase overcurrent protection with selectable time-current curves
Ground overcurrent protection for sensitive earth fault detection
Voltage protection including overvoltage, undervoltage, and overfrequency
Thermal overload protection based on transformer load current
Sudden pressure relay input for rapid fault detection
Overfluxing protection for voltage/frequency ratio monitoring

Power Supply: 110-250 V DC or 100-240 V AC
Current Inputs: Up to 12 CT inputs for multiple windings
Voltage Inputs: 4 voltage inputs for bus and transformer monitoring
Digital Inputs: 16 configurable
Relay Outputs: 16 form-C contacts
Communication: RS-485 Modbus RTU, Ethernet, IEC 61850
Display: Large graphical LCD with user interface
Operating Temperature: -40°C to +85°C
Protection Rating: IP40 (front panel)
The T60 provides extensive metering and monitoring capabilities for transformer and system analysis:
Three-phase currents and voltages for all monitored windings
Differential current monitoring for internal fault detection
Transformer load current and load loss calculation
Active and reactive power measurements
Harmonic analysis including total harmonic distortion
Sequence components for unbalance detection
Transformer temperature estimation
The T60UJ3HKHF8NH6 supports a comprehensive suite of communication protocols for integration with modern substation automation systems. Standard protocols include Modbus RTU and TCP, DNP 3.0, and IEC 60870-5-103. Optional IEC 61850 support enables integration into next-generation substation automation architectures with GOOSE messaging and SCL configuration. The relay can simultaneously support multiple protocols, providing flexibility for diverse communication requirements.
The relay incorporates advanced diagnostic capabilities including waveform capture, event recording, and oscillography. Waveform capture records pre-fault and post-fault current and voltage waveforms for detailed fault analysis. The event recorder stores time-stamped records of all protection operations, parameter changes, and system events. Sequence of events recording enables reconstruction of fault sequences with high-resolution time stamps.
The GE T60UJ3HKHF8NH6 is suitable for transformer protection in critical applications:
Power transformers in utility substations
Generator step-up transformers in power plants
Industrial facility main transformers
Renewable energy interconnection transformers
Railway traction transformers
Large distribution transformers
The T60 features a large graphical LCD display with intuitive menu navigation, providing access to measured values, protection settings, and diagnostic information. Configuration is performed using GE Multilin configuration software, which provides advanced tools for setting protection parameters, defining logic schemes, and managing configuration files. The software supports offline configuration, enabling setup before relay installation.
The T60UJ3HKHF8NH6 complies with IEC 60255, ANSI C37.90, and IEEE C37.91 standards for protective relays. It meets CE, UL, and CSA requirements for industrial control equipment. The relay is manufactured under ISO 9001 quality management systems and is designed for long-term reliability in demanding substation environments.