The Lauer LCA200 variant 022/581 is a high-performance operator terminal featuring a 10.4-inch TFT color display with resistive touch. Designed for demanding industrial environments, it offers robust construction, extensive communication options, and powerful visualization capabilities. This terminal is suitable for complex machine control, process monitoring, and data acquisition applications in manufacturing, packaging, and material handling industries.
Display: 10.4-inch TFT, 800 x 600 pixels (SVGA), 16.7 million colors, LED backlight, 350 cd/m² brightness, 600:1 contrast ratio, viewing angle 80°/80°/70°/70°.
Touchscreen: 4-wire resistive, 1 million actuations, anti-glare coating.
Processor: ARM Cortex-A8, 800 MHz, 512 MB DDR3 RAM, 256 MB NAND flash (expandable via microSD).
Interfaces: 1 x RS232, 1 x RS422/485, 1 x Ethernet 10/100, 2 x USB 2.0 host, 1 x USB device, 1 x microSD slot, 1 x CANopen (optional).
Power Supply: 24 V DC (18–30 V), consumption 12 W, with surge protection.
Operating Temperature: 0 °C to 50 °C.
Storage Temperature: -20 °C to 70 °C.
Humidity: 10% to 90% non-condensing.
Protection: Front IP65, rear IP20.
Mounting: Panel mount, cutout 280 x 210 mm, depth 55 mm.
Weight: 2.5 kg.
Real-time clock with battery backup.
Buzzer and status LEDs.
The LCA200 supports a wide range of communication protocols including Modbus RTU/TCP, Profibus DP (optional), CANopen, Ethernet/IP, and Siemens S7. It includes a built-in web server for remote diagnostics, data logging to USB or microSD, and comprehensive alarm management. Configuration is performed using Lauer Configurator Pro, which provides a rich library of graphical objects, trend charts, recipe handling, and multi-language support. The panel supports up to 10 user levels with password protection.
Additional features include screen saver, adjustable backlight dimming, and a watchdog timer for automatic system reset. The Ethernet port supports DHCP and static IP addressing, and the USB ports allow connection of external storage or peripherals.
Mount the panel in a panel cutout using the supplied clips and gasket. Connect the 24 V DC power supply with a 1.5 A fuse. For RS485, use shielded twisted-pair cable with 120 Ω termination resistors. For Ethernet, use CAT5e cable. Ensure proper grounding and avoid routing signal cables parallel to power lines. Provide at least 60 mm clearance behind the panel for ventilation and cable connections.
Indoor industrial use, temperature 0–50 °C, humidity<90% non-condensing. Vibration tolerance 0.5 g (10–150 Hz), shock 10 g (11 ms). Backlight lifetime 50,000 hours.
Machine tool control, packaging lines, printing presses, textile machinery, and process control systems.
CE, UL, cUL certified. RoHS compliant. Meets EN 61000-6-2 and EN 61000-6-4.
Available with optional CAN, Profibus, or Ethernet/IP modules. Extended temperature range and higher brightness options available.